Parameter
Factory setting
User Set-
ting
Function
MSCO
-
OFF
Minimum speed cut off
|
MSCO
|
:
|
OFF
|
(factory setting)
If
“
Min. Uout
”
is adjusted (e.g. 2.0
V), than no diconnection of the out-
put takes place (does not go under
“
Min. Uout)
”
.
|
MSCO
|
:
|
-2.0 K
|
(example)
It takes place a disconnection from
Setting
“
Min. Uout
”
to
“
0
”
, if the
given difference is reached related
to the Setpoint.
At a plus value (+) before reaching
the desired value
At a minus value (-) after falling
below the desired value.
Hysteresis
|
H
|
ON /OFFs: approx.
1 K
Setting range: -10.0 K...+10.0 K
Value>Set =
n+
-
ON
Controller function
|
Value>Set = n+
|
:
|
ON
|
Cooling =
increasing modulation for increas-
ing actual value over Setpoint.
|
Value>Set = n+
|
:
|
OFF
|
Heating
= increasing modulation for de-
creasing actual value below Set-
point.
-
Parameter for selected mode not available
Installation and Operating Speci
fi
cation
ETR
Programming
L-BAL-E193-GB 1320
Part.-No.
14/20