background image

11

Leak Detection And Evacuation

Leak Testing

After all lines are connected, the entire system must be leak tested. The complete system should be 
pressurized to not more than 150 PSIG with refrigerant and dry nitrogen. The use of an electronic type 
of leak detector is highly recommended because of its greater sensitivity to small leaks. As a further 
check, it is recommended that this pressure be held for a minimum of 12 hours and then rechecked. For a 
satisfactory installation, the system must be leak tight.

Leak detection can be carried out in the conventional manner. If HCFC or CFC tracer gas is used, care must 
be taken to completely remove all traces of the gas prior to introducing HFC’s. Electronic leak detectors 
are now available that will sense HFC’s. This is considered preferable since it removes the possibility of 
chlorine remaining in the system after leak testing with HCFC’s and/or HCFC’s. There is a view that even 
small quantities of chlorine may act as a catalyst encouraging copper plating and/or corrosion and should 
therefore be avoided.

Within the last several years, manufacturers have developed fluorescent dye leak detection systems 
for use with refrigerants.  These dyes mix with the lubricant and, when exposed to an ultraviolet light, 
fluoresce to indicate the location of leaks. Copeland has tested and approved the Rigid “System Safe” dye 
and found it to be compatible with the compressor materials in systems.

Evacuation

 

 

 

 

       

CAUTION:

  Do not use the refrigeration compressor

 

 

 

 

 

 

to evacuate the system. Do not start the

 

 

 

 

 

 

compressor while it is in a vacuum.

Due to the smaller molecule size of HFC’s, they will tend to leak more readily than CFC. Consequently, it 
is of the utmost importance that proper system evacuation and leak detection procedures be employed. 
Copeland recommends a minimum evacuation to 500 microns. In addition, a vacuum decay test is strongly 
recommended to assure there is not a large pressure differential between the system and vacuum pump. 
Good evacuation processes include frequent vacuum pump oil changes and large diameter, short hose 
connections to both high and low sides of the system preferably using bronze braided hose.

A good, deep vacuum pump should be connected to both the low and high side evacuation valves with 
copper tube or high vacuum hoses (1/4” ID minimum). If the compressor has service valves, they should 
remain closed. A deep vacuum gauge capable of registering pressure in microns should be attached to the 
system for pressure readings.

A shut-off valve between the gauge connection and vacuum pump should be provided to allow the 
system pressure to be checked after evacuation. Do not turn off vacuum pump when connected to an 
evacuated system before closing shut-off valve.

The vacuum pump should be operated until a pressure of 1,500 microns absolute pressure is reached – at 
which time the vacuum should be broken with the refrigerant to be used in the system through a drier 
until the system pressure rises above “0” psig.

 

 

 

NOTE:

  Refrigerant used during evacuation can not be vented.

 

 

 

 

Reclaim all used refrigerant. EPA regulations are constantly

 

 

 

 

being updated. Ensure your procedures follow correct regulations.

Repeat this operation a second time.

Open the compressor’s service valves and evacuate the entire system to 500 microns absolute pressure. 

Raise the pressure to 2 psig with the refrigerant and remove the vacuum pump.

Summary of Contents for FlexPack H-IM-FP

Page 1: ...1 Multiple Compressor Condensing Units H IM FP March 2004 Part No 25006801 Nomenclature 2 General Safety Information 2 Compressor Module Speci cations 3 4 Dimensional Diagrams 5 Condensing Unit Placem...

Page 2: ...hipment should be carefully checked against the bill of lading The shipping receipt should not be signed until all items listed on the bill of lading have been accounted for Check carefully for concea...

Page 3: ...FV 208 230 1 60 11 2 61 0 17 4 40 404a 9 25 30 CS14K6E TF5 208 230 3 60 8 2 55 0 12 8 40 404a 9 25 30 CS18K6E PFV 208 230 1 60 14 4 82 0 22 4 40 404a 22 25 30 CS18K6E TF5 208 230 3 60 9 4 65 5 14 6 40...

Page 4: ...0 30 0 80 404a 22 5 35 ZS45K4E TF5 208 230 3 60 21 5 156 0 33 5 80 404a 22 5 35 ZF06K4E PFV 208 230 1 60 12 2 61 0 19 0 40 404a 22 40 0 ZF06K4E TF5 208 230 3 60 8 3 55 0 13 0 40 404A 22 40 0 ZF08K4E P...

Page 5: ...e Fan Top View Two Fan Top View Three Fan Top View X 59 00 Single Fan Length X 78 00 Two Fan Length X 100 50 Three Fan Length Please note system positions Liquid Lines Suction Lines Electrical Knockou...

Page 6: ...orrosive atmospheres require custom designed condensers Another consideration which must be taken is that the unit should be mounted away from noise sensitive spaces and must have adequate support to...

Page 7: ...rigging measures must be taken to support unit weight and to protect the unit from damage during unloading and placement process Rigging holes have been provided in legs and under the unit compressor...

Page 8: ...0 feet towards the compressor in direction of ow d Suitable P type oil traps should be located at the base of each suction riser to enhance oil return to the compressor e For desired method of superhe...

Page 9: ...drain lines should be used and properly protected from freezing In running drain lines provide a minimum of 4 inches per foot pitch for proper drainage Drain lines should be at least as large as the e...

Page 10: ...copper tubing 4 Do not use short radius ells Short radius elbows have points of excessive stress concentration and are subject to breakage at these points 5 Thoroughly inspect all piping after the equ...

Page 11: ...olecule size of HFC s they will tend to leak more readily than CFC Consequently it is of the utmost importance that proper system evacuation and leak detection procedures be employed Copeland recommen...

Page 12: ...d in the condensing unit for proper connections 3 Wire type should be of copper conductor only and of the proper size to handle the connected load 4 The unit must be grounded 5 For multiple evaporator...

Page 13: ...e set at two minutes the third marker c Check high and low pressure controls pressure regulating valves oil pressure safety controls and all other safety controls and adjust them if necessary d Liquid...

Page 14: ...djust if necessary e Check head pressure controls for pressure setting f Check crankcase heater operation if used g Install instruction card and control system diagram for use of building manager or o...

Page 15: ...ng potentially costly repairs of a premature failure due to equipment neglect The following is our minimum recommendations for regularly scheduled preventive maintenance of your refrigeration system O...

Page 16: ...16 Preventive Maintenance...

Page 17: ...17 Preventive Maintenance...

Page 18: ...an Blade 22999901 Fan Guard Motor Mount 23104401 High Pressure Control 28913201 Low Pressure Control Adjustable 2891402 Fixed 28913401 Time Delay Relay Low Pressure Switch 22536801 Fuse 15 Amp 2251000...

Page 19: ...M1 1 R1 0 NO C C1A1 NC CCH1 Fused Disconnect 208 230 V 60 HZ 1 PH PB1 GR POWER SUPPLY RC1 RUN CAPACITOR SC1 START CAPACITOR SR1 START RELAY C1 COMP1 R C S COMP1 C1 SC1 1 SR1 5 2 RC1 CCH2 NO C2A1 NC C2...

Page 20: ...mpressor Superheat for the COOLER Should be between 20 F 30 F YES NO Check Compressor Superheat for the FREEZER Should be between 20 F 30 F YES NO Force unit into a Defrost Check heater amps Should ma...

Page 21: ...on Pressure ______PSIG System 3 Suction Pressure ______PSIG System 1 Suction Temp ______ F System 2 Suction Temp ______ F System 3 Suction Temp ______ F System 1 Refrigerant Charge ______lbs System 2...

Page 22: ...22 Notes...

Page 23: ...23 Notes...

Page 24: ...inuing effort we reserve the right to make changes in speci cations without notice WARNING Refrigerant can be harmful if it is inhaled Refrigerant must be used and recovered responsibly Failure to fol...

Reviews: