11
Increasing your DC cable size will help improve the situation.
Our company recommends the following cables for optimum inverter performance
Model No
Wire AWG
Inline Fuse
Also, use only high quality copper wiring and keep cable length short from 3-6 feet.
2-7 Inverter Operation:
To operate the power inverter, turn it on using the ON/OFF switch on the front panel. The
power inverter is now ready to deliver AC power to your loads.
If you are operating several loads from the power inverter, turn them on separately after the
inverter has been turned on.
This will ensure that the power inverter does not have to deliver the starting currents for all
the loads at once.
2-7-1 Controls and indicators:
The ON / OFF switch turns the control circuit in the power inverter on and off.
The Inverter operates from an input voltage ranging from :
20 to 32 VDC for 24V models
42 to 62VDC for 48V models
90 to 140VDC for 110V models.
180 to 275VDC for 220V models
The Inverter will indicate high and low DC voltage conditions as follows:
Model
DC Input over
voltage shut-down
DC Input over
voltage alarm
DC Input under
voltage alarm
DC Input under
voltage shut-down
RM-PSW245KVA/E
32VDC
31VDC
21VDC
20VDC
RM-PSW485KVA/E
62VDC
61VDC
43VDC
42VDC
RM-PSW1105KVA/E
140VDC
135VDC
95VDC
90VDC
RM-PSW2205KVA/E
275VDC
270VDC
185VDC
180VDC
Note: Inverter will automatically start operating when input returns back to normal voltage
range, as per 2-7-1
2-7-2 Output Voltage Indicator:
LED displays light on VAC as show as output Voltage value
2-7-3 Output Current Indicator
LED displays light on AMP as show as output current value
2-7-4 Output Watts Indicator
LED displays light on Watts as show as output Watts value
RM
-PSW245KVA/E
#4/0
300A
RM
-PSW485KVA/E
#2/0
200A
RM
-PSW1105KVA/E
#4
100A
RM
-PSW2205KVA/E
#6
50A