Page 22 of 30
3. Press
“
Enter (Mode)
”
key to activate Sound output. The corresponding relay is activated.
3.5 Zone Disable
1. Press and held Mode key for more than three seconds until the Activate LED blinks.
2. Press
“
Up
”
and
“
Down
”
arrow key to select Zone Disable LED blinks.
3. Press
“
Enter (Mode)
”
key to enter Zone Disable menu.
3. Press
“
Up
”
and
“
Down
”
arrow key to select Zone1 to Zone16, the selected Zone LED blinks.
4. Press
“
Enter (Mode)
”
key to disable the corresponding zone. Then panel will be reset automatically.
5. After reset automatically, the disabled Zone Yellow LED turns on, and the Zone Disable LED turns on.
3.6 Sound Disable
1. Press and held Mode key for more than three seconds until the Activate LED blinks.
2. Press
“
Up
”
and
“
Down
”
arrow key to select Sound Disable LED blinks.
3. Press
“
Enter (Mode)
”
key to enter Sound Disable menu.
4. Press
“
Up
”
and
“
Down
”
arrow key to select Sound1 to 4, the selected Sound LED blinks.
5. Press
“
Enter (Mode)
”
key to disable the corresponding sound. Then panel will be reset automatically.
6. After reset automatically, the disabled Zone Yellow LED turns on, and the Zone Disable LED turns on.
3.7 Manual / Automatic running mode switch
1. Press and held Mode key for more than three seconds until the Activate LED blinks.
2. Press
“
Up
”
and
“
Down
”
arrow key to select Manual or Automatic LED blinks.
2. Press
“
Enter (Mode)
”
key to set panel running mode.
In program mode, press
“
Cancel (Silence
”
) key to exit the program mode in any time.
A pause of up to 30 seconds is allowed between each key press, otherwise the panel will exit program mode
anyway.
3.8 Zone Input mode selection
There is one jump J2 on the right bottom of main PCB board,
1. Short the terminal 1, 2, all zone input short circuit indicate the fault event.
2. Short the terminal 2, 3, all zone input short circuit indicate the alarm event.
Summary of Contents for HM-1000 Series
Page 4: ...Notes ...
Page 6: ...Page 6 of 30 HM 1000 HM 1000 Main Circuit Board HM 1000 Terminals and Connectors ...
Page 8: ...Page 8 of 30 FIGURE 1 1 HM 1000 Panel FIGURE 1 1 HM 1000 Panel ...
Page 11: ...Page 11 of 30 FIGURE 1 3 2 HM 1008 LEDs and Keypad ...
Page 12: ...Page 12 of 30 FIGURE 1 3 3 HM 1016 LEDs and Keypad ...