11.1.1 Module Removal
Notice: When one or several inverter modules is/are removed, live parts become accessible. Replace module with blinds without
delay.
Inverter module is not switched off when opening the handle. The handle only hooks the module to the shelf.
Use a screw driver to release the latch of the handle.
Open the handle and Pull the module out.
Replace with new module or blind unit.
A) Use screwdriver to release the latch
B) open the cover completely
C) Use the cover as a handle to remove
the module
11.1.2 Inserting
Check module compatibility (DC Voltage!)
Use a screw driver to release the latch of the handle.
Open the handle and Push firmly until the unit is properly connected.
Close the cover and latch in position.
A) Slide the module in
B) Push firmly till the connection is
properly engaged
C) Close the cover and latch the module
in place if too hard redo step B
Once the module is properly insert and locked it will restart automatically and the load will be transferred from the by-pass
module to the inverter. The sequence might take 10 to 40 seconds.
29
– Bravo ST 230 VAC– User manual – v7.3
Inserting/removing/replacing modules