background image

15 

1) A 

 Air sensor: Regulation (heating control) is based on the SET POINT applied to the internal room air temperature 

sensor.

 

 

2) AF 

 Air sensor plus floor sensor: Regulation is based on SET POINT applied to the internal room temperature sensor 

but also controlled by the floor temperature sensor ensuring that the floor temperature remains within the set limits. The 
lower floor temperature limit is specified in Parameter 14 (FtL) and the high temperature limit in Parameter 15 (FtH).

 

 

3) F 

 Floor sensor: Regulation is based on the SET POINT applied to the external floor temperature sensor.

 

 

4) FA 

 Floor sensor plus air sensor: Regulation is based on SET POINT applied to the external floor sensor but is also 

controlled by the internal air temperature sensor ensuring that the room temperature remains within the set limits. The 
lower air temperature limit is specified in Parameter 12 (AtL) and the higher temperature limit in Parameter 13 (AtH).

 

 

5) t 

 Time regulator: Regulation is based on the time settings for heating which will be ON during the time in Parameter 

23 (tOn) and then OFF during the time in Parameter 24 (tOf). This cycle will be repeated constantly.

 

 

6) tA 

 Time reg Air sensor: Regulation is based on the time set by Parameters 23 and 24 but also controlled by 

the internal air temperature sensor ensuring that the room temperature remains within the set limits. The air temperature 
limits are specified in Parameters 12 and 13.

 

 

7) tF 

 Time reg Floor sensor Parameters: Regulation is based on the time set by Parameters 23 and 24 but also 

controlled  by  the  floor  temperature  sensor  ensuring  that  the  floor  temperature  remains  within  set  limits.  The  floor 
temperature limits are specified in Parameters 14 and 15.

 

 

Example:

 

In FA mode the SET POINT is set to 30°C, AtL is set to 24°C and AtH is set to 27°C:

 

a)  If  floor  temperature  is  lower  than  30°C  and  the  room  temperature  is  lower  than  27°C  the  HE-HT01  will  operate  in 
HEATING mode.

 

b) If the floor temperature is higher than 30°C or the room temperature is higher than 27°C then the HE-HT01 will enter 
IDLE mode which switches off the heater.

 

c) If the room temperature is lower than 24°C the Heating Thermostat will operate in HEATING mode even though the 
floor temperature is higher than 30°C. 

d)  If  the  room  temperature  is  higher  than  27°C  the  Heating  Thermostat  will  enter  IDLE  mode  even  though  the  floor 
temperature is lower than 30°C.

 

Factory default value is 3 (F).

 

 
Caution: 

Be careful when setting the lower limitation 

 Parameters 12 (AtL) and 14 (FtL) 

 to be sure that the value is 

not too high, and it can be reached. Otherwise the HE-HT01 will stay always in HEATING mode.

 

Note:

 For safety reasons the HE-HT01 will enter IDLE mode if the floor temperature reaches 40°C despite Parameter 

settings. 

Note:

 

If there  is no  floor sensor installed, or it becomes damaged (indicated by ”  –

 

 

“ in  the “FLOOR TEMP”), the 

regulation mode (A) will be automatically selected as the source sensor. This can only be changed to 

“t” 

or 

“tA”. 

If one of 

the source sensors is selected from the list 

F

”, “

FA

”, “

AF

” 

or 

“tF”, the message “Err” will appear on the screen.

 

 
Parameter 12 

(“AtL”) –

 Air Temperature Minimum (Lowest level)

 

This Parameter is the room temperature low limit 

 reading the internal temperature sensor. This only comes into effect 

if 

FA

 or 

“tA” 

are selected as the source sensor in Parameter  11. The Parameter value can be selected from 1.0°C to 

36.0°C. Through the Z-Wave network the value of this Parameter should be x10, e.g. for 22.5°C set the value 225. The 
factory default value is 21°C (210 through Z-Wave network).

 

 

Note: 

The

 

AtL value cannot be higher than (AtH 

 1)°C.

 

 

Parameter 13 

(“AtH”) –

 Air Temperature Maximum (Highest level)

 

This Parameter is the room temperature high limit 

 reading the internal temperature sensor. This only comes into effect 

if 

FA

 or 

“t

A

 are selected as the source sensor in Parameter 11. The Parameter value can be selected from 2.0°C to 

37.0°C. Through the Z-Wave network the value of this Parameter should be x10, e.g. for 22.5°C set the value 225. The 
factory default value is 27°C (270 through Z-Wave network).

 

 

Note: 

The

 

AtH value cannot be lower than (AtL + 1)°C.

 

 

Parameter 14 

(“FtL”) –

 Floor Temperature Minimum (Lowest level)

 

This Parameter is the floor temperature low limit 

 reading the external NTC temperature sensor. It only comes into effect 

if AF or tF are selected as the source sensor in Parameter 11. The Parameter value can be selected from 1.0°C to 36.0°C. 
Through the Z-Wave network the value of this Parameter should be x10, e.g. for 22.5°C set the value 225. The factory 
default value is 18°C (180 through Z-Wave network). 

 

Note:

 The FtL value cannot be higher than (FtH 

 1)°C.

 

 

Summary of Contents for HE-HT01

Page 1: ...HEATING THERMOSTAT HE HT01 USER MANUAL for Hardware v 12 Firmware v 2 2...

Page 2: ...k 9 Adding to Z Wave network 9 Removing from Z Wave network 9 Security 9 SmartStart 9 Firmware OTA Update 10 Z Wave Plus V2 Specifications 10 Associations 11 Settings Menu 11 Settings available throug...

Page 3: ...ng it always easy to read Highly configurable with automatic safety You can select one of six operation modes with individual set points either manually or by using a Z Wave controller gateway As a sa...

Page 4: ...NTC sensors range 1k to 100k Periodic measurements from o Internal temperature sensor o External floor temperature sensor o Internal humidity sensor o Internal ambient light sensor o Energy consumptio...

Page 5: ...ve the display unit and backplate of the HE HT01 from the packaging 3 FIRST ENSURE THE POWER IS OFF at the main circuit breaker and then test the wires with a probe or multimeter to verify Insert the...

Page 6: ...xt switch On the main power at the circuit breaker see photo above The HE HT01 will start up showing the original default factory settings 8 Remove the clear protective film from the display unit and...

Page 7: ...s for Morning Daytime Evening and Night For example the Morning Schedule could be set to 22 0 C starting at 6 00 The Day Schedule could then be set to 17 0 C at 9 00 when everyone has gone to work or...

Page 8: ...from all or part of the property for a length of time The factory default ECO Set Point is 20 0 C Note In your Z Wave gateway this mode will be shown as Energy Save Heat VAC Vacation Mode Away Use Va...

Page 9: ...wn 3 The current state of the network will display in the Parameter Value position upper right It should display InC Note If E L is displayed the HE HT01 is already Excluded 4 Start the Exclusion Mode...

Page 10: ...nauthenticated or S0 Association Group Info V3 highest granted S2 Authenticated S2 Unauthenticated or S0 Multi Channel Association V3 highest granted S2 Authenticated S2 Unauthenticated or S0 Thermost...

Page 11: ...corner of the LCD The top left corner will display the Parameter Number And the top right corner will display the Parameter Value To scroll through the menu press the Heating Element button to go up...

Page 12: ...cy list below Modification is possible only while the HE HT01 is not included to Z Wave network While the device is included the Antenna Icon is shown at the bottom right corner of the LCD main screen...

Page 13: ...e from the device menu Parameter 04 LPc Energy Consumption values This Parameter allows you to check the Cumulative and Real Time Energy Consumption of the connected load Display information follows t...

Page 14: ...h IDLE state OFF when the external input is open released If Parameter value 2 the external input will operate in Toggle Switch Reverse mode if the external input is shorted the Thermostat switches to...

Page 15: ...even though the floor temperature is higher than 30 C d If the room temperature is higher than 27 C the Heating Thermostat will enter IDLE mode even though the floor temperature is lower than 30 C Fac...

Page 16: ...set the value 12 The factory default value is 0 5 C 5 through Z Wave network Time Configurations Parameter 19 tCr Time Correction by Main Controller If this Parameter value 1 and the HE HT01 is connec...

Page 17: ...142 Note In order not to increase traffic on your network it is not recommended to reduce the value of this Parameter We recommend reducing the value of this Parameter only in case of poor connection...

Page 18: ...and is received If the Basic Set command value is 0 OFF state the HE HT01 will go to Manual MAN mode and switch Off the heating element IDLE mode If the Basic Set command is value is 0xFF ON state the...

Page 19: ...70 50 2 bytes Tuesday Day temperature valueX10 200 10 370 51 2 bytes Tuesday Evening temperature valueX10 230 10 370 52 2 bytes Tuesday Night temperature valueX10 180 10 370 53 2 bytes Wednesday Morni...

Page 20: ...be sent to you EXCEPT AS MAY BE OTHERWISE PROVIDED BY APPLICABLE LAW THIS LIMITED WARRANTY IS IN LIEU OF ALL OTHER COVENANTS AND WARRANTIES EITHER EXPRESS OR IMPLIED INCLUDING WITHOUT LIMITATION ANY I...

Reviews: