![Heinzmann PANDAROS III DG 16.6 Manual Download Page 21](http://html1.mh-extra.com/html/heinzmann/pandaros-iii-dg-16-6/pandaros-iii-dg-16-6_manual_2120031021.webp)
6 Sensors
Digital Governor Basic System PANDAROS III
13
6
Sensors
6.1
Overview
Sensor
Speed
Coolant
Temperature
Oil Pressure
Boost Pressure
HZM Designation
IA ..
TS 01-28-PT1000
DSO 01-6
DSO 01-10
DSL/G 0..-2
DSL/G 0..-5
DSL/G 0..-10
Connection
SV 6-IA-2K
2 pole
SV 6-IA-2K
2 pole
DIN 43650 A
2 Line System
DIN 43650 A
2 Line System
Measuring Procedure inductive, active
PT1000, passive
active
active
Measuring Range
50...9.000 Hz
-50...+150°C
0...6 bar
0...10 bar
0...2 bar
0...5 bar
0...10 bar
Supply Voltage
Range
passive
10...34 V DC
12...36 V DC
Output Signal Range 0...10 V AC
ca. 700...1500 Ohm
4...20 mA
4...20 mA
Operating
Temperature Range
-55...+120°C
-50...+150°C
-25...+125°C
-40...+100°C
In order to ensure maximum flexibility with regard to the sensors, the minimum/ maximum
current values and the measuring ranges of the pressure and temperature sensors have been
provided programmable.