Heatilator • CRAVE4836-C/ST-C, CRAVE6048-C/ST-C, CRAVE7260-C/ST-C, CRAVE8472-C/ST-C Installation Manual • 2601-980 Rev. N • 11/21
30
B. Vent Termination Minimum Clearances
Roof Pitch
H (Min.) Ft
Flat to 6/12...........................................................1.0*
Over 6/12 to 7/12 .................................................1.25*
Over 7/12 to 8/12 .................................................1.5*
Over 8/12 to 9/12 .................................................2.0*
Over 9/12 to 10/12 ...............................................2.5*
Over 10/12 to 11/12 .............................................3.25
Over 11/12 to 12/12 .............................................4.0
Over 12/12 to 14/12 .............................................5.0
Over 14/12 to 16/12 .............................................6.0
Over 16/12 to 18/12 .............................................7.0
Over 18/12 to 20/12 .............................................7.5
Over 20/12 to 21/12 .............................................8.0
Figure 4.1 Minimum Height From Roof to Lowest Discharge
Opening
HORIZONTAL
OVERHANG
VERTICAL
WALL
GAS DIRECT VENT
TERMINATION CAP
12
X
ROOF PITCH
IS X/ 12
LOWEST
DISCHARGE
OPENING
2 FT.
MIN.
20 INCHES MIN.
H (MIN.) - MINIMUM HEIGHT FROM ROOF
TO LOWEST DISCHARGE OPENING
4
4
Termination Location and Vent Information
Fire Risk.
Maintain vent clearance to combustibles as
specified.
•
DO NOT
pack air space with insulation or other
materials.
Failure to keep insulation or other materials away
from vent pipe could cause overheating and fire.
WARNING
* H minimum may vary depending on regional snowfall.
Refer to local codes.
A. Approved Pipe
WARNING! Risk of Fire, Delayed Ignition or Asphyxi-
ation.
This appliance requires a separate vent.
DO NOT
vent to a pipe serving any other appliance.
This appliance is only approved for use with Hearth &
Home Technologies DVP venting systems. Refer to Sec
-
tion 12.A for vent component information and dimensions.
Only use listed decorative termination caps/shrouds with
Hearth & Home Technologies approved venting systems.
DO NOT
mix pipe, fittings or joining methods from differ
-
ent manufacturers.
The pipe is tested to be run inside an enclosed wall.
There is no requirement for inspection openings at each
joint within the wall.