Network Series - Installation Guide
Model:
Net Monitor
You can connect up to 6 Heatmiser sensors to the NetMonitor for monitoring purposes.
A table below describes the sensors available.
Sensor Part Number
Description
Heatmiser Internal Sensor
Used to measure air sensor, for internal use only
Heatmiser Immersion Sensor
Used to measure water flow temperature
Supplied with a pocket for immersing the probe in to pipe-work
Heatmiser Clamp On Sensor
Used to measure water temperature in
pipes. Designed to clamp on to the outside of pipe-work.
Heatmiser External Sensor
Used to measure external air temperature
Important: A 5°C differential applies to the sensor alarms.
Assume you set a low limit of 12C. The NetMonitor
will send an email and/or text message as soon as the temperature drops to 12°C. The temperature will then
need to rise to 17C and drop back to 12°C before the alarm is retriggered. The same differential applies applies
for a high limit temperature.
Input Set-up
The NetMonitor has 6 inputs which can be used for various applications. For example, wiring your security system
to the NetMonitor means that you can receive notification by email/sms, should your alarm be triggered.
To set-up the NetMonitor Inputs, follow these steps.
Click Input Setup, you will see a screen like this.
•
You can now enter the title for each input on the NetMonitor.
•
Select whether the input is a normally open or a normally closed contact.
•
Enable or disable the SMS* and Email notification when an input is made (*NetM Only).
•
Configure the NetMonitor to enable one of the 12 volt relay outputs when an input is made.
•
Click Save to store any changes made.
Output Set-up
The Heatmiser NetMonitor has six 12volt relay outputs
which can be used for various applications.
Click Output Setup.
You can now enter a title for each 12v output.
Click Save to store changes.
Email Set-up
Click Email Setup.
You must enter the details in
the fields as shown here.
These settings will be provided
to you by your ISP.
The Heatmiser NetMonitor
has 6 email address settings.
Activated alarms will be sent
to the addresses enabled in
the list.
Click Save to store changes.
Reset Network Settings
This function will reset the IP address, username & password settings.
Follow the steps below:
•
Press and hold down the Reset IP button until the LEDs on the small plugin ethernet board stop
flashing.
•
When the LEDs stop flashing, release the button and the NetMonitor will reboot with the default IP
address and username/password.