Central ventilation unit –
KWL 200/300 W/W ET
Installation and Operating Instructions
EN
EN
8
3.3 Technical data
Technical data
KWL 200 W/W ET
KWL 300 W/W ET
Voltage/frequency
1~ 230 V~/50 Hz ±6 %
1~ 230 V~/50 Hz ±6 %
Rated current – ventilation
1.2 A
2.0 A
Rated current – preheater
4.4 A
4.4 A
Rated current – max. total
1.2 A (5.6 A incl. preheater)
2.0 A (6.4 A incl. preheater)
Electrical preheater (output)
1.0 kW (accessories)
1.0 kW (accessories)
Elec. supply line to subdistribution board
NYM-J 3 x 1.5 mm
2
NYM-J 3 x 1.5 mm
2
Max. flow rate V
max
at 100 Pa
166
m
3
/h (KWL 200 W)
193
m
3
/h (KWL 200 W ET)
275
m
3
/h (KWL 300 W)
306
m
3
/h (KWL 300 W ET)
Temperature operating range
-20 °C to +45 °C
-20 °C to +45 °C
Temperature installation area
+5 °C to +45 °C
(< 90 % RH., non-condensing)
+5 °C to +45 °C
(< 90 % RH., non-condensing)
Protection category
IP34
IP34
Protection class
I
I
Weight
37 kg (KWL 200 W)
41 kg (KWL 200 W ET)
37 kg (KWL 300 W)
41 kg (KWL 300 W ET)
Heat exchanger
Plastic
Plastic
2
T3
T1
T2
2
1
1
5
1
T6
Externe Fühler
(Raumseitige Installation)
CO2-Fühler
•
Feuchte/Temperaturfühler
•
VOC-Fühler
•
Fortluft
Zuluft
Abluft
Außenluft
Bei Verwendung eines Heizregisters, muss das Rohrsystem 0,5 m vor und nach dem Heizregister
mit temperaturbeständigem bzw. nicht brennbarem Rohr versehen werden (z.B. Wickelfalzrohr)
Abb. KWL 200/300 W Rechts
(T7)
Rücklauf
WW-Register
T4
F-AB
3
Fig. 2
Non-combustible duct (e.g. spiral duct)
Insulated ducting system IsoPipe
®
Ø125
IP 125/2000 (accessories)
Short duct connector Ø125
RVBD 125 K (accessories)
Electric or warm water heating element
EHR-R 1.2/125 oder WHR 125 (accessories)
Internal humidity sensor
T1
Intake air temperature sensor
T2
Supply air temperature sensor
T3
Extract air temperature sensor
T4
Exhaust air temperature sensor
T6
Air temperature duct sensor
KWL-LTK (accessories)
Supply air
Extract air
Intake air
Exhaust air
External sensor
(Room-side installation)
CO2 sensor
Humidity/temperature sensor
VOC sensor
Fig. KWL 200/300 W Right
Summary of Contents for easyControls 3.0 KWL 200 W
Page 37: ...Zentrales Lüftungsgerät KWL 200 300 W W ET Montage und Betriebsvorschrift DE 36 ...
Page 73: ...Central ventilation unit KWL 200 300 W W ET Installation and Operating Instructions EN 36 ...
Page 109: ...Unité de ventilation centrale KWL 200 300 W W ET Notice de montage et d utilisation FR 36 ...
Page 110: ...Unité de ventilation centrale KWL 200 300 W W ET Notice de montage et d utilisation FR 37 ...
Page 111: ...Unité de ventilation centrale KWL 200 300 W W ET Notice de montage et d utilisation FR 38 ...