  Series battery connection: When using multiple batteries in series, all 

batteries must be equal in voltage and amp hour capacity, and the sum 

of their voltages must be equal to the voltage of INVERMAX Nominal 

Input Voltage (Apply to INVERMAX 1500/2000) 

 

 

z

  Parallel battery connection: When using multiple batteries in parallel, 

each battery’s voltage must be equal to the voltage of INVERMAX 

Nominal Input Voltage (Apply to INVERMAX 500/1000 extend the 

backup time) 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 

Summary of Contents for INVERMAX 1000

Page 1: ...USER MANUAL ...

Page 2: ... must be rated for 75o C or higher and should be no less than 10AWG gauge The inner diameter of the copper ring terminal which is used to connect battery cables to INVERMAX DC terminals should be no less than 6mm 8 Be extra cautious when working with metal tools around batteries Short circuiting the batteries could cause an explosion 9 Read the battery manufacturer s installation and maintenance i...

Page 3: ... charges the battery set via charging system In UPS mode INVERMAX automatically convert battery energy into AC power for backing up the connected devices Features z Automatic line to battery switchover z Selectable Input voltage ranges z High efficient DC to AC conversion minimizing energy loss z Rack Tower design for flexible placement z Built in enhanced charger z Intelligent 2 stage charger con...

Page 4: ...urn on automatically and works in mains mode or inverter mode according to input AC source s status When press this button again INVERMAX will turn off automatically Mains Mode LED The green LED will blink or light steadily when power mains is normal Note The green LED blinks every 2 seconds to indicate that battery capacity is not full enough and battery is being charged by high rate Inverter Mod...

Page 5: ...nal 2 Input Breaker 3 AC Input Connector Three station Terminal Block 4 Output Receptacle s 5 Input Voltage Range Selector Input voltage range is defined in specification chapter and output voltage is the same as input voltage in mains mode A Select Narrow setting for general electrical appliance If you select this mode the INVERMAX operating voltage in Line mode is within ...

Page 6: ... you select the Wide mode and connect the computer to the output of INVERMAX the computer may reboot if the input voltage is too low to be accepted In addition the long transfer time will happen when power failure makes the computer reboot Battery Connection Step 1 Pinch the bottom of DC input cover and Open it See Figure 4 Step 2 Following battery polarity guide located near battery terminal Plac...

Page 7: ... INVERMAX 500 1000 z For the user operation safety we strongly recommend that you should isolate the battery terminals before you start to operate the unit Please refer to below instruction for further information If you parallel more batteries to extend the backup time please make sure that you already use tapes to isolate the rest battery terminals before you start to operate the unit ...

Page 8: ... and the sum of their voltages must be equal to the voltage of INVERMAX Nominal Input Voltage Apply to INVERMAX 1500 2000 z Parallel battery connection When using multiple batteries in parallel each battery s voltage must be equal to the voltage of INVERMAX Nominal Input Voltage Apply to INVERMAX 500 1000 extend the backup time ...

Page 9: ...hat AC source is disconnected before attempting to connect AC to INVERMAX Step 2 Connect the hot wire black brown of AC input cable to the HOT IN terminal Step 3 Connect the neutral wire white blue of AC input cable to the NEU IN terminal Step 4 Connect the ground wire green of AC input cable to the GND IN terminal Step 5 Tighten screws to affix wires in terminal block Step 6 Cover up the AC Input...

Page 10: ... input connection Mains normal but works in inverter mode 2 Input protector is effective 2 Reset the input protector Alarm buzzer beeps continuously 1 Overload 1 Verify that the load matches the capability specified in the specs 1 Overload 1 Remove some non critical load Back up time is shorten 2 Battery voltage is too low 2 Charge battery for 8 hours or more If any abnormal situations occur that ...

Page 11: ...arge Protection 14 5V 0 3V charger stops and fault 29V 0 6V charger stops and fault TRANSFER TIME Typical 8ms Typical AC to AC 95 EFFICIENCY DC to AC 80 AC Mode Green lighting Battery Mode Yellow lighting Battery Charging Mode Green flashing every 2 seconds Overload Red flashing every 0 5 second INDICATOR Fault Red lighting Low Battery at Battery Mode Sounding every 2 seconds Overload Sounding eve...

Reviews: