Heatilator • ST42A US-CAN • 4012-039 Rev D • 11/07
10
B. Clearances
2 in. (51 mm) min.
0 in. to level
of standoffs
Attic
Insulation
Shield
Ceiling Firestop
(ceiling)
(roof)
(attic)
(ceiling)
Ceiling Firestop
Offset/Return with
hanger straps
Storm Collar
Roof Flashing
1/2 in. (13 mm) to side of appliance
2 in. (51 mm) min.
2 in. min.
(51 mm)
Must have 2 in. (51 mm)
minimum clearance
to header
0 in.
to floor
2 in. (51 mm) min.
2 in. (51 mm) min.
2 in. (51 mm) min.
2 in. (51 mm) min.
Figure 3.2 Clearances to Combustible Materials
Fire Risk
• Comply with all minimum clearances to combustibles as speci
fi
ed.
• Framing
or
fi
nishing material used on the front of, or in front of, the
appliance closer than the minimums listed, must be constructed entirely
of noncombustible materials (i.e., steel studs, concrete board, etc.).
Failure to comply may cause
fi
re.
WARNING
Note:
Chimney air kit and 11-10 in. (279-254 mm) adapter not
shown but required in Canada.