CHAPTER 2
:
Installation
2.1 Mounting Options
The cabinet may be either semi-flush or surface mounted. The door
is attached to the cabinet by two hinges. The cabinet mounts using
two key slots and one additional 0.250" (6.35 mm) diameter holes
located in the backbox. The key slots are located at the top of the
backbox and the one securing holes at the bottom.
Carefully unpack the system and check for shipping damage.
Mount the cabinet in a clean, dry, vibration-free area where extreme
temperatures are not encountered. The area should be readily
accessible with sufficient room to easily install and maintain the
panel. Locate the top of the cabinet approximately five feet above the floor with the hinge mounting on the left.
Determine the number of conductors required for the devices to be installed. Sufficient knockouts are provided for
wiring convenience. Select the appropriate knockout(s) and pull the required conductors into the box. All wiring
should be in accordance with the National and/or Local codes for fire alarm systems.
2.2 Backbox Mounting
✓
Open the door.
✓
Remove the main PC board assembly by unscrewing the four screws in the corners of the board.
Set the board aside in a safe, clean place. Avoid static discharge which may damage the board.
✓
Mark and predrill holes for the top two keyhole mounting bolts using the dimensions illustrated.
✓
Install two upper fasteners in the wall with the screw heads protruding.
✓
Using the upper 'keyholes', mount the backbox over the two screws.
✓
Mark and drill the lower one holes.
✓
Mount backbox, install remaining fasteners and tighten.
✓
When the location is dry and free of construction dust, reinstall the main PC board.
Summary of Contents for HM-1000 Series
Page 4: ...Notes ...
Page 6: ...Page 6 of 30 HM 1000 HM 1000 Main Circuit Board HM 1000 Terminals and Connectors ...
Page 8: ...Page 8 of 30 FIGURE 1 1 HM 1000 Panel FIGURE 1 1 HM 1000 Panel ...
Page 11: ...Page 11 of 30 FIGURE 1 3 2 HM 1008 LEDs and Keypad ...
Page 12: ...Page 12 of 30 FIGURE 1 3 3 HM 1016 LEDs and Keypad ...