Heat & Glo • 6000CF-OAK-IPI • 2092-900 Rev.
I
• 1/06
D. Installing the Flue Restrictor
Figure 7.6 Flue Restrictor
BREAK
HERE
Figure 7.5
1.
Break the Flue Restrictor (see Figure 7.5) into two piec-
es. Do this by bending the part back and forth until it
breaks (see Figure 7.6).
2.
Match the amount of vertical in the system with the chart
to find the appropriate position to set the Flue Restrictor
(see Figure 7.7).
1 2 3 4 5
SETTINGS
1 2 3 4 5
Figure 7.8
3
. Center the Flue Restrictor on vent and secure in place by
using two self-tapping screws (see Figure 7.8).
- CHART -
Vertical
Top Vent
NG
Top Vent
LP
4'
1-1
No
Restrictor
8'
2-2
1-2
15'
3-3
3-2
20'
3-4
3-3
25'
3-4
3-3
30'
4-4
3-4
35'
4-4
3-4
40'
5-4
4-4
45'
5-4
4-4
50'
5-4
4-4
Figure 7.7
FLUE
RESTRICTOR
E. Installing the Fiberglass Gasket
Figure 7.9 Fiberglass Gasket
The fiberglass gasket supplied in the manual bag seals
between the first 8 inch (203mm) vent component and
the outer fireplace wrap. Using 2 self-tapping screws from
the manual bag secure the gasket to the outer wrap (see
Figure 7.9).
FIRST VENT
COMPONENT
FIBERGLASS
GASKET
OUTERWRAP