34
P/N 240010943, Rev. C [09/07/2016]
FIGURE 9 -2 User Interface
9.3
Program Boiler Control
Key
Description
- Manual Lockout Reset
- Enter/Exit user menu
- Go to previous screen
- Select a menu item
- Confirm new parameter value
- Scroll up to next menu item
- Increase value
- Scroll down to next menu item
- Decrease value
Boiler is factory programmed with following factory
default settings, Table 10.
Parameters can be adjusted to suit particular application
using the user interface. See figure 9-2.
Detailed explanation of each can be found in Appendix A
- Control Module.
Record new values in space provided for furture reference,
in event of factory default parameters are changed.
Control Parameter
Factory Default
Setting
Setting Range
*Actual
Parameter
Settings
°F
°C
°F
°C
User
Menu
Settings
Central Heating Setpoint
140°F
60°C
104-195°F 40-91°C
DHW Setpoint
180°F
82°C
104-195°F 40-91°C
Temperature Units
°F
°F/°C
Installer
Menu
Boiler
Configuration
Boiler Address
0
0-15
Low Water Cutoff
External
N/A
Pump Mode
0
0 & 4
Service Reminder Status
On
ON/OFF
Service Reminder Days
365 Days
1- 999 Days
CH Settings
CH Mode
1
0, 1, 2, 3
Warm Weather Shutdown
70°F
21°C
35-100°F
2-38°C
Reset Curve Design Temperature - Boiler
180°F
82°C
60-195°F 40-91°C
Reset Curve Design Temperature - Outdoor
25°F
-4°C
-60-32°F
-51-
25°C
Reset Curve Mild Weather Temperature - Boiler
100°F
37°C
35-120°F
2-49°C
Reset Curve Mild Weather Temperature - Outdoor
70°F
21°C
35-85°F
2-29°C
Reset Curve Boiler Minimum Temperature
70°F
21°C
40-180°F
4-82°C
Reset Curve Boiler Maximum Temperature
180°
82°C
80-195°F 27-91°C
Boost Function Temperature
0°F
0°C
0-36°F
0-20°C
Boost Function Time
20 Minutes
1-120
Maximum Power CH
100%
1-100%
DHW Mode
2
0/2
DHW Maximum Priority Time
30 Minutes
1-60 minutes
* List parameters when factory default settings are changed.
9 - START UP PROCEDURE
Table 10 - Default Parameters