Feature
Description
Setting
01
Temperature Format
00=
°
C 01=
°
F (
°
C Default)
02
Switching Differential
01=1
°
C/F, 02=2
°
C/F,
03=3
°
C/F
(01 = Default)
03
Temperature Calibrate
Enter Value
04
Frost Mode
00=Disabled 01=Enabled
(01 = Default)
05
Frost Protection Temp
07-17
°
C (12
°
C Default)
06
Output Delay
Enter Value
00 - 30 minutes 00=Default
07
Comms # (PRT-EN)
Enter number 01-32
08
Optimum Start (Preheat)
00=Disabled (Default)
01=01 hr
02=02 hr 03=03 hr
09
Rate of Change
For information only,
10
Air Sensor Selection
00=Internal(Default) 01=Remote
11
Floor Sensor (Mode 1)
00=Disabled 01 Enabled
12
13
14
Floor Limit (Mode 1)
Not Used
Floor or Air&Floor Mode
(Mode 00) | (Mode 01)
20-45
°
C (28
°
C Default)
Floor Sensor Only = 00
Air & Floor Sensor = 01 Default
Summary of Contents for PRT-E
Page 23: ......