Heatrae Sadia HRU ECO 4 User Manual Download Page 23

The supply fan (top) has stopped
Cause

Solution

a) The fan connector is loose or not properly connected.

Fit the fan connector on the correct connector 

on the circuit board.

b) Frost control is active.

If the outside temperature becomes very cold, 

the fan is switched off to avoid freezing of the 

heat exchanger.

The fan will start running again when the 

outside temperature rises enough.

c) The fan is blocked or stuck due to heavy soiling.

Clean the fan impeller. Watch out for the 

balance clips.

d) The fan is defective.

Replace the fan.

e) The ventilation unit PCB is faulty.

Replace the PCB and carry out the 

commissioning procedure again.

The ventilation unit is noisy
Cause

Solution

a) The fan is blocked or stuck due to heavy soiling.

Clean the fan impeller. Watch out for the 

balance clips.

b) The fan is imbalanced.

Replace the fan.

c) The unit is mounted on a wall/ceiling/floor with 

insufficient load-bearing capacity.

If the ventilation unit cannot be relocated, try 

using vibration dampers to decouple it from 

the wall, ceiling or floor.

d) The ducts are not correctly connected to the unit.

Check the connections and ensure that fixed 

ducts are clamped to the wall, ceiling or floor.

e) The bypass valve is blocked (rattling noise).

The bypass valve strikes the stop during the 

self-test after power is switched on. Wait 30 

seconds and check whether the noise has 

stopped.

Inspect the valve. Clean it if it has become 

blocked with dirt. Replace the valve if there is a 

different cause of the fault.

The ventilation unit is not responding to the RF remote controls
Cause

Solution

a) The battery of the RF remote control is empty.

Replace the battery.

b) The RF remote control is not paired with the 

ventilation unit.

Restart the commissioning procedure and pair 

the RF remote control.

c) The distance between the ventilation unit and the RF 

remote control is too large or there are too many 

obstacles interfering with the signal.

Try pairing the devices again. If this does not 

work, move the RF remote control to a location 

where there are fewer obstacles to interfere 

with it.

d) The brand names of the RF control switch and the 

ventilation unit are different.

Replace the RF device by one with the same 

brand name as the ventilation unit.

e) The ventilation unit PCB is faulty.

Replace the PCB and carry out the 

commissioning procedure again.

23

Summary of Contents for HRU ECO 4

Page 1: ...HRU ECO 4 User manual...

Page 2: ...Translation of the original document...

Page 3: ...em or surrounding area Note Instructions important for the installation functioning operation or maintenance of the product Failure to observe these instructions can result in minor damage to the prod...

Page 4: ...fiche information 12 2 8 Accessories 13 2 9 Recycling 13 3 Operation 14 3 1 Ventilation speeds 14 3 2 Devices 15 3 3 Sensors 15 3 4 Pairing and unpairing wireless devices and sensors 15 4 Inspection...

Page 5: ...experience knowledge if under supervision or after having received instructions regarding safe use and if they are aware of the product and or system hazards Cleaning and maintenance by the user may...

Page 6: ...pect the product regularly for faults In the event of faults switch the product off and contact your installer or Heatrae Sadia Customer Service immediately Switch the product off if The product is no...

Page 7: ...ECO 4 ventilation system from Heatrae Sadia is an example of these advanced appliances The HRU ECO 4 is a balanced ventilation system with heat recovery The ventilation unit is equipped with two fans...

Page 8: ...rgies who are sensitive to this During the product s lifetime the filters will become dirty which reduces the capacity of the ventilation unit It is therefore essential that the filters are cleaned as...

Page 9: ...nergy efficient manner When the the CO2 level has fallen sufficiently the capacity of the ventilation unit is automatically decreased Tip It is possible to place several wireless sensors and controls...

Page 10: ...2x s Bypass mode Lit Normal operation Pattern Function Red Orange Blinks 1x s Blinks 1x s Exhaust fan fault Blinks 1x s Blinks 2x s Supply fan fault Blinks 2x s Blinks 2x s Exhaust temperature sensor...

Page 11: ...ring forced drying Good ventilation and air circulation are essential during the drying process During the first year keep furniture approximately 5 cm away from the walls to allow the moisture to esc...

Page 12: ...Pmax W 154 Sound power level LWA dB 52 Reference flow rate qref m3 s 0 069 Reference pressure difference Pref Pa 50 Specific power input SPI W m3 h 0 255 Ventilation control Manual control no DCV Con...

Page 13: ...n how to do so The product s packaging can be recycled These materials should be disposed of in a responsible manner in accordance with government regulations As a reminder of the need to dispose of b...

Page 14: ...te The timer can be stopped at any time by pressing the button for low speed high speed or automatic mode Auto Night Auto Night raises the minimum ventilation speed to ensure sufficient ventilation du...

Page 15: ...on page 15 3 4 Pairing and unpairing wireless devices and sensors 3 4 1 Pairing wireless devices Pairing a wireless control switch should be done in the vicinity of the ventilation unit a Switch off p...

Page 16: ...he ventilation unit is switched on For more information consult the documentation provided with the relevant sensor The sensor is paired and the ventilation unit briefly changes speed to confirm the p...

Page 17: ...heck for soiling and leakage 6 months 1 year Motor module Check for soiling imbalance 1 year Bypass valve Frost valve Check functioning and for soiling 1 year Heat exchanger Check for soiling 1 year A...

Page 18: ...he filters as follows a Disconnect power to the ventilation unit b Remove both filter holders c Visually inspect the filters for soiling If the filters are dirty they must be cleaned or replaced d Cle...

Page 19: ...me time Warning HRU ECO 4 should always be fitted with the appropriate filters Without filters the appliance can be irreparably damaged Note The dirty filter indication cannot be reset via the control...

Page 20: ...ubber gaskets b Fully immerse the valves in a solution of a mild cleaning agent such as washing up liquid or all purpose cleaner If necessary the valves can be cleaned in a dishwasher c Wipe off the v...

Page 21: ...an for soiling and clean it if necessary Check the fan for defects and replace it if necessary The status LED on the ventilation unit blinks once red and twice orange Cause Solution a The ventilation...

Page 22: ...he unit will automatically return to normal operation Neither fan is rotating Cause Solution a The ventilation unit s plug is not plugged into a power socket Insert the plug into a power socket b The...

Page 23: ...connected to the unit Check the connections and ensure that fixed ducts are clamped to the wall ceiling or floor e The bypass valve is blocked rattling noise The bypass valve strikes the stop during t...

Page 24: ...nect the switch wires correctly see wiring diagram d The ventilation unit PCB is faulty Replace the PCB and carry out the commissioning procedure again The ventilation unit is leaking water Cause Solu...

Page 25: ...g supplied to the dwelling Cause Solution a The filter in the extraction outlet is blocked Clean or replace the filter in the air outlet b The air valves are not correctly adjusted Put the ventilation...

Page 26: ...claimer This warranty does not apply to Disassembly and assembly costs Faults which are caused by incorrect treatment Negligence or accident Faults that have been caused by repairs by third parties wi...

Page 27: ...mmission Delegated Regulation EU No 1254 2014 of 11 July 2014 supplementing Directive 2010 30 EU of the European Parliament and of the Council with regard to energy labelling of residential ventilatio...

Page 28: ...HEATRAE SADIA HEATING Hurricane Way Norwich NR6 6EA www heatraesadia com SERVICE 44 0 344 871 1535 EMAIL customer support heatraesadia com 01 02504 002 ID 2018 02 07 1426...

Reviews: