background image

9

4.0 INSTALLATION - DIRECT
      UNITS

4.1 PLUMBING CONNECTIONS

Direct units require the following pipework connec-
tions.

Cold water supply to and from inlet controls.

Outlet to hot water draw off points.

Discharge pipework from valve outlets to tundish.

4.2 ELECTRICAL SUPPLY (FIG. 6)

The Heatstore HSUDC100 litre units are fitted with
one 3kW immersion heater, all other direct models are
fitted with two 3kW immersion heaters as standard. It
is recommended that these should be wired via a suit-
able controller to BSEN 60730. 

The Heatstore HSU

MUST be earthed.

 The 250 and 300 litre units have an

additional boss which has a blanking plug fitted. An
additional immersion heater can be fitted in place of
the blanking plug where a higher electrical input is
required for faster recovery times, order Part No. 95
970 510 if required.
All wiring to the unit must be installed in accordance
with the latest IEE Wiring Regulations and the circuit
must be protected by a suitable fuse and double pole
isolating switch with a contact separation of at least
3mm in both poles. The Live and Neutral connections
are made directly onto the combined thermostat and
thermal cut-out located under the terminal cover(s)
mounted on the side of the unit. The Earth connection
should be made to the earth connection located to
the side of the immersion heater boss(es). The supply
cable must be routed through the cable gland located
on the unit casing beneath the terminal housing.

DO NOT

 operate the immersion heaters until the

Heatstore HSU has been filled with water.

4.3 SAFETY

DISCONNECT FROM THE MAINS SUPPLY
BEFORE REMOVING ANY COVERS.

Never attempt to replace the immersion heater(s) other
than with the recommended Heatstore HSU  immersion
heater(s).

DO NOT

 

BYPASS THE THERMAL CUT-OUT(S) IN

ANY CIRCUMSTANCES

. Ensure the two male spade

terminations on the underside of the combined
thermostat and thermal cut-out are pushed firmly onto
the corresponding terminations on the element plate
assembly.
In case of difficulty contact Heatstore, tel: 0117 923
5375.

5.0 INSTALLATION - INDIRECT
      UNITS

5.1 PLUMBING CONNECTIONS

Indirect units require the following pipework connec-
tions.

Cold water supply to and from inlet controls.

Outlet to hot water draw off points.

Discharge pipework from valve outlets to tundish

Connection to the primary circuit.

Primary connections are 22mm compression. However,
3/4”BSP parallel threaded fittings can be fitted to the
primary coil connections if required.

5.2 ELECTRICAL SUPPLY (FIG. 6)

All Indirect units are fitted with a 3kW immersion
heater and a combined thermostat and thermal cut-
out to control the indirect heating source. 

The

Heatstore HSU  MUST be earthed.

All wiring to the unit must be installed in accordance
with the latest IEE Wiring Regulations and the supply
circuits must be protected by a suitable fuse and double
pole isolating switch with a contact separation of at
least 3mm in both poles. All connections are made to
the terminal block located under the terminal cover
mounted on the side of the unit. The supply cable(s)
must be routed through the cable grip(s) in the terminal
housing.

DISCONNECT FROM MAINS SUPPLY BE-
FORE REMOVING ANY COVERS. DO NOT

 

BY-

PASS THE THERMAL CUT-OUTS IN ANY CIRCUM-
STANCES.

 Ensure the thermostat and thermal cut-

out sensing bulbs are pushed fully into the pockets
on the element plate assembly.

5.3 BOILER SELECTION

The boiler should have a control thermostat and non
self-resetting thermal cut-out and be compatible with
unvented storage water heaters.

5.4 PRIMARY CIRCUIT CONTROL

The 2 port motorised valve supplied with the Heatstore
HSUIC indirect units MUST be fitted to the primary
flow to the Heatstore HSU heat exchanger and wired
in series with the indirect thermostat and thermal cut-
out fitted to the unit.
Primary circulation to the Heatstore HSU heat ex-
changer MUST be pumped, gravity circulation WILL
NOT WORK due to the special design of the heat
exchanger.

5.5 SPACE AND HEATING SYSTEMS CONTROLS

The controls provided with the Heatstore HSU indi-
rect units will ensure the safe operation of the unit
within a central heating system. Other controls will be
necessary to control the space heating requirements
and times that the system is required to function. The
Heatstore HSU is compatible with most heating con-
trols, examples of electrical circuits are shown in Figs.
7 and 8. However, other systems may be suitable, refer
to the controls manufacturers’ instructions, supplied
with the controls selected, for alternative system wir-
ing schemes.

Summary of Contents for HSUDC100

Page 1: ...sue 1 PACK CONTENTS zHeatstore unvented water heater incorporating immersion heater s and thermal controls zFactory fittedTemperature Pressure ReliefValvezColdWaterCombinationValve zExpansionVessel zExpansionVessel Mounting BracketzTundish zMotorisedValve Indirect models only zCom pression nutsand olives zImmersionheaterspanner zInstallation Instructions ...

Page 2: ...ntrol devices needed to allow connec tion to the cold water mains All these components are pre adjusted NOTE Prior to installation the unit should be stored in an upright position in an area free from excessive damp or humidity This appliance complies with the requirements of the CE marking directive and is KIWAapproved to show compliance with Building Regulations Section G3 The following instruct...

Page 3: ...oldWater CombinationValve can be con nected to a maximum mains pressure of 16 bar 2 4 OUTLET TERMINALFITTINGS TAPS ETC The Heatstore HSU can be used with most types of terminalfittings Itisadvantageousinmanymixershow ers to have balanced hot and cold water supplies In these instances a balanced pressure cold water con nection should be placed between the Cold Water Combination Valve and the Heatst...

Page 4: ...can be achieved by attaching a hose to the drain tap outlet spigot 3 5 EXPANSION VESSEL The Expansion Vessel accommodates expansion that results from heating the water inside the unit The unit is pre charged at 3 5 bar The Expansion Vessel must be connected between the Cold Water Combination Valve and the Heatstore HSU see Fig 5 The loca tion of the Expansion Vessel should allow access to recharge...

Page 5: ...ndirectly heated Primary flow 82deg C at 15l min HSUIC150 24mins 20mins Indirectly heated Primary flow 82deg C at 15l min HSUIC210 32mins 29mins Indirectly heated Primary flow 82deg C at 15l min Test results obtained by WRc NSFin accordance with Test Criteria 1 50 220 and 1 50 222 SURFACE AREA sq m RATING kW RECOVERY mins 120 0 43 12 5 22 121 150 0 55 16 4 21 152 170 0 61 16 0 24 173 210 0 68 18 3...

Page 6: ...er than the nominal outlet size of the safety device unless its total equiva lent hydraulic resistance exceeds that of a straight pipe 9m long i e discharge pipes between 9m and 18m equivalent resistance length should be at least two sizes larger than the nominal outlet size of the safety device between 18 and 27m at least 3 sizes larger and so on Bends must be taken into account in calculat ing t...

Page 7: ...m up to 9m up to 18m up to 27m 0 8m 1 0m 1 4m G3 4 22mm 28mm 35mm 42mm up to 9m up to 18m up to 27m 1 0m 1 4m 1 7m G1 28mm 35mm 42mm 54mm up to 9m up to 18m up to 27m 1 4m 1 7m 2 3m Table 4 Sizing of copper discharge pipe D2 for common temperature relief valve outlet sizes FIG 4 Typical discharge pipe arrangement extract from Building Regulation G3 Guidance section 3 9 3 9 WARNINGS Under no circum...

Page 8: ... CABLE SIZE TO INDIRECT SYSTEM CONTROLS JUNCTION BOX SEE FIGS 7 8 GREEN YELLOW BROWN BLUE 3 DIRECT THERMOSTAT B A 1 1 2 2 3 INDIRECT THERMOSTAT INDIRECT THERMAL CUT OUT EXPANSION VESSEL COLD WATER COMBINATION VALVE T P RELIEF VALVE TO HOT OUTLETS MAINS WATER SUPPLY ISOLATING VALVE NOT SUPPLIED TUNDISH DISCHARGE PIPE DRAIN COCK NOT SUPPLIED PRIMARY RETURN PRIMARY FLOW ELEMENT CONTROLS HOUSING INLET...

Page 9: ...Cold water supply to and from inlet controls Outlet to hot water draw off points Discharge pipework from valve outlets to tundish Connection to the primary circuit Primary connections are 22mm compression However 3 4 BSP parallel threaded fittings can be fitted to the primary coil connections if required 5 2ELECTRICALSUPPLY FIG 6 All Indirect units are fitted with a 3kW immersion heater and a comb...

Page 10: ...ringmay differ from those shown Refer to instructions with controls selected ADOUBLEPOLEISOLATING SWITCHMUSTBEINSTALLED INTHEMAINSSUPPLY ALLEARTHCONNECTIONS BECONNECTEDBACKTO THEMAINSEARTHSUPPLY PROGRAMMER BOILER PUMP ROOM STAT ZONE VALVE DHW SUPPLIED ZONE VALVE HTG INDIRECT CONTROLS TERMINAL BLOCK JUNCTION BOX 1 2 3 4 5 6 7 8 9 10 1 2 3 4 5 6 7 8 9 10 L N G Br Bl O GY G W Bl O GY 1 3 2 L N 2 3 2 ...

Page 11: ...anufacturer s commissioning instructions To ensure the Heatstore HSU primary heat exchanger is filled the 2 port motorised valve supplied should be manu ally opened by moving the lever on the motor hous ing to the FLUSHING ONLY setting When the pri mary circuit is full return the lever to the NORMAL USE position Switch on the boiler ensure the pro grammer is set to Domestic Hot Water and allow the...

Page 12: ...e immersion heater s the unit must be drained Ensure the water and electrical supply and boiler are OFF before draining Attach a hosepipe to the drain cock having sufficient length to take water to a suitable discharge point below the level of the unit Open a hot tap close to the unit and open drain cock to drain unit Direct models Open the cover s to the immersion heater housing s and disconnect ...

Page 13: ...alve cartridge 6bar 95 605 864 Expansion valve complete 6bar 95 607 030 Cold water combination valve complete 95 605 022 Cold water combination valve body 95 605 030 Check valve housing 95 605 028 Pressure reducing valve cartridge 3 5bar 95 607 029 Pressure reducing valve housing 95 605 027 Temperature Pressure Relief Valve 95 605 810 Expansion vessel 12 litre 100 120 and 150 litre models 95 607 8...

Page 14: ...ec k boiler operation If fault is s us pec ted c ons ult boiler m anufac turer s ins truc tions 5 INDIRE CT therm al c ut out has operated 5 Chec k Res et by pus hing button on c ut out Chec k operation of indirec t therm os tat 6 INDIRE CT m otoris ed valve not c onnec ted c orrec tly 6 Chec k wiring and or plum bing c onnec tions to m otoris ed valve s ee Fig 7 W ater dis c harges 1 INTE RM ITTE...

Page 15: ...e controls are located within the lower grey terminal housing along with the immersion heater thermostat The thermostat is factory set to give a water storage temperature of approx 55o to 60o C Access to the thermostat can be made by opening the terminal housing cover DIS CONNECT THE ELECTRICAL SUPPLY BEFORE OPENING THE COVER Temperature adjustment is made by inserting a flat bladed screwdriver in...

Page 16: ...unit is not guaranteed against damage by frost and the inner container with integral immersion heater s is not guaranteed against excessive scale build up Periodic loss of charge pressure from the Expansion Vessel is normal indicated by an intermittent discharge of water from the Expansion Valve and is not cov ered under the product guarantee Refer to Section 7 5 for details on how to restore the ...

Reviews: