15
Tab. 1
b Kontrollmass
b- Control dimension
Leitungsquerschnitt
Conductor cross section
A: Ø -Bereich Leitung / A: Ø Range of cable
mm
3.0
– 6.0
5.5
– 9.0
mm
Mm
2
AWG
Typ / Type
~ 3
1.5
– 2.5
14
PV-K...T4/...2.5l
PV-K...T4/...2.5ll
~ 5
4
– 6
12 / 10
PV-K...T4/...6l
PV-K...T4/...6ll
~ 7.2
10
-
PV-K...T4/...10ll
(ill. 10)
Strip the cable.
Remove the insulation of the cable over
a length of 6.0 to 7.5 mm.
Warning:
Do not cut any individual wires when
stripping!
Note:
1
In order to use the stripping pliers
PV-AZM... and replace the sets of
blades, please refer to the operating
instructions MA267 at www.multi-
contact.com
C
rimping
(ill. 11)
Open the clamping bracket (K) and hold it
firmly.
Place
the
contact
in
the
appropriate cross-section area. Turn the
crimping lugs upwards. Release the
clamping bracket (K). The contact is now
fixed.