The CVE ECO 2 RFT unit is controlled using the radio
frequency module. For information about installing and
operating the RFT option, please refer to the handbook
provided with the RFT remote control set.
Setting the basic printed circuit board
Potentiometer settings:
The basic printed circuit board has two potentiometers
to adjust the ventilation unit. The potentiometers can
be adjusted to set the minimum and/or maximum
capacity.
Potentiometer 1 adjusts the low setting for the unit.
This potentiometer is limited on the lower side, so there
can never be too little ventilation. The factory setting is
75 m
³
/h. This potentiometer should be adjusted to
achieve the minimum rate as defined in ADF. If the
minimum rate cannot be achieved at low speed then
the medium speed should be set to the ADF minimum
rate instead. The medium speed is calculated
automatically by the unit, it is defined by a difference in
the low and high speeds. Potentiometer 2 adjusts the
high speed setting.