G. WHEN REMOVING A WATER HEATER FROM AN EXISTING COMMON VENT SYSTEM
At the time of removal of an existing gas water heater, the following steps shall be followed with
each appliance remaining connected to the common venting system placed in operation, while the
other appliances remaining connected to the common venting system are not in operation.
a. Seal any unused openings in the common venting system.
b. Visually inspect the venting system for proper size and horizontal pitch and determine there is no
blockage or restriction, leakage, corrosion and other deficiencies which could cause an unsafe
condition.
c. Insofar as is practical, close all building doors and windows and all doors between the space in
which the appliances remaining connected to the common venting system are located and other
spaces of the building. Turn on clothes dryers and any appliance not connected to the common
venting system. Turn on any exhaust fans, such as range hoods and bathroom exhausts, so they
will operate at maximum speed. Do not operate a summer exhaust fan. Close fireplace dampers.
d. Place in operation the appliance being inspected. Follow the lighting instructions. Adjust
thermostat so appliance will operate continuously.
e. Test for spillage after 5 minutes of main burner operation. Use the flame of a match or candle, or
smoke from a cigarette, cigar, or pipe.
f.
After it has been determined that each appliance remaining connected to the common venting
system properly vents when tested as outlined herein, return doors, windows, exhaust fans,
fireplace dampers, and any other gas-burning appliance to their previous conditions of use.
g. Any improper operation of common venting system should be corrected so the installation
conforms with the National Fuel Gas Code, ANSI Z223.1 — latest edition. Correct by resizing to
approach the minimum size as determined using the appropriate tables in Table 13 of NFPA54
ANSI Z223.1 2006 of that code. Canadian installations must comply with B149.1 or B149.2
Installation Code.
H. WATER CHEMISTRY
PART 3: PREPARE WATER HEATER LOCATION
(CONTINUED)
n
DANGER
Do not install the Phoenix into a common vent with any other appliance. This will cause
flue gas spillage or appliance malfunction, resulting in possible severe personal injury,
death or substantial property damage.
n
WARNING
Failure to follow all instructions can result in flue gas spillage and carbon monoxide
emissions, causing severe personal injury or death.
n
CAUTION
Chemical imbalance of your water can cause severe damage to your water heater and
associated equipment and may also affect the efficiency. You may have to have your
water quality professionally analyzed to determine whether you need to install a water
softener. Failure of a heat exchanger due to lime scale build-up on the heating surface,
low pH or other chemical imbalance is non-warrantable.