7.2 Menus of Modes
4.00
-
4.01
Parameter
Factory setting
User Setting Function
INFO
Δ
p
0 Pa
0 Pa
Display actual value for differential pres-
sure
Setpoint 1
-
500 Pa
Display active Setpoint
Uout
0.0 V
0.0 V
Magnitude of the output voltage 0...10 V
EDR
0.00
0.00
software version
SETTING
only at
4.01
Setpoint 1
-
500 Pa
Setting Setpoint
Setpoint 2
-
500 Pa
Setpoint 2 active, if voltage at terminals 1, 2
Pband
-
500 Pa
Setting Pband
Min. Uout
-
0.0 V
Setting minimal output voltage
Max. Uout
-
10.0 V
Setting maximal output voltage
BASE SETUP
Mode
4.00
4.01
Mode selection
Measuring Range
1: 0...1000 Pa
2: 0...500 Pa
3: 0...300 Pa
4: 0...200 Pa
Factory setting = max. Range
Offset
0 Pa
0 Pa
Sensor offset
-
Parameter for selected mode not available
Installation and Operating Speci
fi
cation
EDR
Menu operation
L-BAL-E192-GB 1320
Part.-No.
10/17