A. Chimney Requirements
Vertical distances are measured from the base of the
fi
re-
place as shown in Figure 5.2.
To determine the chimney components needed to complete
your particular installation, follow the steps below:
• Determine the total vertical height of the fireplace
installation. This dimension is measured from the base of
the
fi
replace assembly to the point where the smoke exits
the termination cap.
• Subtract the effective height of the
fi
replace assembly from
the overall height of the
fi
replace installation (measured
from the base of the fireplace to the bottom of the
termination cap).
• Refer to Table 5.1 to determine what components must
be selected to complete the
fi
replace installation.
• Determine the number of ceiling
fi
restops, stabilizers,
roof flashing, etc. required to complete the fireplace
installation.
d & g
Ceiling Firestop
h
i
58-7/8 in.
(1495 mm)
Effective
Height
a,b,c,f
11-10 in. (279-254 mm)
adapter required in
Canada.
Figure 5.2 Chimney Requirements (refer to list in Sect. 5.A.)
Table 5.1
• Do NOT connect this fireplace to a chimney flue
servicing another appliance.
• Do NOT connect to any air distribution duct or
system.
CAUTION
Fire Risk
• Must maintain 2 in. (51 mm) air clearance
to insulation and other combustible
materials.
WARNING
ft
meters
a. Minimum overall straight height
14.0
4.27
b. Minimum height with offset/return
16.5
5.03
c. Maximum height
90.0
27.43
d. Maximum chimney length between an offset and
return
20.0
6.1
e. Maximum distance between chimney stabilizers
35.0
10.67
f. Double offset/return minimum height
22.0
6.71
g. Maximum unsupported chimney length between the
offset and return
6.0
1.83
h. Maximum unsupported chimney height above the
fi
replace
35.0
10.67
i. Maximum unsupported chimney above roof
6.0
1.83
Note:
A maximum of two pairs offsets and returns may
be used.
HEIGHT OF CHIMNEY
COMPONENTS
in.
mm
US
Canada
Chimney Stabilizer
SL11
SL4
4-3/4
121
Ceiling Firestops
FS538
FS538
0
0
FS540
FS540
0
0
Offsets/Returns
SL1130
SL430
14-1/2
368
Roof Flashing
RF570
RF570
0
0
RF571
RF571
0
0
Chimney Sections*
SL1106
SL406
4-3/4
121
SL1112
SL412
10-3/4
273
SL1118
SL418
16-3/4
425
SL1136
SL436
34-3/4
883
SL1148
SL448
46-3/4
1187
n/a
SLA10
16-3/4
425
* Dimensions re
fl
ect effective height.