Smart Defrost Kit (SDK) Summary
The condensing unit control panel contains the relays, contactors,
time delay and a terminal block which is appropriately marked to
match the low voltage wiring connections. A sensor for outdoor air
temperature measurement is installed on the condensing unit.
System Requirements
• Refrigeration Systems with electric defrost heaters
• Defrost Control Voltage must be 230VAC, 50Hz or 60Hz
• System must have electro-mechanical time clock that
contains a contact closure reset input for defrost
termination
System Requirements
Technical Information
•
Dimensions
•
Operational Temperature Range: -40F to +130F
•
Humidity: 0-95% relative humidity non-condensing
over operational range
•
Operational Voltage Range: 187-260 VAC
•
Frequency: 50/60Hz
•
UL Recognized
©2019 Heatcraft Worldwide Refrigeration
IMPORTANT NOTE:
On multiple evaporators, since a
transformer is in each evaporator, the voltage tap must
be set on each evaporator.