Service diagnosis
42 Domestic air conditioner
10.3.12 High work-intense protection
Outdoor display
ƾƾƾ?(
LED1 flash 21 times
Method of High work-intense control is activated in the heating mode if the temperature
Malfunction being sensed by the heat exchanger thermistor exceeds the limit.
Detection
Malfunction Activated when the temperature being sensed by the heat exchanger
Decision rises above 65
ć
twices in 30 minutes.
Conditions
Supposed
Ƶ
Faulty electronic expansion valve
Causes
Ƶ
Dirty heat exchanger
Ƶ
Faulty heat-exchange sensor
Ƶ
Insufficient gas
Troubleshooting * Caution Be sure to turn off power switch before connect or disconnect connector, or
else parts damage may be occurred.
Electrify the machine again and turn it on with the
remote controller, check whether the wind
temperature is below 65
ć
The malfunction is reported
after the machine has run
for some time?
1
ǃ
Check room temperature and
pipe temperature sensor.
2
ǃ
the temperature monitoring circuit
of the indoor mainboard
The indoor unit blows poorly
due to blocked filters or poor
condition of the fan?
1) Clean the filters
2) Reinstall the fan.
Use some tools to measure the pressure of system
ˈ
YES
NO
YES
NO
Summary of Contents for JS026-D1
Page 12: ...Piping diagrams Domestic air conditioner 5 Piping diagrams 10 EEV EEV...
Page 14: ...Printed circuit board connector wiring diagram 12 Domestic air conditioner PCB 1...
Page 46: ...Sincere Forever...
Page 51: ...three 6 Removal Procedure 4 Domestic Air Conditioner Remove the casing 1 2 3...
Page 55: ...Removal Procedure 8 Domestic Air Conditioner motor cover motor cover...