3.0 INSTALLATION

3.1 IMPORTANT INSTALLATION POINTS
3.1.1

 The  Hotflo  unvented  water  heater  MUST  be  fitted  with  a  Pressure   

(expansion) Relief Valve. This MUST be fitted to the cold water supply 

near the heater. 

 

FAILURE  TO  PROVIDE ADEQUATE  PRESSURE  RELIEF  WILL 

INVALIDATE ANY  GUARANTEE AND  LEAD  TO A  DANGEROUS 

INSTALLATION.

3.1.2  Expansion can take place within the cold water supply 

 

PROVIDED THAT BOTH :

 

(a) Backflow in the main is not prevented by any stopvalve with loose 

jumper, check valve, pressure reducing valve or similar

 

AND                                           

 

(b) Hot water expansion does not enter a branch to a cold water outlet 

(see Figure 01, page 3 for expansion pipe lengths). 

 

Note: Both the above conditions must be met. Additionally expansion 

within  the  cold  water  supply  will  not  be  possible  if  the  static  supply 

pressure exceeds 0.41 Mpa (4.1 bar).

3.1.3 If any of the conditions in 3.1.2 above cannot be met, expansion must  

be  accommodated using an Expansion Vessel. To ensure all expansion   

takes place in the vessel, a 

Check V

alve must also be fitted (see Fig. 

03, page 5). Use Accessory Pack U5 code no. 95 970 356.

3.1.4 If the static supply pressure exceeds 0.41 MPa (4.1 bar), a Pressure 

Reducing Valve must be fitted to the cold main supply. If a Pressure 

Reducing  Valve  is  used,  an  Expansion  Vessel  must  also  be  used 

(see Fig. 04, page 5). Use Accessory Packs U1 and U5 code no.’s                        

95 970 352 and 95 970 356.

3.1.5  Where  specifications  demand  the  fitting  of  a Temperature/Pressure      

Relief  Valve,  one  can  be  fitted  on  site  (see  Fig.  04,  page  5).  Use 

Accessory Pack U6 code no. 95 970 359. NOTE the fitting of Pack 

U6 does not alter the requirements detailed in points 3.1.2 to 3.1.4 

above.

3.1.6 National Wiring rules may contain restrictions concerning the installation 

of these units in bathrooms.

3.1.7 The installation must be carried out in accordance with the relevant 

         requirements of:      

       • The appropriate Building Regulations either The Building     

           

Regulations, The Building Regulations (Scotland) or Building

          Regulations (Northern Ireland). 

Summary of Contents for Hotflo 10

Page 1: ...1 HOTFLO 10 15 Fitting Instructions and User Guide...

Page 2: ...alling your Hotflo unvented water heater Particular attention should be paid to the section headed IMPORTANT INSTALLATION POINTS Following installation and commissioning the operation of the heater sh...

Page 3: ...15 litres Weight full 10 litre 16 5kg 15 litre 23 4kg Rated pressure 0 6 MPa 6 bar Minimum supply pressure 0 08 MPa 0 8 bar 15 Litre 10 Litre Dimension 613 457 A 656 500 B 516 360 C NOTE If fitting P...

Page 4: ...be accommodated using an Expansion Vessel To ensure all expansion takes place in the vessel a Check Valve must also be fitted see Fig 03 page 5 Use Accessory Pack U5 code no 95 970 356 3 1 4 If the s...

Page 5: ...IGURE 02 FOR INLET PRESSURES UP TO 0 41 MPa 4 1 BAR FIGURE 03 FOR INLET PRESSURES UP TO 0 41 MPa 4 1BAR WHERE EXPANSION IN MAIN SUPPLY IS NOT POSSIBLE FIGURE 04 FOR INLET PRESSURES ABOVE 0 41 MPa 4 1B...

Page 6: ...age 3 and the Dimensions Table to determine a suitable position for the heater 3 2 3 NOTE Ensure that the wall can support the full weight of the unit see TECHNICAL SPECIFICATIONS and that there are n...

Page 7: ...of the valves 3 5 DISCHARGE 3 5 1 The discharge outlet from the Pressure Expansion Relief Valve and the Temperature Pressure Relief Valve if fitted must be connected to a discharge pipe It is recommen...

Page 8: ...ricity supply should be fused 13 Amp and be via a double pole isolating switch with a contact separation of at least 3mm in both poles Refer to Fig 06 below 3 6 2 The wires are colour coded as follows...

Page 9: ...hed the indicator light will go out 5 0 EXPLANATION TO USER Following Installation and Commissioning of the water heater the operation should be fully explained to the user 5 1 HOT WATER 5 1 1 Indicat...

Page 10: ...ing any work on the water heater Water contained in the water heater may be very hot To ensure the continued safe and efficient operation of the water heater it should be regularly maintained In hard...

Page 11: ...th links to the earthing stud 6 3 4 Remove the element plate assembly by unscrewing the five securing screws tapped jacking points are provided Remove any loose scale from the container Carefully clea...

Page 12: ...60 p s i This can reduce over time and eventually require re charging To do this 6 5 2 Turn off water supply to the unit open a hot tap to relieve system pressure 6 5 3 Remove dust cap from top of Exp...

Page 13: ...lve Discharge of water from INSTALLATION POINTS page 4 1 Fit Pack U2 see IMPORTANT possible 1 Expansion in mains not intermittently Presure Relief Valve Discharge of water from 2 Fit Packs U1 and U2 4...

Page 14: ...12 633 Indicator light 95 607 992 Element plate gasket 95 611 708 Pressure Expansion Relief Valve 95 607 986 Temperature Pressure Relief Valve 95 970 359 Check Valve 95 607 987 Expansion Vessel 95 607...

Page 15: ...tions 4 The unit has been used only for heating potable water The unit is not guaranteed against damage by frost and the inner container with integral immersion heater is not guaranteed against excess...

Page 16: ...Hexagon Business Centre Springfield Road Hayes Middlesex UB40 0TY Tel 020 8606 3567 Parts Centre Tel 0845 2709800 www partscentre co uk Newey Eyre Specialist Products Division Please contact your loc...

Reviews: