3.8 Door switch
The door switch refers to the switch on the sauna door. This switch complies with the regulations laid down in
Section 22.100 of the standard EN 60335 2-53. Public and private saunas, i.e. saunas where the heater can be
switched on from outside the sauna or by using a timer, must have a door switch.
Image. 8 Door switch
3.9 Installing the sensor near a supply air vent
The sauna room air should be exchanged six times in an
hour. The diameter of the supply air pipe should be
between 50 and 100 mm.
A circular air supply vent (360°) must be
installed at least 1000 mm away from the sensor.
An air supply vent with a flow-directing panel
(180°) must be installed at least 500 mm away from
the sensor. Air flow must be directed away from the
sensor.
Installation and User Manual
SAGA ELECTRO
9
360°
1000 mm
180°
500 mm
Sensor
Sensor
Door switch
Magnet
Max 18 mm
Connection box
Min 300mm
Sensor
Contactor
Box
T2