background image

6

Worked example of discharge pipe sizing

The example below is for a G1/2 temperature relief valve
with a discharge pipe (D2) having 4 No. elbows and
length of 7m from the tundish to the point of discharge.

From Table 4:
Maximum resistance allowed for a straight length of
22mm copper discharge pipe (D2) from a G1/2 tempera-
ture relief valve is 9.0m.
Subtract the resistance for 4 No. 22mm elbows at 0.8m
each = 3.2m

Therefore the permitted length equates to: 5.8m

5.8m is less than the actual length of 7m therefore
calculate the next largest size.

Maximum resistance allowed for a straight length of
28mm pipe (D2) from a G1/2 temperature relief valves
equates to 18m.
Subtract the resistance of 4 No. 28mm elbows at 1.0m
each = 4.0m

Therefore the maximum permitted length equates to: 14m

As the actual length is 7m, a 28mm (D2) copper pipe will
be satisfactory.

3.8 DISCHARGE PIPEWORK

It is a requirement of Building Regulation G3 that any
discharge from an unvented system is conveyed to
where it is visible, but will not cause danger to per-
sons in or about the building. The tundish and dis-
charge pipes should be fitted in accordance with the
requirements and guidance notes of Building Regula-
tion G3. The G3 Requirements and Guidance section
3.9 are reproduced in the following sections.
Information Sheet No. 33 available from the British
Board of Agrement gives further advice on discharge
pipe installation. For discharge pipe arrangements not
covered by G3 Guidance or BBA Info Sheet No.33
advice should be sought from either your local Build-
ing Control Officer or Heatstore.

G3 REQUIREMENT

“...there shall be precautions...to ensure that the hot
water discharged from safety devices is safely
conveyed to where it is visible but will not cause
danger to persons in or about the building.”

G3 GUIDANCE SECTION 3.9

The discharge pipe (D1) from the vessel up to and
including the tundish is generally supplied by the
manufacturer of the hot water storage system. Where
otherwise, the installation should include the discharge
pipe(s) (D1) from the safety device(s). In either case
the tundish should be vertical, located in the same
space as the unvented hot water storage system and
be fitted as close as possible and within 500mm of the
safety device e.g. the temperature relief valve.
The discharge pipe (D2) from the tundish should ter-
minate in a safe place where there is no risk to persons
in the vicinity of the discharge, preferably be of metal
and:
a.  be at least one pipe size larger than the nominal
outlet size of the safety device unless its total equiva-
lent hydraulic resistance exceeds that of a straight
pipe 9m long i.e. discharge pipes between 9m and 18m
equivalent resistance length should be at least two
sizes larger than the nominal  outlet size of the safety
device, between 18 and 27m at least 3 sizes larger , and
so on. Bends must be taken into account in calculat-
ing the flow resistance. Refer to Diagram 1, Table 1
and the worked example.
An alternative approach for sizing discharge pipes
would be to follow BS 6700:1987 

Specification for

design installation, testing and maintenance of ser-
vices supplying water for domestic use within build-
ings and their curtilages, 

Appendix E, section E2 and

table 21.
b.  have a vertical section of pipe at least 300mm long,
below the tundish before any elbows or bends in the
pipework.
c.  be installed with a continuous fall.
d.  have discharges visible at both the tundish and the
final point of discharge but where this is not possible
or is practically difficult there should be clear visibil-
ity at one or other of these locations. Examples of
acceptable discharge arrangements are:

i.   ideally below a fixed grating and above the water
seal in a trapped gully.
ii.  downward discharges at low level; i.e. up to 100mm
above external surfaces such as car parks, hard stand-
ings, grassed areas etc. are acceptable providing that
where children may play or otherwise come into con-
tact with discharges a wire cage or similar guard is
positioned to prevent contact, whilst maintaining vis-
ibility.
iii. discharges at high level; e.g. into a metal hopper
and metal down pipe with the end of the discharge
pipe clearly visible (tundish visible or not) or onto a
roof capable of withstanding high temperature dis-
charges of water and 3m from any plastics guttering
system that would collect such discharges (tundish
visible).
iv. where a single pipe serves a number of discharges,
such as in blocks of flats, the number served should
be limited to not more than 6 systems so that any
instalation discharging can be traced reasonably eas-
ily. The single common discharge pipe should be at
least one pipe size larger than the largest individual
discharge pipe (D2) to be connected. If unvented hot
water storage systems are installed where discharges
from safety devices may not be apparent i.e. in dwell-
ings occupied by blind, infirm or disabled people, con-
sideration should be given to the installation of an
electronically operated device to warn when discharge
takes place.

Note: 

The discharge will consist of scalding water and

steam. Asphalt, roofing felt and non-metallic rainwa-
ter goods may be damaged by such discharges.

Summary of Contents for HSUDC100

Page 1: ...sue 1 PACK CONTENTS zHeatstore unvented water heater incorporating immersion heater s and thermal controls zFactory fittedTemperature Pressure ReliefValvezColdWaterCombinationValve zExpansionVessel zExpansionVessel Mounting BracketzTundish zMotorisedValve Indirect models only zCom pression nutsand olives zImmersionheaterspanner zInstallation Instructions ...

Page 2: ...ntrol devices needed to allow connec tion to the cold water mains All these components are pre adjusted NOTE Prior to installation the unit should be stored in an upright position in an area free from excessive damp or humidity This appliance complies with the requirements of the CE marking directive and is KIWAapproved to show compliance with Building Regulations Section G3 The following instruct...

Page 3: ...oldWater CombinationValve can be con nected to a maximum mains pressure of 16 bar 2 4 OUTLET TERMINALFITTINGS TAPS ETC The Heatstore HSU can be used with most types of terminalfittings Itisadvantageousinmanymixershow ers to have balanced hot and cold water supplies In these instances a balanced pressure cold water con nection should be placed between the Cold Water Combination Valve and the Heatst...

Page 4: ...can be achieved by attaching a hose to the drain tap outlet spigot 3 5 EXPANSION VESSEL The Expansion Vessel accommodates expansion that results from heating the water inside the unit The unit is pre charged at 3 5 bar The Expansion Vessel must be connected between the Cold Water Combination Valve and the Heatstore HSU see Fig 5 The loca tion of the Expansion Vessel should allow access to recharge...

Page 5: ...ndirectly heated Primary flow 82deg C at 15l min HSUIC150 24mins 20mins Indirectly heated Primary flow 82deg C at 15l min HSUIC210 32mins 29mins Indirectly heated Primary flow 82deg C at 15l min Test results obtained by WRc NSFin accordance with Test Criteria 1 50 220 and 1 50 222 SURFACE AREA sq m RATING kW RECOVERY mins 120 0 43 12 5 22 121 150 0 55 16 4 21 152 170 0 61 16 0 24 173 210 0 68 18 3...

Page 6: ...er than the nominal outlet size of the safety device unless its total equiva lent hydraulic resistance exceeds that of a straight pipe 9m long i e discharge pipes between 9m and 18m equivalent resistance length should be at least two sizes larger than the nominal outlet size of the safety device between 18 and 27m at least 3 sizes larger and so on Bends must be taken into account in calculat ing t...

Page 7: ...m up to 9m up to 18m up to 27m 0 8m 1 0m 1 4m G3 4 22mm 28mm 35mm 42mm up to 9m up to 18m up to 27m 1 0m 1 4m 1 7m G1 28mm 35mm 42mm 54mm up to 9m up to 18m up to 27m 1 4m 1 7m 2 3m Table 4 Sizing of copper discharge pipe D2 for common temperature relief valve outlet sizes FIG 4 Typical discharge pipe arrangement extract from Building Regulation G3 Guidance section 3 9 3 9 WARNINGS Under no circum...

Page 8: ... CABLE SIZE TO INDIRECT SYSTEM CONTROLS JUNCTION BOX SEE FIGS 7 8 GREEN YELLOW BROWN BLUE 3 DIRECT THERMOSTAT B A 1 1 2 2 3 INDIRECT THERMOSTAT INDIRECT THERMAL CUT OUT EXPANSION VESSEL COLD WATER COMBINATION VALVE T P RELIEF VALVE TO HOT OUTLETS MAINS WATER SUPPLY ISOLATING VALVE NOT SUPPLIED TUNDISH DISCHARGE PIPE DRAIN COCK NOT SUPPLIED PRIMARY RETURN PRIMARY FLOW ELEMENT CONTROLS HOUSING INLET...

Page 9: ...Cold water supply to and from inlet controls Outlet to hot water draw off points Discharge pipework from valve outlets to tundish Connection to the primary circuit Primary connections are 22mm compression However 3 4 BSP parallel threaded fittings can be fitted to the primary coil connections if required 5 2ELECTRICALSUPPLY FIG 6 All Indirect units are fitted with a 3kW immersion heater and a comb...

Page 10: ...ringmay differ from those shown Refer to instructions with controls selected ADOUBLEPOLEISOLATING SWITCHMUSTBEINSTALLED INTHEMAINSSUPPLY ALLEARTHCONNECTIONS BECONNECTEDBACKTO THEMAINSEARTHSUPPLY PROGRAMMER BOILER PUMP ROOM STAT ZONE VALVE DHW SUPPLIED ZONE VALVE HTG INDIRECT CONTROLS TERMINAL BLOCK JUNCTION BOX 1 2 3 4 5 6 7 8 9 10 1 2 3 4 5 6 7 8 9 10 L N G Br Bl O GY G W Bl O GY 1 3 2 L N 2 3 2 ...

Page 11: ...anufacturer s commissioning instructions To ensure the Heatstore HSU primary heat exchanger is filled the 2 port motorised valve supplied should be manu ally opened by moving the lever on the motor hous ing to the FLUSHING ONLY setting When the pri mary circuit is full return the lever to the NORMAL USE position Switch on the boiler ensure the pro grammer is set to Domestic Hot Water and allow the...

Page 12: ...e immersion heater s the unit must be drained Ensure the water and electrical supply and boiler are OFF before draining Attach a hosepipe to the drain cock having sufficient length to take water to a suitable discharge point below the level of the unit Open a hot tap close to the unit and open drain cock to drain unit Direct models Open the cover s to the immersion heater housing s and disconnect ...

Page 13: ...alve cartridge 6bar 95 605 864 Expansion valve complete 6bar 95 607 030 Cold water combination valve complete 95 605 022 Cold water combination valve body 95 605 030 Check valve housing 95 605 028 Pressure reducing valve cartridge 3 5bar 95 607 029 Pressure reducing valve housing 95 605 027 Temperature Pressure Relief Valve 95 605 810 Expansion vessel 12 litre 100 120 and 150 litre models 95 607 8...

Page 14: ...ec k boiler operation If fault is s us pec ted c ons ult boiler m anufac turer s ins truc tions 5 INDIRE CT therm al c ut out has operated 5 Chec k Res et by pus hing button on c ut out Chec k operation of indirec t therm os tat 6 INDIRE CT m otoris ed valve not c onnec ted c orrec tly 6 Chec k wiring and or plum bing c onnec tions to m otoris ed valve s ee Fig 7 W ater dis c harges 1 INTE RM ITTE...

Page 15: ...e controls are located within the lower grey terminal housing along with the immersion heater thermostat The thermostat is factory set to give a water storage temperature of approx 55o to 60o C Access to the thermostat can be made by opening the terminal housing cover DIS CONNECT THE ELECTRICAL SUPPLY BEFORE OPENING THE COVER Temperature adjustment is made by inserting a flat bladed screwdriver in...

Page 16: ...unit is not guaranteed against damage by frost and the inner container with integral immersion heater s is not guaranteed against excessive scale build up Periodic loss of charge pressure from the Expansion Vessel is normal indicated by an intermittent discharge of water from the Expansion Valve and is not cov ered under the product guarantee Refer to Section 7 5 for details on how to restore the ...

Reviews: