HELVAR DIGIDIM EnOcean 434 Installation Manual Download Page 2

2

Helvar 434 EnOcean Gateway: Installation Guide

Set up EnOcean Gateway using Designer

1. Discover the Gateway in Designer

•  Ensure the PC is connected to the lighting router 

(e.g. Helvar 920) controlling the lighting network.

•  Run Designer software and connect to the 

appropriate workgroup.

•  ‘EnOcean Gateway 434‘ now appears in the Device 

Tree, under one of the connected DALI subnets.

Note:

 You cannot put the Gateway in a group. You can 

group the buttons of the switch units (when the switch 

unit is paired with the Gateway) .

2. Put the Gateway in Learning Mode

•  In Designer’s Device Tree, click ‘EnOcean Gateway 434’.
•  In the Properties window, set ‘Learning Mode’ either 

to ‘Top is Off’, or to ‘Top is On’. If you are not going 

to use these default settings, choose either mode. 

In Learning Mode, the status LED will flash red at 

intervals of 1.25 s.

Note:

 The Gateway cannot be used to control the lights 

while in Learning Mode.

3. Pair the Switch Unit with the Gateway

•  On the EnOcean switch unit, press the left button up 

or down (dual rocker switch) or the up or down button 

(single rocker switch). Make sure the switch is within 

signal range of the Gateway unit.

Helvar Router

(905 / 910 / 920)

esigner

          

Ethernet

DALI

Default EnOcean switch unit settings (Designer)

Dual Rocker Switch

Single Rocker Switch

 

Top is On

Top is Off

Top is On

Top is Off

1

2

3

4

1:

Scene 1.1 (On)

Scene 1.15 (Off)

3

4

1:

NOT USED

NOT USED

2:

Scene 1.15 (Off)

Scene 1.1 (On)

2:

NOT USED

NOT USED

3:

Scene 1.1 (On)

Scene 1.15 (Off)

3:

Scene 1.1 (On)

Scene 1.15 (Off)

4:

Scene 1.15 (Off)

Scene 1.1 (On)

4:

Scene 1.15 (Off)

Scene 1.1 (On)

•  The Gateway detects the switch. The status LED flashes 

green. After a few seconds, the switch appears in the 

Device Tree.

Note: 

If the switch does not appear in the Device Tree, 

check DALI network activity in the DALI History window 

(View > History > 

DALI Subnet

).

To pair other switches (maximum 20 per Gateway), repeat 

step 3.

4. Turn off Learning Mode

•  In the Device Tree, click ‘EnOcean Gateway 434’ and 

select ‘Properties’.

•  In the Properties window, set ‘Learning Mode’ to ‘OFF’. 

The status LED will stop flashing red.

Note:

 The Gateway, now out of Learning Mode, can send 

commands to the lighting network.

5. Group Buttons and Configure Button Actions 

If you are not going to use the default switch unit settings, 

configure the button actions using Designer (see the “Device 

Configuration” section of the Designer Help files).

The Gateway and switches should now be operational. 

Summary of Contents for DIGIDIM EnOcean 434

Page 1: ...all as far away as possible from the surface of metal objects Note Install EnOcean switches so that obstructions between the switches and gateway are minimised 1 Isolate the DALI network cable from power Twist and remove the housing mounting Remove the knockouts as required 2 Thread the DALI cable through the housing mounting and screw the housing mounting in place Remove the DALI connector block ...

Page 2: ...thin signal range of the Gateway unit Helvar Router 905 910 920 esigner Ethernet DALI Default EnOcean switch unit settings Designer Dual Rocker Switch Single Rocker Switch Top is On Top is Off Top is On Top is Off 1 2 3 4 1 Scene 1 1 On Scene 1 15 Off 3 4 1 NOT USED NOT USED 2 Scene 1 15 Off Scene 1 1 On 2 NOT USED NOT USED 3 Scene 1 1 On Scene 1 15 Off 3 Scene 1 1 On Scene 1 15 Off 4 Scene 1 15 O...

Page 3: ... sure the switch is within signal range of the Gateway unit The status LED flashes green To confirm that the Gateway has detected the switch check that a new row appeared in DALI history assigned to the Gateway address One press is enough to pair the switch with the gateway You can press the buttons more times to check the signal range limits of the switch unit Note Paired Switch Units will appear...

Page 4: ...to 50 C Relative Humidity Max 90 non condensing Storage Temperature 10 C to 70 C Conformity and Standards EMC Emission EN 61000 6 3 EMC Immunity EN 61547 Safety EN 60950 R TTE 1999 5 EC ARIB STD T108 434 R2 Wireless protocol ISO IEC 14543 3 10 Environment Complies with WEEE and RoHS directives Status LED Status LED red or green In normal operation the LED remains unlit The red LED flashes to indic...

Reviews: