Helios RM-PSW 1105KVA Instruction Manual Download Page 9

 

 

 

 

2-4  Quick hooking 

 up and testing:

 

 

 

2-4-1

 

Unpack and inspect the power inverter, check to see that the power switch in the OFF 

position.

 

 

 

2-4-2 Connect the cables to the DC input terminals on the rear panel of power inverter.   

The red terminal is positive (+) and black terminal is negative (-).   
Insert the cables into the terminals and tighten relative nut to clamp the wires securely.   
 

 

 

 

WARNING! 

You  may observe a spark when you make this connection since 
current may flow to charge capacitors in the power inverter. 
Do not make this connection in the presence of flammable fumes. 
Explosion or fire may result. 

 

WARNING! 

Make sure all the DC connections are tight (torque to 9-10 ft-lbs, 
11.7-13Nm). Loose connections will overheat and could result in 
a potential hazard.

 

   

2-3-3 Safe 

 Do not install in a battery compartment or other areas where flammable 

fumes may exist, such as fuel storage areas or engine compartments. 

 

   

2-3-4 Ventilated 

 Allow at least one inch of clearance around the inverter for air flow. Ensure 

the ventilation openings on the rear and bottom of the unit are not obstructed. 

 

   

2-3-5 Dust-free 

 Do not install the Inverter in a dusty environments where are dust, wood 

particles or other filings/shavings. The dust can be pulled into the unit when the cooling 
fan is operating. 

 

   

2-3-6

 

Close to batteries 

 Avoid excessive cable lengths but do not install the Inverter in the 

same compartment as batteries. 
Use the recommended wire lengths and sizes (Ref. point 2-6). 
Also do not mount the Inverter where it will be exposed to the gases produced by the 
battery.   
These gases are very corrosive and prolonged exposure will damage the Inverter. 

 

Summary of Contents for RM-PSW 1105KVA

Page 1: ...0 PSW2205KVA E 2U x 19 rack mount 50 PSW5KVA Series www heliosps com Email New Zealand sales heliosps co nz Australia sales heliosps com au Asia Middle East sales heliosps asia REV 22 05 2020 50 PSW24...

Page 2: ...n 7 2 4 Quick hook up and testing 8 2 5 AC safety grounding 9 2 6 Making DC wiring connections 10 2 7 Inverter operation 11 2 8 Cooling fan working code 13 3 Maintenance 13 4 Troubleshooting guide 14...

Page 3: ...Application l Power tools circular saws drills grinders sanders buffers weed and hedge trimmers air compressors l Office equipment computers printers monitors facsimile machines scanner l Household it...

Page 4: ...0VDC 20VDC 42VDC 90VDC 180VDC No load Current Draw 1 64A 0 82A 0 42A 0 24A 1 30A 0 68A 0 35A 0 18A Output Voltage Adjustment 100 120V Tune VR 200 240V Tune VR Frequency 50 60Hz 0 05 Switch Selectable...

Page 5: ...4 1 3 Mechanical Drawings...

Page 6: ...ons in this manual before installing and using this model 2 1 Front Panel Operation 2 1 1 Front view 2 1 2 ON OFF switch Please leave in the OFF position during installation 2 1 3 Function Key When se...

Page 7: ...egative Reverse polarity connection will blow internal fuse and may damage inverter permanently 2 2 4 RS 232 Connect to computer to remote control working status Alarm relay operation Voltage free con...

Page 8: ...afety hazard WARNING Shock Hazard Before proceeding further carefully check the inverter is NOT connected to any batteries and that all wiring is disconnected from any electrical sources Do not connec...

Page 9: ...nd could result in a potential hazard 2 3 3 Safe Do not install in a battery compartment or other areas where flammable fumes may exist such as fuel storage areas or engine compartments 2 3 4 Ventilat...

Page 10: ...ompletely 2 4 7 Please use a power meter accurately measure the true output R M S voltage of Inverter We use a power meter such as IDRC CP 350 or ABM 2019 to measure our product 2 5 AC Safety Groundin...

Page 11: ...ING Do not operate the power inverter without connecting it to Ground Electrical shock hazard may result 2 6 Marking DC Wiring Connections Follow this procedure to connect the battery cables to the DC...

Page 12: ...ates from an input voltage ranging from 20 to 32 VDC for 24V models 42 to 62VDC for 48V models 90 to 140VDC for 110V models 180 to 275VDC for 220V models The Inverter will indicate high and low DC vol...

Page 13: ...cause its input voltage fell below 24V 48 110 220VDC Ref point 2 7 1 2 7 10 Over temp protection indicator OTP The over temp indicator indicates that the power inverter has shut itself down because it...

Page 14: ...gy sources requirement Until output power is up to 300W the cooling fan will start to work in order to drop the inner temperature If the ventilation opening is obstructed the inverter will enter over...

Page 15: ...on l Move the television as far away from the power inverter as possible l Keep the cables between the battery and the power inverter as short as possible and twist them together about 2 to 3 twists p...

Page 16: ...al special or consequential even though caused by negligence or other fault 6 Important Safety Instructions WARNING Before you install and use your inverter be to read and save these safety instructio...

Page 17: ...klaces and watches when working with a lead acid battery A lead acid battery produces a short circuit current high enough to weld a ring or the like to metal causing a severe burn 7 Appendices A 7 1 D...

Page 18: ...N SPEC N is an integer number ranging from 0 to 9 The unit is Volt d O P voltage PPP P P is an integer number ranging form 0 to 9 The unit is Volt e O P current QQQ QQQ is a percent of maximum current...

Page 19: ...y Low 5 SPEC 4 SPEC 3 SPEC 2 SPEC 1 SPEC 0 SPEC j Stop Byte cr Example Computer Q1 cr INVERTER 208 4 140 0 208 4 034 59 9 2 05 35 0 00110000 cr Means I P voltage is 208 4V SPEC I P fault voltage is 14...

Reviews: