HELVAR SA-IR-PROG Manual Download Page 2

SA-IR-PROG

Data is subject to change without notice. More information at: www.helvar.com

T13 142 1A 07.11.2011 2/2

Programming 

Preset 

functions 

0

 

1

 

2

 

3

 

UHS5 Handset Graphics 

Description 

 

Button Activation 

 

 

On / Raise 

On 

Raise 

 

 

 

Turn lights on or to raise lights. 

Off / Lower 

Off 

Low er 

 

 

 

Turn lights off or to lower lights. 

Walk test 

On 

Off 

 

 

 

When set to On this causes a red LED to flash on the sensor 

when it detects mov ement. Use this f eature to check f or 

adequate sensitiv ity  lev els. 

Time Out 

(Time 

adjustment) 

1, 10 & 

20 

minutes 

5, 15 & 

30 

minutes 

10 

seconds 

 

 

Once the detector is turned on, this v alue sets how long the 

lights will stay  on once mov ement has ceased. 

Lux on 

level 

(Switch 

level on) 

2, 5 & 7 

4, 6 & 9   

 

 

Lux lev el setting to prev ent the luminaires being switched on if  

the ambient light lev el is sufficient (adjustable between 1  

and 9). The luminaires will alway s be switched on at lev el 9.  

Light Level 

 

 

2 (200) 

5 (500) 

7 (700) 

4 (400) 

6 (600) 

9 (900) 

 

Sets a target light lev el to be maintained by the lighting system.  

Lux off 

level 

(Switch 

level off) 

2, 5 & 7 

4, 6 & 9   

 

 

Lux lev el setting to switch the luminaires off during occupancy  if 

the ambient light lev el goes abov e the setting (adjustable 

between 1 and 9). Lev el 9 will alway s keep the lights on. This 

setting can be used for “window row switching”.

 

Sensitivity 

1, 5 & 9 

3, 6 & 8   

 

 

Sensitiv ity  lev el f or detecting mov ement. 

1 = low sensitiv ity  

9 = high sensitiv ity  

Defaults 

 

 

 

 

Returns the unit to the def ault settings. 

Burn-in 

50 

100 

 

 

Determines how long the output will be at 100% so that lamps 

‘burn-in’. The ’burn-in’ time is not aff ected by power supply  

interruptions.  

Presence / 

Absence 

Presence  Absence   

 

 

Presence mode allows the output to turn on when mov ement is 

detected and off  when mov ement ceases. Absence mode 

allows the output to turn off when mov ement ceases, but must 

be manually  turned on f irst. 

Preset PRS 

 

 

 

2 presets f or Presence mode. 

See Product Guide for device to 

be programmed 

Preset ABS 

 

 

 

2 presets f or Absence mode. 

See Product Guide for device to 

be programmed 

Shift 

 

 

 

 

 

Use this button to select the settings in red and blue signif ied 

by the ‘Shif t 1’ and ‘Shift 2’ LEDs 

Number of Shift key presses 

SHIFT  1  SHIFT  2 

SHIFT  1  SHIFT  2 

SHIFT  1  SHIFT  2 

SHIFT  1  SHIFT  2 

Programmer Graphics

Reviews: