68
P/N 240010943, Rev. C [09/07/2016]
1.4
Sequence of Operation
Operational State
User Interface Display
Explanation
If flame detected before Gas Valve
opens during ignition boiler will
lockout.
Please refer to troubleshooting guide.
Gas Valve energized to deliver air/fuel
to burner.
If flame undetected after 3 seconds
boiler will de-energize Gas Valve and
enter post purge mode for 30 seconds.
Boiler will run provided all operational
and safety devices are within limits
Refer to for more information.
Control module adjusts firing rate
according to heating demand. When
Boiler detects demand met, will enter
post purge mode then standby mode.
If simultaneous demand for Central
Heat and DHW, boiler will enter DHW
Priority Mode.
Priority mode limits amount of time
boiler can run in DHW mode to meet
CH demand.
Max DHW Priority Time setting
determines maximum time allowed for
DHW heating mode.
Please refer to section Appendix A
section 1.5 for more information.
Flame
Detected?
Gas Valve
Energized
Flame
Detected?
Heat Demand
Met?
DHW
Priority
Mode
Simultaneous
DHW + CH
Demand?
No
Yes
No
Yes
See Max DHW
Priority Time
Setting
No
After 2 seconds
After 3 seconds
No
30 second
post purge
Yes
Yes
Lockout
Error A21
Note:
Lockout A01
after allowed
ignition trials
are exceeded
APPENDIX A - CONTROL MODULE