74
Defrost #8 start time (0000 to 2330 HHMM), 2530 if not used
Word
41
DF08
Defrost #9 start time (0000 to 2330 HHMM), 2530 if not used
Word
42
DF09
Defrost #10 start time (0000 to 2330 HHMM), 2530 if not used
Word
43
DF10
Defrost #11 start time (0000 to 2330 HHMM), 2530 if not used
Word
44
DF11
Defrost #12 start time (0000 to 2330 HHMM), 2530 if not used
Word
45
DF12
Number of CU fans (1 to 4)
Word
46
CU Fan #1 mode (0=off, 1=on, 2=press. ctl., 3=temp. ctl.)
Word
47
FAN1
CU Fan #2 mode (0=off, 1=on, 2=press. ctl., 3=temp. ctl.)
Word
48
FAN2
CU Fan #3 mode (0=off, 1=on, 2=press. ctl., 3=temp. ctl.)
Word
49
FAN3
CU Fan #4 mode (0=off, 1=on, 2=press. ctl., 3=temp. ctl.)
Word
50
FAN4
CU Fan #1 On pressure (125 to 315 psia), displayed as 110 to 300 psig
Word
51
F1ON
CU Fan #2 On pressure (125 to 315 psia), displayed as 110 to 300 psig
Word
52
F2ON
CU Fan #3 On pressure (125 to 315 psia), displayed as 110 to 300 psig
Word
53
F3ON
CU Fan #4 On pressure (125 to 315 psia), displayed as 110 to 300 psig
Word
54
F4ON
CU Fan #1 Off pressure (125 to 315 psia), displayed as 110 to 300 psig
Word
55
F1OF
CU Fan #2 Off pressure (125 to 315 psia), displayed as 110 to 300 psig
Word
56
F2OF
CU Fan #3 Off pressure (125 to 315 psia), displayed as 110 to 300 psig
Word
57
F3OF
CU Fan #4 Off pressure (125 to 315 psia), displayed as 110 to 300 psig
Word
58
F4OF
CU Fan #1 On temperature (+30 to +90 degrees F)
Word, signed
59
F1ON
CU Fan #2 On temperature (+30 to +90 degrees F)
Word, signed
60
F2ON
CU Fan #3 On temperature (+30 to +90 degrees F)
Word, signed
61
F3ON
CU Fan #4 On temperature (+30 to +90 degrees F)
Word, signed
62
F4ON
CU Fan #1 Off temperature (+30 to +90 degrees F)
Word, signed
63
F1OF
CU Fan #2 Off temperature (+30 to +90 degrees F)
Word, signed
64
F2OF
CU Fan #3 Off temperature (+30 to +90 degrees F)
Word, signed
65
F3OF
CU Fan #4 Off temperature (+30 to +90 degrees F)
Word, signed
66
F4OF
(not used)
---
67 to 7999
Remote Control (0xAA55=activate, 0xFF00=deactivate)
Word
8000
NOTE: The Write Remote Control command with a data value of 'activate'
is ignored unless the Mohave Control is in "Off" or "Service" modes
Diagnostic -
CMD 0x08 (Read/Write)
Sub-Function
Restart communications
0x01
Clear Counters and Diagnostic Register
0x0A
Read Bus Message Counter
0x0B
Read Bus Communication Error Counter
0x0C
Read Bus Exception Error Counter
0x0D
Read Slave Message Counter
0x0E
Read Slave No Response Counter
0x0F
Read Slave NAK Counter
0x10
Read Slave Busy Counter
0x11
Read Bus Character Overrun Counter
0x12
Clear Overrun Counter and Flag
0x14
Activate Remote Control mode
0xAA55
Deactivate Remote Control mode
0xFF00
NOTE: The Activate Remote Control command is ignored
unless the Mohave Control is in "Off" or "Service" modes
Mohave Hot Gas Control Modbus Definitions
Summary of Contents for Mohave
Page 13: ...13 Piping The following are examples of proper piping layout for typical system configurations...
Page 14: ...14 Piping...
Page 38: ...38 Standard Independent Evaporator Power Supply with VFD Condenser Fans Wiring Diagram...
Page 39: ...39 Standard Independent Evaporator Power Supply with VFD Condenser Fans Wiring Diagram...
Page 45: ...45 Defrost Operation Black Piping Inactive Gray Piping Active Hot Gas Defrost Cycle Diagrams...
Page 46: ...46 Defrost Operation Black Piping Inactive Gray Piping Active Hot Gas Defrost Cycle Diagrams...
Page 75: ...75 Notes...