77.4 Multifunction Key (MP-Key) and Multifunction inputs (MP-INP)
Tare
x
In the function group MP.KEY, programme the function TARA to ON. In the operating mode select the
current measured value (ACTUAL) and briefly press the MP Key.
x
In the function group MP.INP, programme the function MP.INP1 or MP.INP2 to TARA. In the operating
mode briefly activate the multifunction input 1 or multifunction input 2
Reset Tare Value
x
In the function group MP.KEY, programme the function TARA to ON. In the operating mode select the
current measured value (ACTUAL) and press the MP Key >5 sec.
x
In the function group MP.INP, programme the function MP.INP1 or MP.INP2 to R.TARA. In the operating
mode briefly activate the multifunction input 1 or multifunction input 2.
Reset MIN value memory
x
In the function group MP.KEY, programme the function RES.MIN to ON. In the operating mode select the
minimum value memory (MINIMU) and briefly press the MP Key.
x
In the function group MP.INP, programme the function MP.INP1 or MP.INP2 to RES.MIN or R.PEAKS. In
the operating mode briefly activate the multifunction input 1 or multifunction input 2.
Reset MAX value memory
x
In the function group MP.KEY, programme the function RES.MAX to ON. In the operating mode select the
maximum value memory (MAXIMU) and briefly press the MP Key.
x
In the function group MP.INP, programme the function MP.INP1 or MP.INP2 to RES.MAX or R.PEAKS. In
the operating mode briefly activate the multifunction input 1 or multifunction input 2.
Reset of relay outputs in Latch mode
x
In the function group MP.KEY, programme the function RES.REL to ON. In the operating mode briefly press
the MP Key.
x
In the function group MP.INP, programme the function MP.INP1 or MP.INP2 to RES.REL. In the operating
mode briefly activate the multifunction input 1 or multifunction input 2.
Reset Totalizer
x
In the function group MP.KEY, programme the function RES.TOT to ON. In the operating mode, select the
totalizer (TOTAL) and briefly press the MP Key.
x
In the function group MP.INP, programme the function MP.INP1 or MP.INP2 to RES.TOT. In the operating
mode briefly activate the multifunction input 1 or multifunction input 2
Display Hold
x
In the function group MP.INP, programme the function MP.INP1 or MP.INP2 to DISP.HD.
x
In the operating mode, select either the current measured value (ACTUAL) or the totalizer (TOTAL) and
activate multifunction input 1 or multifunction input 2.
Lock-out Limit Value (Alarm) setting
x
In the function group MP.INP, programme the function MP.INP1 or MP.INP2 to LOC.ALR.
x
In the operating mode, activate multifunction input 1 or multifunction input 2
Lock-out Programming and Default setting
x
In the function group MP.INP, programme the function MP.INP1 or MP.INP2 to LOC.PRG.
x
In the operating mode, activate multifunction input 1 or multifunction input 2.
Lock-out Keypad
x
In the function group MP.INP, programme the function MP.INP1 or MP.INP2 to LOC.KEY.
x
In the operating mode, activate multifunction input 1 or multifunction input 2
.