7
Start-Up Operation
Single System With 1 Evaporator
• Check all wiring connections to be sure they are
correct and tight.
• On the condensing unit
-
Check the setting of time delay relay.
It should be set at 1 minute {the second
marker).
-
Check the adjustable low pressure switch
setting on freezer units. Refer to H-IM-CU. On
some condensing units, the low pressure switch
has a fixed setting and cannot be adjusted.
• Turn power on
Start-Up Operation
CU
M
M
= Master Evaporator
CU
= Condensing unit
• On the evaporator
-
Use the “
PROGRAM REVIEW
” button to scroll
through settings.
-
Check “
rEF
” (Refrigerant Type). Factory defaults
are: Air Defrost R-404A, Electric Defrost R-404A.
Change to the refrigerant being used.
-
Check
“
bot
”
(Box Temperature). Factory
defaults are: air defrost 35°F and electric defrost
–10°F. Change to the desired temperature.
-
Review and change other settings if necessary
-
See procedures on pages 11-12 for how to
change settings.