Heatmaster 35 TC Installation, Operating And Servicing Instructions Download Page 6

EN • 6

ENGLISH

FRANCAIS

NEDERLANDS

ESP

AÑOL

IT

ALIANO

DEUTSCH

664Y2800.B

DESCRIPTION OF THE SPECIFICATIONS

The 

HeatMaster

®

 TC

 is an hot water producer combined in

a condensing boiler in accordance to the Belgium "

HR-Top

"

standard. The boiler is certified compliant with "

CE

" standards as 

a connected appliance C13(x) - C33(x) - C43(x) - C53 - C83(x), but 
it can also be connected as an open appliance in category B23.

Lining

The boiler is protected by a steel lining that first of all undergoes a 
degreasing and phosphation process before being lacquered and 
heated at 220°C. The inside of this lining is coated with a layer of 
thermal and acoustic insulation, reducing losses to a minimum.

Heat exchanger

The core of the 

HeatMaster

®

 TC

 features a new stainless steel 

heat exchanger. This piece of technology represents the fruit of 
exhaustive research and intensive laboratory testing. It reflects 
ACV’s eighty years of experience in using stainless steel for 
heating and hot water functions. The particular geometry of the 
exchanger pipes is calculated to obtain a very large Reynolds 
number throughout its cycles.
The 

HeatMaster

®

 TC

 achieves an exceptional output that remains 

stable throughout the boiler’s life, given that it causes no oxidation 
on the exchanger, which is manufactured entirely from quality 
steel.

Burner

ACV uses its BG 2000-M burner for the 

HeatMaster

®

 TC

: this 

is an air/gas premix burner providing safe and silent operation 
while limiting emissions (NOx and CO) to an incredibly low level. 
Although the ACV BG 2000-M boiler is very modern, it uses
proven technology and is manufactured from standard spare 
parts that are easily available on the market.

Temperature regulation

The basic version of the 

HeatMaster

®

 TC

 is fitted with a

microprocessor controlled regulator (MCBA) which takes over 
both the safety functions (ignition, monitoring the flame, limiting 
the temperature, etc.) and control of the boiler temperature.
This MCBA also includes a weather-dependent regulator. All you 
need to do is connect the outdoor temperature sensor available 
as an option to the device. However, this regulator can also 
operate with a standard on/off room thermostat In addition, 
with the combination of a weather-dependent regulator and a 
room thermostat, you can control the temperatures based on 
the weather with compensation for the indoor temperature.
There are four user adjustable parameters. By entering a
special maintenance code, qualified installers can access 
several other parameters to adapt the boiler to special
requirements. In principle, these parameters are factory set 
for all normal applications.

PRODUCTION OF HOT WATER

In addition to its exceptional hot water performances, the 

ACV

Tank-in-Tank concept provides the follwoing advantages :

 

- A solution for scale deposits:

 thanks to the specially designed 

corrugations, the hot water tank expands and contracts during 
the heating cycle, preventing the formation of scale.

 

- A guarantee against the risk of Legionnellae Disease and

bacteria: 

the hot water tank is fully immersed in the primary 

circuit and the hot water is constantly kept at a temperature 
above 60°C.

 

- Exceptional resistance against corrosion and aggression:

 

provided by the stainless steel.

FROST PROTECTION

The boiler is equipped with an integrated frost protection: as soon 
as the boiler temperature drops below 7°C, the system activates 
the central heating pump. As soon as the NTC1 flow temperature 
drops below 3°C, the system automatically ignites the burner until 
the temperature rises above 10°C. The pump continues to run 
for about 10 minutes.

If an outdoor temperature sensor is connected to the system, 
the pump is activated as soon as the outside temperature drops 
below the specified threshold.

To provide efficient protection for the whole system against frost, 
all the valves on the radiators and the convectors should be 
completely open.

INTRODUCTION

Summary of Contents for 35 TC

Page 1: ...EN 1 ENGLISH FRANCAIS NEDERLANDS ESPA OL ITALIANO DEUTSCH 664Y2800 B Installation Operating and Servicing Instructions...

Page 2: ...ey 12 Connection to the gas 13 Domestic hot water connection 13 Heating connections 14 Installation of a single high temperature circuit with room thermostat ACV 15 control 15 Installation of a weathe...

Page 3: ...aller must carry out the assembly commissioning maintenance and repair of the system in accordance with current standards in force ACV shall not accept any responsibility for damage caused by non comp...

Page 4: ...eratures eliminating bacterial formation such as Legionellae as well as resulting in high volume hot water production The down firing flue tubes pass through the upper circuit through the separation p...

Page 5: ...ion chamber 14 Control panel 15 Primary heating circuit 16 Boiler shunt pump 17 Separation plate 18 Drain cock HeatMaster 85 TC 1 Flue connection concentric 100 150 mm convertible to parallel connecti...

Page 6: ...ing the flame limiting the temperature etc and control of the boiler temperature This MCBA also includes a weather dependent regulator All you need to do is connect the outdoor temperature sensor avai...

Page 7: ...nd the last two characters give the current central heating temperature setting To change this temperature press or until the last two digits show the desired temperature value Press Store to save the...

Page 8: ...46 5 137 148 134 145 Flue gas pipe Max pressure drop Pa 130 130 150 150 Concentric flue gas channel maximum length 80 125 mm m 20 20 20 20 Gas G20 G25 G31 Category varies by country I 2E S B I 2Er I...

Page 9: ...HU BE CH ES FR UK IE IT PT CZ DK ES FI FR UK IE IT NL NO PT SE AT CH CZ DE FR I 3P G31 30 mbar I 3P G31 37 mbar I 3P G31 50 mbar I 3 G30 G31 28 30 37 mbar I 3B G30 28 30 mbar I 3B G30 50 mbar DOMESTIC...

Page 10: ...afety contact thermostat RAM optional 21 Ionisation and ignition cable 22 Burner power supply 230 V only HeatMaster 85 TC B Blue Bk Black Br Brown G Grey Or Orange R Red V Violet W White Y Gr Yellow G...

Page 11: ...the meter ventilate the rooms and contact your installer ACCESSIBILITY The appliance must be positioned in such a way to be accessible any time In addition the following distances are required around...

Page 12: ...uarantees optimum combustion with very low emission levels To avoid any condensate flow through the terminal the horizontal flue gas pipes must always be installed with a min slope of 5 mm per meter u...

Page 13: ...the domestic hot water circuit Flush out the system before connecting the domestic hot water part The installation must be fitted with an approved safety unit with a 7 bar safety valve a non return v...

Page 14: ...representative about the use of inhibitors It is possible that the pumps are locked due to the presence of residual water from tests completed on the appliance Therefore we recommend that you unblock...

Page 15: ...Typical setting Description 00 Heating mode OFF 01 Heating mode ON Setting temperature for the heating water adjustable between 30 and 85 C 00 Using a outside temperature sensor and a room thermostat...

Page 16: ...11 module Controls the second heating circuit communicates directly with the MCBA 10800152 HM 35 TC Low temperature kit DN20 Including one circulation pump two isolating valves check valve two thermo...

Page 17: ...djustable between 15 and 25 C 10 Heating pump controlled by room thermostat hot water priority active 21 Heating pump runs continuously hot water priority active 50 Heating pump controlled by room the...

Page 18: ...cuit alarm contact operates only in conjonction with the Room Unit RSC 10800152 HM 35 TC X2 Low temperature kit DN20 Including one circulation pump two isolating valves check valve two thermometers th...

Page 19: ...de OFF 01 Heating mode ON Maximum temperature of the heating circuit must be higher than hot water setpoint AV MPK ZU AUF 0 24V A B VF VE ZMC1 N Y1 Y2 N B A AV MPK ZU AUF 0 24V A B VF VE ZMC1 N Y1 Y2...

Page 20: ...rs are set in accordance with the user s needs see page 3 Directions for Use Check the boiler settings this task can only be carried out by an ACV trained installer or by the ACV maintenance departmen...

Page 21: ...bove Remove the burner gasket Clean the combustion chamber using a vacuum cleaner It could be necessary to clean the flue tubes by putting water in the combustion room After that operation it is neces...

Page 22: ...he temperature two last digits and b with the error code Status Boiler function Standby no demand for heat Fan first fan after Ignition Operation of the boiler burner for the heating Operation of the...

Page 23: ...hanged The screen flashes once to confirm the data has been saved To activate the parameters you changed press MODE once more which brings you into Info mode However if you do not press a key the syst...

Page 24: ...as been accepted STORE Press MODE until the system displays the correct mode REQUEST FOR INFORMATION ON THE INSTALLATION Info Mode To switch from Standby to Info mode press Mode twice Key Screen Descr...

Page 25: ...P Maximum outdoor temperature adjust the heating curve STEP Frost protection temperature STEP Correction of outdoor temperature STEP Blockage T 0 Disabled STEP Acceleration time lag 00 Stop minute STE...

Page 26: ...minute STEP Domestic hot water pump over run time step 10 2 sec STEP Central Heating modulation hysteresis enabled STEP Central Heating modulation hysteresis disabled STEP Domestic hot water modulati...

Page 27: ...n possible hot water priority active 50 Controlled circuit outside sensor AM3 11 module heating pump controlled by room thermostat hot water priority not active 61 Controlled circuit outside sensor AM...

Page 28: ...y Screen Description of parameters STEP Code error of the last lock out STEP Status of the boiler at the time of the error STEP Temperature T1 at the time of the error STEP Temperature T2 at the time...

Page 29: ...NTC1 is OK please verify that the water flows trough the boiler T2 110 C Check the NTC wiring and replace if necessary T1 gradient too high Check that the pump is turning If there is no problem with...

Page 30: ...ction of the NTC2 sensor Check the wiring of the NTC2 sensor If the problem persists replace the NTC2 sensor NTC3 connection open Check the connection of the NTC3 sensor Check the wiring of the NTC3 s...