TOTALLY CONDENSING :

The HeatMaster

®

 TC combines the 

unique ACV Tank-in-Tank concept with

a dual primary circuit resulting in

exceptional performance from a totally 

condensing combination boiler.

Tank-in-Tank technology

ACV’s advanced implementation of thermal storage technology is 
tried and tested and is remarkably simple, efficient and reliable.
At the heart of the 

HeatMaster

®

 

TC

 is a stainless steel tank 

through which the flue tubes pass.
This is surrounded by a mild steel shell containing the primary 
water, which extends down to the combustion chamber and even 
around the flue tubes. The burner fires onto the primary water
which indirectly heats the stainless steel tank containing the hot 
water. As with all Tank-in-Tanks, this is corrugated over its full 
height and is suspended in the 

HeatMaster

®

 

TC

 by its hot and 

cold water connections.
The area of the heat transfer surface is therefore much greater 
than that of standard direct fired water heaters. A much larger 
heat transfer surface means that Tank-in-Tank units recover much 
faster than any other kind of hot water storage device - and keeps 
boiler cycling to a minimum. The high storage temperature within 
the inner tank also results in exceptional hot water outputs.

Dual primary circuit technology

The 

HeatMaster

®

 

TC

 primary circuit is split into two sections - a 

high temperature upper circuit and a low temperature lower circuit, 
divided by a separation plate. The hot water storage tank is located 
in the upper circuit which always operates at a temperature of 
between 60°C and 90°C. This is ideal for hot water production as
it maintains the stored water at constantly high temperatures, 
eliminating bacterial formation such as Legionellae, as well as 
resulting in high volume hot water production.
The down-firing flue tubes pass through the upper circuit, through 
the separation plate and into the lower circuit. The primary water 
here operates at a temperature typically between 30°C and 60°C 
for heating (dependent on the heating return temperature), perfect 
for condensing when working in heating mode.

Dual coil technology

During hot water mode, the bottom circuit operates at a much 
lower temperature, typically 5°C to 20°C depending on the 
cold water inlet temperature. The incoming cold water enters 
the lower primary circuit via an indirect water preheater. As 
this preheater is wrapped around the lower flue tubes of the 
combustion chamber, it is able to absorb the remaining heat 
from the flue gases. The result is that during hot water mode the 

HeatMaster

®

 

TC

 totally condenses whether on full or part-load.

INTRODUCTION

Heating

The heating return
enters the lower circuit
of the boiler, which allows
the boiler to operate
in condensing mode.
The upper circuit of the

HeatMaster

®

 

TC

 is kept

at a consistently high
temperature due to the
internal shunt pump which
ensures that the primary
water circulates around
the heat exchanger flue
tubes.

Heating and
hot water

Once up to temperature,
the 

HeatMaster

®

 

TC

 is

capable of producing
heating and hot water
simultaneously.

Hot water

With the upper circuit 
maintained at high 
temperature, the 

HeatMaster

®

 

TC

 is always 

ready to supply hot water 
on demand.

The cold water enters 
through the indirect water 
preheater at the base of 
the heat exchanger and is 
preheated before entering 
the hot water tank. The low 
temperature of the bottom 
circuit results in continuous 
condensation of the flue 
gases in hot water mode.

Operating modes

In both heating and hot water modes, the premix 
gas burner fully modulates the power to match 
the system demand.

1

3

2

Summary of Contents for 35 TC

Page 1: ...EN 1 ENGLISH FRANCAIS NEDERLANDS ESPA OL ITALIANO DEUTSCH 664Y2800 B Installation Operating and Servicing Instructions...

Page 2: ...ey 12 Connection to the gas 13 Domestic hot water connection 13 Heating connections 14 Installation of a single high temperature circuit with room thermostat ACV 15 control 15 Installation of a weathe...

Page 3: ...aller must carry out the assembly commissioning maintenance and repair of the system in accordance with current standards in force ACV shall not accept any responsibility for damage caused by non comp...

Page 4: ...eratures eliminating bacterial formation such as Legionellae as well as resulting in high volume hot water production The down firing flue tubes pass through the upper circuit through the separation p...

Page 5: ...ion chamber 14 Control panel 15 Primary heating circuit 16 Boiler shunt pump 17 Separation plate 18 Drain cock HeatMaster 85 TC 1 Flue connection concentric 100 150 mm convertible to parallel connecti...

Page 6: ...ing the flame limiting the temperature etc and control of the boiler temperature This MCBA also includes a weather dependent regulator All you need to do is connect the outdoor temperature sensor avai...

Page 7: ...nd the last two characters give the current central heating temperature setting To change this temperature press or until the last two digits show the desired temperature value Press Store to save the...

Page 8: ...46 5 137 148 134 145 Flue gas pipe Max pressure drop Pa 130 130 150 150 Concentric flue gas channel maximum length 80 125 mm m 20 20 20 20 Gas G20 G25 G31 Category varies by country I 2E S B I 2Er I...

Page 9: ...HU BE CH ES FR UK IE IT PT CZ DK ES FI FR UK IE IT NL NO PT SE AT CH CZ DE FR I 3P G31 30 mbar I 3P G31 37 mbar I 3P G31 50 mbar I 3 G30 G31 28 30 37 mbar I 3B G30 28 30 mbar I 3B G30 50 mbar DOMESTIC...

Page 10: ...afety contact thermostat RAM optional 21 Ionisation and ignition cable 22 Burner power supply 230 V only HeatMaster 85 TC B Blue Bk Black Br Brown G Grey Or Orange R Red V Violet W White Y Gr Yellow G...

Page 11: ...the meter ventilate the rooms and contact your installer ACCESSIBILITY The appliance must be positioned in such a way to be accessible any time In addition the following distances are required around...

Page 12: ...uarantees optimum combustion with very low emission levels To avoid any condensate flow through the terminal the horizontal flue gas pipes must always be installed with a min slope of 5 mm per meter u...

Page 13: ...the domestic hot water circuit Flush out the system before connecting the domestic hot water part The installation must be fitted with an approved safety unit with a 7 bar safety valve a non return v...

Page 14: ...representative about the use of inhibitors It is possible that the pumps are locked due to the presence of residual water from tests completed on the appliance Therefore we recommend that you unblock...

Page 15: ...Typical setting Description 00 Heating mode OFF 01 Heating mode ON Setting temperature for the heating water adjustable between 30 and 85 C 00 Using a outside temperature sensor and a room thermostat...

Page 16: ...11 module Controls the second heating circuit communicates directly with the MCBA 10800152 HM 35 TC Low temperature kit DN20 Including one circulation pump two isolating valves check valve two thermo...

Page 17: ...djustable between 15 and 25 C 10 Heating pump controlled by room thermostat hot water priority active 21 Heating pump runs continuously hot water priority active 50 Heating pump controlled by room the...

Page 18: ...cuit alarm contact operates only in conjonction with the Room Unit RSC 10800152 HM 35 TC X2 Low temperature kit DN20 Including one circulation pump two isolating valves check valve two thermometers th...

Page 19: ...de OFF 01 Heating mode ON Maximum temperature of the heating circuit must be higher than hot water setpoint AV MPK ZU AUF 0 24V A B VF VE ZMC1 N Y1 Y2 N B A AV MPK ZU AUF 0 24V A B VF VE ZMC1 N Y1 Y2...

Page 20: ...rs are set in accordance with the user s needs see page 3 Directions for Use Check the boiler settings this task can only be carried out by an ACV trained installer or by the ACV maintenance departmen...

Page 21: ...bove Remove the burner gasket Clean the combustion chamber using a vacuum cleaner It could be necessary to clean the flue tubes by putting water in the combustion room After that operation it is neces...

Page 22: ...he temperature two last digits and b with the error code Status Boiler function Standby no demand for heat Fan first fan after Ignition Operation of the boiler burner for the heating Operation of the...

Page 23: ...hanged The screen flashes once to confirm the data has been saved To activate the parameters you changed press MODE once more which brings you into Info mode However if you do not press a key the syst...

Page 24: ...as been accepted STORE Press MODE until the system displays the correct mode REQUEST FOR INFORMATION ON THE INSTALLATION Info Mode To switch from Standby to Info mode press Mode twice Key Screen Descr...

Page 25: ...P Maximum outdoor temperature adjust the heating curve STEP Frost protection temperature STEP Correction of outdoor temperature STEP Blockage T 0 Disabled STEP Acceleration time lag 00 Stop minute STE...

Page 26: ...minute STEP Domestic hot water pump over run time step 10 2 sec STEP Central Heating modulation hysteresis enabled STEP Central Heating modulation hysteresis disabled STEP Domestic hot water modulati...

Page 27: ...n possible hot water priority active 50 Controlled circuit outside sensor AM3 11 module heating pump controlled by room thermostat hot water priority not active 61 Controlled circuit outside sensor AM...

Page 28: ...y Screen Description of parameters STEP Code error of the last lock out STEP Status of the boiler at the time of the error STEP Temperature T1 at the time of the error STEP Temperature T2 at the time...

Page 29: ...NTC1 is OK please verify that the water flows trough the boiler T2 110 C Check the NTC wiring and replace if necessary T1 gradient too high Check that the pump is turning If there is no problem with...

Page 30: ...ction of the NTC2 sensor Check the wiring of the NTC2 sensor If the problem persists replace the NTC2 sensor NTC3 connection open Check the connection of the NTC3 sensor Check the wiring of the NTC3 s...

Reviews: