NA SERIES INSTALLATION INSTRUCTIONS

WARNING!

Maintain a minimum of 2” air clearance to all

parts of the chimney system at all times! 

Fail-

ure to maintain this 2” air clearance will cause

a structure fire.

CAUTION:

Inner  flue  and  outer  liner  sections  cannot  be

disassembled  once  locked  together.    Plan

ahead to ensure the proper installation height

is achieved with the selected chimney compo-

nents.

Figure 12 - Installing an Attic Insulation Shield

Note: 

You must provide support for the pipe during

construction and check to be sure inadvertent load-

ing has not dislodged the chimney section from the

fireplace or at any chimney joint.

WARNING!

When chimney sections exceeding six feet in

length are installed between an offset and re-

turn, structural support must be provided to re-

duce off-center loading and prevent chimney

sections from separating at the chimney joints.

Figure 13 - Offset/Return with Stabilizer

6. Attic Insulation Shield

An insulation shield should be installed when there is

a possibility of insulation coming into contact with the

factory built chimney system. The insulation shield is

installed  by  positioning  it  over  the  vertical  chimney

section  where  it  penetrates  a  firestop  spacer.  The

firestop spacer will support the insulation shield. See

Figure 12.

7. Double-checking the Chimney Assembly

Continue assembling the chimney sections up through

the  firestop  spacers  as  needed.  While  doing  so,  be

aware of the height and unsupported chimney length

limitations that are given on page 12 under “Chimney

Requirements”.
Check each section by pulling up slightly from the top

to  ensure  proper  engagement  before  installing  the

succeeding  sections.  If  they  have  been  connected

correctly, they will not disengage when tested.

8. Securing the Chimney System

When offsets and returns are joined to straight pipe

sections,  they  must  be  locked  into  position  with  the

screws provided (outer only), using the predrilled holes.

To prevent gravity from pulling the chimney sections

apart,  the  returns  and  the  chimney  stabilizers  have

straps for securing these parts to joists or rafters. See

Figure 13.

Summary of Contents for NA36

Page 1: ...42 WOODBURNING FIREPLACE WARNING Improper installation adjustment alteration service or maintenance can cause injury or property damage Refer to this manual For assistance or additional information co...

Page 2: ...r related problems that may result from the lack of adequate combustion air It is the responsibility of the builder contractor to ensure that adequate combustion air has been provided for the fireplac...

Page 3: ...f the home If you desire to put a fireplace in your basement we recommend that you consider a direct vent gas fireplace Basements always have a significant negative air pressure that causes the firepl...

Page 4: ...illustrations and diagrams used throughout these installation instructions are not drawn to scale Figure 1 Typical Fireplace System B DESCRIPTION OF THE FIREPLACE SYSTEM A LISTINGS AND CODE APPROVALS...

Page 5: ...i b a C d e h c r A 6 3 0 1 P D 2 4 0 1 P D h s i n i F k c a l B s r o o D s s a l G n o i t p e c r e P B 6 3 0 1 P D B 2 4 0 1 P D h s i n i F s s a r B d e h s i l o P s r o o D s s a l G n o i t...

Page 6: ...6 17789 Rev H 07 03 NA SERIES INSTALLATION INSTRUCTIONS Fireplace Dimensions OUTSIDE AIR KIT AK14 NAAK14...

Page 7: ...5 1 3 L S 5 1 n r u t e R t e s f f O y e n m i h C 0 3 3 L S A N 0 3 3 L S 0 3 n r u t e R t e s f f O y e n m i h C 8 3 3 S F A N 8 3 3 S F t h g i a r t S p o t s e r i F 9 3 3 S F 5 1 p o t s e r...

Page 8: ...ARF370 Roof Flashing Flat to 6 12 Pitch RF371 Roof Flashing 6 12 to 12 12 Pitch CB876 Chimney Bracket AS8 Straight Attic Insulation Shield Chimney Sections Firestop Spacer JB877 Joint Band g o l a t a...

Page 9: ...TION INSTRUCTIONS LDS33 3 x 3 LDS46 4 x 6 Decorative Shroud TR344 NATR344 Round Termination Cap TR342 Round Telescoping Termination Cap ST375 Square Termination Cap CT35 Chase Top CAK4A Chimney Air Ki...

Page 10: ...n a basement near frequently opened doors central heat outlets or returns or other locations of considerable air movement can affect the performance and cause intermittent smoke spillage from the fron...

Page 11: ...opening with the width shown in the Table below x 40 tall The finished cavity depth must be no less than 23 Figure 5 shows a typical framing using 2 x 4 lumber of the fireplace assuming combustible m...

Page 12: ...fireplace location the chimney construction and necessary clearances must be considered The fireplace system and chimney components have been tested to provide flexibility in construction The followi...

Page 13: ...Whenever the chimney penetrates a floor ceiling a firestop spacer must be installed 6 The effective height of the fireplace assembly is measured from the base of fireplace to top of starter collar See...

Page 14: ...e what components must be selected to complete the fireplace installation d Determine the number of firestop spacers stabi lizers roof flashing etc required to complete the fireplace installation 2 Ch...

Page 15: ...he instructions for framing on pages 10 12 Slide the fireplace into position Be sure to provide the minimum air clearance at the sides and back of the fireplace assembly 2 Placing the Protective Metal...

Page 16: ...ion meets the stop bead on the lower section The inner flue is placed to the inside of the flue section below it The outer casing is placed outside the outer casing of the chimney section below it See...

Page 17: ...n insulation shield should be installed when there is a possibility of insulation coming into contact with the factory built chimney system The insulation shield is installed by positioning it over th...

Page 18: ...r See page 22 for building a chase 14 Installing the Chimney Air Kit Required in Canada When installing the chimney air kit follow the instructions provided with this accessory 13 Installing the Outsi...

Page 19: ...replace to allow for connection of a certified gas log lighter or a decorative gas appliance with a maximum input of 100 000 BTU hour incorporating an automatic gas shut off device and complying with...

Page 20: ...fireplace from both radiant heat and sparks The construction of and materials used for a hearth extension are shown in Figures 17 and 18 A hearth extension of this construction may be covered with an...

Page 21: ...terials are those consisting entirely of steel iron brick tile concrete slate glass or plasters or any combination thereof c Noncombustible Sealant Material Sealants which will not ignite and burn Gen...

Page 22: ...8 level above the fireplace assembly This reduces heat loss through the chase 4 In cold climates the walls of the chase should be insulated to the level of the false ceiling as shown in Figure 21 Thi...

Page 23: ...Cap a Install the chimney sections up through the chase enclosure When using a TR344 NATR344 round termination cap the uppermost top section of pipe must extend 6 above the top of the chase collar to...

Page 24: ...ey system and enclosure To protect against the effects of corrosion on those parts exposed to the weather we recommend that the chase top and termination cap be painted with a rust Figure 24 Installin...

Page 25: ...ces for Installation in Vented Fireplaces ANSI Z21 60 When operating your fireplace the flue damper must be in the open position This fireplace was not tested and listed for use with an unvented gas l...

Page 26: ...e a greater density than soft woods A piece of hardwood will contain about 60 more BTU s than an equal size piece of soft wood Firewood is commonly sold by the cord 128 cu ft A cord of seasoned oak ha...

Page 27: ...od to allow air to circulate freely around and through the woodpile b Elevate the woodpile off the ground to allow air circulation underneath c The smaller the pieces the faster the drying process Any...

Page 28: ...imney is clean and free of creosote buildup Make sure overhanging trees and branches are cut back within ten feet of the top of the chimney Ensure the chimney cap is clean and free of any buildup of s...

Page 29: ...d If creosote has accumulated it should be removed to reduce the risk of a chimney fire 3 Chimney Cleaning If you do detect a buildup of creosote contact a qualified chimney sweep or clean it yourself...

Page 30: ...30 17789 Rev H 07 03 NA SERIES INSTALLATION INSTRUCTIONS HOMEOWNER S NOTES...

Page 31: ...estop Spacer 8 Installation 16 Firewood 25 26 Flue 25 Framing 11 Fuel 25 26 G Gas Codes 19 25 Gas Knockout Location 6 Gas Log Lighter Provisions 19 General Information 25 Glass Doors 5 21 26 Grate 26...

Page 32: ...haust fans or forced air furnaces or other causes 5 use of fuels other than those specified in the Operating Instructions 6 installation or use of components not supplied with the Fireplace or any oth...

Reviews: