11 Electrical connection
Digital Governor Basic System PANDAROS III
41
The allowed length and necessary cross-sections of the cables to connect are as follows:
L 1
Power supply
max. 15 m
2 x 2.50 mm²
L 2.1 Actuator feedback
3 x 0.75 mm², shielded
L 2.2 Actuator drive
up to 10 m
2 x 2.50 mm²
over 10 - 20 m
2 x 4.00 mm²
L 3.1 Setpoint potentiometer
3 x 0.75 mm², shielded
L 3.2 4 - 20 mA input
2 x 0.75 mm²
L 3.3 0 - 5 V
2 x 0.75 mm², shielded
L 3.4 Synchronizer
2 x 0.75 mm², shielded
L 3.5 Load measuring unit
2 x 0.75 mm², shielded
L 4
Magnetic pick-up
2 x 0.75 mm², shielded
L 5.1 Temperature sensor
2 x 0.75 mm²
L 5.2 Boost sensor
2 x 0,75 mm²
L 5.3 Oil pressure sensor
2 x 0.75 mm²
L 6.1 Engine stop
1 x 0.75 mm²
L 6.2 Increase speed
1 x 0.75 mm²
L 6.3 Decrease speed
1 x 0.75 mm²
L 6.4 other switch functions
1 x 0.75 mm²
(the switches have to be supplied with battery plus)
L7
Error message
1 x 0.75 mm²
(the error lamp has to be supplied with battery plus, ground is switched)
L 13 CAN communication with DGM 02
2 x 0,14 mm², shielded