Heat&GloGlo 6000CF-OAK-IPI Owner'S Manual Download Page 28

28

Heat & Glo  •  6000CF-OAK-IPI  •  2092-900  Rev. 

I

  •  1/06

NOTE:

  Have the gas supply line installed in accordance

with local building codes, if any. If not, follow ANSI 223.1.

Installation should be done by a qualified installer approved

and/or  licensed  as  required  by  the  locality.  (In  the

Commonwealth  of  Massachusetts  installation  must  be

performed by a licensed plumber or gas fitter.)

A.  Fuel Conversions

WARNING

Fire Risk.

Explosion Hazard.

High pressure will damage valve.

• Disconnect gas supply piping BEFORE

pressure testing gas line at test pressures

above 1/2 psig.

• Close the manual shutoff valve BEFORE

pressure testing gas line at test pressures

equal to or less than 1/2 psig.

B.    Gas Pressures

C.    Gas Connection

Proper input pressures are required for optimum appliance

performance. Gas line sizing requirements need to be made

following NFPA51.

Gas Information

9

NOTE:

    Gas  line  may  be  run  from  either  side  of  the

appliance provided the hole in the outer wrap does NOT

exceed 2-1/2 inches in diameter and does not penetrate

the firebox.

NOTE:

A listed (and Commonwealth of Massachusetts ap-

proved) 1/2 inch (13mm) T-handle manual shut-off valve and

flexible gas connector are connected to the 1/2 inch (13mm)

control valve inlet.

• If substituting for these components, please consult

local codes for compliance.

NOTE:

The  gap  between  supply  piping  and  gas  access

hole may be caulked with high temperature caulk or stuffed

with  non-combustible,  un-faced  insulation  to  prevent  cold

air  infiltration.

Before  making  gas  connections  ensure  that  appliance

being installed is compatible with the available gas type.
Any natural or propane gas conversions necessary to meet

the appliance and locality needs must be made by a quali-

fied technician using Hearth & Home Technologies speci-

fied and approved parts.

Refer to Reference Section 16 for location of gas line ac-

cess in appliance.

WARNING

Gas Leak Risk

• Support  control  when  attaching  pipe  to

prevent bending gas line.

WARNING

Verify inlet pressures.
• High  pressure  may  cause  overfire

condition.

• Low  pressure  may  cause  explosion.
• Verify  minimum  pressures  when  other

household  gas  appliances  are  operating.

Install  regulator  upstream  of  valve  if  line

pressure is greater than 1/2 psig.

Pressure requirements for appliance are shown in the ta-

ble below. Minimum pressures must be met when other

household gas appliances are operating.

Pressure

Natural Gas

Propane

Minimum

5.0 inches

11.0 inches

Inlet Pressure

w.c.

w.c.

Maximum Inlet

14.0 inches

14.0 inches

Gas Pressure

w.c.

w.c.

Manifold

3.5 inches

10.0 inches

Pressure

w.c.

w.c.

Summary of Contents for 6000CF-OAK-IPI

Page 1: ...dren in same room as appliance Alert children and adults to hazards of high temperatures Do NOT operate with protective barriers open or removed Keep clothing furniture draperies and other combustible...

Page 2: ...ce can be found on the rating plate usually located in the control area of the appliance Homeowner Reference Information Heat Glo a of Hearth Home Technologies Inc brand 20802 Kensington Boulevard Lak...

Page 3: ...tact Information 54 Section 1 Listing and Code Approvals A Appliance Certification 4 B Glass Specifications 4 C BTU Specifications 4 D High Altitude Installations 4 E Non Combustible Materials Specifi...

Page 4: ...ifice to a smaller size Input rate should be reduced by 4 for each 1000 feet above a 2000 foot elevation in the U S A or 10 for elevations between 2000 and 4500 feet in Canada If the heating value of...

Page 5: ...ing The vent system components and trim doors are shipped in separate packages The gas logs may be packaged separately and must be field installed Report to your dealer any parts damaged in shipment p...

Page 6: ...from traffic areas A Selecting Appliance Location When selecting a location for your appliance it is important to consider the required clearances to walls see Figure 3 1 Figure 3 1 Appliance Location...

Page 7: ...her prevent drafts the wall shield and ceiling firestops should be caulked with high temperature caulk to seal gaps Gas line holes and other openings should be caulked with C Clearances Fire Risk Cons...

Page 8: ...ther Combustibles above Appliance Figure 3 4 Clearances to Mantel Legs or Wall Projections Acceptable on both sides of opening Note All measurements in inches 1 inch 3 feet MANTEL LEG Top View 7 1 4 7...

Page 9: ...Over 18 12 to 20 12 7 5 Over 20 12 to 21 12 8 0 Figure 4 1 Figure 4 2 Minimum Height from Roof to Lowest Discharge Opening Termination Locations 4 Measure horizontal clearances from this surface Meas...

Page 10: ...nd with an overhang are permitted with the dimensions specified for vinyl or non vinyl siding and soffits 1 There must be 3 feet minimum between termination caps 2 All mechanical air intakes within 10...

Page 11: ...run A length of straight pipe is allowed between two 450 elbows see Figure 5 1 Figure 5 1 A Vent Table Key The abbreviations listed in this vent table key are used in the vent diagrams Symbol Descrip...

Page 12: ...pipe may cause fire WARNING 1 Top Vent Horizontal Termination One Elbow Two Elbows V1 Minimum H1 Maximum 6 inches 152mm 3 ft 914 mm 1 ft 305 mm 3 ft 914 mm 2 ft 610 mm 6 ft 1 8 m 3 ft 914 mm 9 ft 2 7...

Page 13: ...457 mm 6 ft 1 8 m 1 ft 305 mm 3 ft 914 mm 1 ft 305 mm 3 ft 914 mm 2 ft 607 mm 6 ft 1 8 m 2 ft 610 mm 6 ft 1 8 m 2 ft 610 mm 6 ft 1 8 m 4 ft 1 4 m 12 ft 3 7 m 3 ft 914 mm 9 ft 2 7 m 3 ft 914 mm 9 ft 2...

Page 14: ...t 305 mm 3 ft 914 mm 2 ft 607 mm 6 ft 1 8 m 4 ft 1 2 m 12 ft 3 7 m V1 V2 H1 50 ft 15 2m Max No specific restrictions on this value EXCEPT V1 V2 H1 cannot exceed 50 ft 15 2m V1 6 inches 152 mm Min NOTE...

Page 15: ...tinued V1 H1 H2 V2 V1 V2 Minimum H1 H2 Maximum 6 in 152 mm 3 ft 914 mm 3 ft 914 mm 1 ft 305 mm 3 ft 914 mm 3 ft 914 mm 2 ft 610 mm 6 ft 1 8 m 6 ft 1 8 m 4 ft 1 2 m 12 ft 3 7 m 12 ft 3 7 m H1 H2 17 ft...

Page 16: ...the shield in place using the four pilot holes pro vided in the part Position the shield so the longest dimension 13 1 2 inch is placed in same direction the elbow is pointing Center the shield direc...

Page 17: ...e being penetrated is surrounded by noncombusti ble materials such as concrete a hole with diameter one inch greater than the pipe is acceptable B Wall Penetration Framing Figure 6 5 Horizontal Ventin...

Page 18: ...the vent pipe Installing Attic Shield Note An additional ceiling firestop is not required if attic shield is used Frame opening for attic shield Attic shield may be installed above or below ceiling s...

Page 19: ...d slots The face of the sheetrock ledge assembly and the unit surround should be flush to each other Figure 7 3 Remove the lower access panel to run the electrical and gas lines to the unit see Figure...

Page 20: ...bs on each side Keep nailing tabs flush with the framing Secure the appliance to the framing by using nails or screws through the nailing tabs Figure 7 4 Proper Positioning Leveling and Securing of Ap...

Page 21: ...7 8 3 Center the Flue Restrictor on vent and secure in place by using two self tapping screws see Figure 7 8 CHART Vertical Top Vent NG Top Vent LP 4 1 1 No Restrictor 8 2 2 1 2 15 3 3 3 2 20 3 4 3 3...

Page 22: ...from horizontal to vertical one screw minimum should be put in the outer flue at the horizontal elbow joint to prevent the elbow from rotating Use screws no longer than 1 inch If predrilling screw ho...

Page 23: ...ng the inner and outer flues of the slip section can be cut to the desired length Assembling Minimum Installations MI Sections MI sections are non unitized so that they can be cut to a certain length...

Page 24: ...of pipe must be supported every 8 feet after the 25 foot maximum unsupported rise The vent support or plumber s strap spaced 120 apart may be used to do this see Figure 8 8 Horizontal Sections Horizon...

Page 25: ...rom the pipe section see Figure 8 12 Installing the Horizontal Termination Cap Vent termination must not be recessed in the wall Siding may be brought to the edge of the cap base Flash and seal as app...

Page 26: ...oof Pitch H Min Ft HORIZONTAL OVERHANG VERTICAL WALL TERMINATION CAP 12 X ROOF PITCH IS X 12 LOWEST DISCHARGE OPENING H MIN MINIMUM HEIGHT FROM ROOF TO LOWEST DISCHARGE OPENING 2 FT MIN 20 INCHES To a...

Page 27: ...both halves of the storm collar with two screws see Figure 8 15 Wrap the storm collar around the exposed pipe section and align brackets Insert a bolt provided through the brackets and tighten nut to...

Page 28: ...o the 1 2 inch 13mm control valve inlet If substituting for these components please consult local codes for compliance NOTE The gap between supply piping and gas access hole may be caulked with high t...

Page 29: ...heck with local authorities Ensure that gas line does not come in contact with outer wrap of appliance Follow local codes Incoming gas line should be piped into the valve com partment and connected to...

Page 30: ...irements Wiring for optional accessories should be done now to avoid reconstruction This appliance may be used with a wall switch wall mounted thermostat and or a remote control If using thermostat us...

Page 31: ...TERMITTENT PILOT IGNITOR IGNITION MODULE 3V ON OFF WALL SWITCH LOW VOLTAGE PLUG IN 3V TRANSFORMER NEUTRAL HOT GROUND FLAME SPARKER SENSOR REMOTE CONTROL SEE NOTE 1 ORG WHT VALVE PIGGYBACK ON OFF SWITC...

Page 32: ...res to the junction box as shown Add a 1 4 inch insulated female connector to the red switch leg wire route it through the knockout in the face of the junction box and connect to the top fan switch co...

Page 33: ...y a 300o F minimum sealant Figure 11 2 Mantel Leg or Wall Projections Acceptable on both sides of opening Figure 11 1 Clearances to Mantels or other Combustibles above Appliance SEALANT MATERIAL 0 FIN...

Page 34: ...ee Ser vice Parts List for appropriate accessories Refer to Section 16 Removing Optional GFK 160A Fan ITEM 1 Remove front from the fireplace see Fig ure 12 1 2 Remove glass assembly from the fire plac...

Page 35: ...acing the Ember Material Ember material is shipped with this gas appliance To place the ember material Embers CANNOT be placed directly over ports Care should be taken not to cover the lighting trail...

Page 36: ...LOG 1 SRV385 720 Place the log so that the notches on the bottom of log line up with the grate bars Note There should be about 1 4 gap between the log and the hump on the burner STEP 3 LOG 2 SRV385 7...

Page 37: ...the slot in the underside of this log Place the log so that this slot fits onto the right metal tab on log 1 Swing the lower end so that it sits in or above the dent on the top of log 2 STEP 6 LOG 5...

Page 38: ...er up the gap between the sheet rock and the appliance Do not obstruct or modify the air inlet outlet grilles When overlapping on both sides leave enough space so that the bottom grille can be lowered...

Page 39: ...er removed Contact your dealer or Hearth Home Technologies if the barrier is not present or help is needed to properly install one Glass door must be in place when appliance is operating Risk of Combu...

Page 40: ...r maintenance can cause injury or property dam age Refer to the owner s informa tion manual provided with this ap pliance This appliance needs fresh air for safe operation and must be in stalled so th...

Page 41: ...nt or if appliance will not be used for an extended period of time Property damage possible from elevated temperatures CAUTION Fire Hazard Keep combustible materials gasoline and other flammable vapor...

Page 42: ...module with ON OFF switch in ON position Acceptable readings of a good transformer are between 3 2 and 2 8 volts AC b A shorted or loose connection in wiring configuration or wiring harness Remove and...

Page 43: ...ch or wall switch in ON position Hold ground wire about 3 16 inch away from I terminal on module If there is no spark at I terminal module must be replaced If there is a spark at I terminal module is...

Page 44: ...s Handle glass assembly with care NOTE Clean glass after initial 3 4 hours operation Longer operation without cleaning glass may cause a permanent white film on glass CAUTION When cleaning glass door...

Page 45: ...t as necessary 2 Replace appliance if firebox has been perforated Burner Ignition and Operation 1 Verify burner is properly secured and aligned with pilot or igniter 2 Clean off burner top inspect for...

Page 46: ...raming dimensions and clearances refer to Section 3 Figure 16 1 Appliance Dimensions A B C D E F G H I J K L M N O P Q Inches 28 1 2 14 1 4 21 1 2 12 7 8 8 38 6 7 8 2 1 8 21 1 2 32 1 4 36 1 8 41 1 8 7...

Page 47: ...DVP12A 3 to12 DVP12MI 3 to12 DVP24MI 3 to 24 10 1 2 in 10 7 8 in 45 7 3 8 in 11 3 8 in 1 1 4 in 9 1 4 in 13 1 4 in 1 2 in TYP DVP90 DVP90ST 90 Elbow 10 in 1 in 12 in 14 in 1 in 8 in 6 in 10 in 1 1 2 i...

Page 48: ...erm Cap Effective Length Effective Length TRAP1 4 1 8 in 5 5 8 in TRAP2 6 3 4 in 10 5 8 in Wall Shield Firestop Heat Shield DVP TRAP1 DVP TRAPK1 Horizontal Termination Cap Kit DVP90ST Wall Shield Fire...

Page 49: ...13 1 4 in 24 5 8 in 27 1 2 in RF6M Roof Flashing Multi pak 31 in 24 5 8 in 13 1 4 in RF12M Roof Flashing Multi pak BEK Trap Cap Brick Extension 13 3 4 in 5 in 13 3 4 in 7 1 4 in 5 1 4 in 12 1 2 in DV...

Page 50: ...pressly authorized and approved by HEAT GLO in writing 6 Anydamages caused by environmental conditions inadequate ventilation or drafting caused by tight sealing construction of th estructure air hand...

Page 51: ...ontact your Heat Glo dealer with any questions or concerns For the number of your nearest Heat Glo dealer please call 1 888 427 3973 Printed in U S A Copyright 2006 DO NOT DISCARD THIS MANUAL CAUTION...

Reviews: