Important Safety Instructions
General Safety
•
DANGER!
Risk of carbon monoxide poisoning. Failure to provide
proper ventilation could result in serious illness or death.
• Check that the heater is in sound condition and good
working order. Take immediate action to repair or
replace damaged parts.
• Only use diesel or kerosene to fuel this heater, in
accordance with instructions contained in this manual.
• Locate heater on a level and stable surface.
•
WARNING!
Only use heater in well ventilated areas.
Ensure continuous ventilation is provided to the heater
operating area via windows and doors etc. If people are
not required to be present in the heated area, the volume
of air to be heated (m
3
)/heat output (kW) ratio must be at
least 10:1 and people must be advised not to remain in
the heated area for prolonged periods. If people are
required to be present in the heated area, the volume of
air to be heated (m
3
)/heat output (kW) ratio must be at
least 30:1. Ventilation must be to the outside of the
premises in which the heater is to be operated. Minimum
Ventilation Opening Needed: AB2200Q - 5990cm
2
(6.5ft
2
). The volume concentration of oxygen (O
2
) in the
heated room, must always remain above 17%.
•
WARNING!
DO NOT
use the heater near flammable material,
liquids, solids, gases or compressed gas cylinders etc.
•
DO NOT
stand or place any object less than 3m from
the heater output and keep the heater a minimum of 2m
from any walls or objects (see figure 5 on page 8).