setBack scHedule

Hold Button: 

MENU/<System Settings>/<Stage Settings>/<Setback Schedule>

This menu provide the Day/Night Schedule as well as the Setback and Boost settings.

seQ and MoV setBack

Adjustable 0

°

F/0

°

C to 80°F/44°C 

Default: 0

°

F/0

°

C

------ SETBACK -------

     0 F

[            ]

BACK        SAVE

Hold Button: 

MENU/<SEQ Settings>/.../<Setback Schedule>/Setback

 

Ext Output 1 = Shutdown or SEQ Tstat

Hold Button: 

MENU/<SEQ Settings>/<SEQ System Settings>/Setback

 

External Output 1 = Setback

•   The Setback feature can be used to provide the SQ-Elite-MV with a lower temperature Set Point when less load is required.

•   The new Set Point will appear on the main display indicating this condition "

Setback to 160 F

".  For example, if the 

calculated temperature is 180°F and the Setback is 20°F, then when in Setback, the SQ-Elite-MV will hold a Set Point of 160°F.

•   A typical use for Setback is to provide less system temperature to a building during the night or on the weekends when building is 

not occupied, but heat is still required.

•   If External Output 1 was set to Shutdown or SEQ Tstat, the Setback will be activated using the Day/Night Schedule.  Otherwise, if 

Setback was selected, the Setback can only be activated using  a dry-contact input on terminals 

35 and 36

.  See page 

19

.

•   After selecting a value in Setback, you'll be directed to the Boost menu.

seQ and MoV Boost

Adjustable 0°F/0°C to 80°F/44°C 

Default: 0

°

F/0

°

C

Hold Button: 

MENU/<SEQ Settings>/.../<Setback Schedule>/Setback/Boost

 

SEQ

Hold Button: 

MENU/<MOV Settings>/.../<Setback Schedule>/Setback/Boost

 

MOV

•   This features brings the building to warm-up quickly after a Setback period.

-------- BOOST ---------

     0 F

[            ]

BACK        SAVE

•   The Boost temperature will be the number of degrees to be added to the Target.

•   The new Set Point will appear on the main display indicating this condition "

Boost to 190 F

".

•   Using the previous example, if the Target was 180°F and the Boost was 10°F for 30 minutes, after the scheduled setback period, the 

Boost will change the target to 190°F for a period of 30 minutes.

•   If External Setback was used, the Boost will take place after the Setback is deactivated.

•   If 0

˚

F Was selected, no boost will take place.

seQ and MoV Boost perIod

Adjustable 0 to 120 minutes 

Default: 0 minutes

Hold Button: 

MENU/<SEQ Settings>/.../Setback/Boost/Boost Period

 

SEQ

Hold Button: 

MENU/<MOV Settings>/.../Setback/Boost/Boost Period

 

MOV

•   This will determine the length of Boost the System will receive.

--- BOOST PERIOD ---

     30min

[

        ]

BACK        SAVE

•   For convenience, the Boost will start a full Boost Period prior to the switch from Night Schedule to Day Schedule operation.  It 

will then terminate at the start of the Day Schedule.  If the Day was set to start at 7:00Am and the Boost Period was set to 30 

minutes, the Boost will start at 6:30Am and terminate at 7:00Am.

seQ and MoV day/nIgHt scHedules

(available when external Input 1 = shutdown or seQ tstat only)

Hold Button: 

MENU/<SEQ Settings>/<SEQ System>/<Setback Schedule>/Day Schedule

Hold Button: 

MENU/<MOV Settings>/<SEQ System>/<Setback Schedule>/Day Schedule

•   Each of the SEQ and MOV Schedules provide two levels of heat.  The Day level is used 

when a building is occupied and people are active.  The Night/Setback level is used when a 

building is not occupied or when people are asleep.

-- DAY SCHEDULE ---

     07:**Am

BACK        SAVE

- NIGHT SCHEDULE --

     10:**Pm

BACK        SAVE

•   The Night setting reduces the calculated temperature by the Setback setting.  If the Day calculated water temperature was 150˚F 

and the Setback was 20˚F, the Night Schedule will run at (150˚F - 20˚F) = 130˚F.

•   If the Boost feature is being used, it uses the Day Schedule as a Boost ending point.  That is, if the Day Schedule is set to start at 

6:00AM,the Boost was set to 10ºF, and  the Boost Period was 30 minutes, the Boost will start at 5:30AM.  The SQ-Elite-MV will 

then raise the calculated water temperature by the Boost amount.  Using the previous example, at 5:30AM the SQ-Elite-MV will 

raise the calculated water to 170˚F (150˚F + 20˚F) until 6:00AM.

set present tIMe

Hold Button: 

MENU/<SEQ Settings>/<SEQ System>/<Setback Schedule>/Present Time

Hold Button: 

MENU/<Maintenance>/Present Time

•   The Time is used by Day/Night Schedule and History graph and is backed up by the battery.

•   Adjust the time by selecting Time from the menu and then scrolling through the hours

- SET PRESENT TIME

     **:**

BACK        SAVE

Summary of Contents for SQ-Elite-EXt

Page 1: ...CONTROL MOV CLOSE INPUT RATINGS 120VAC 60Hz 12VA MAX Use Copper Conductors Only CAUTION Risk of Electric Shock PWR L N 1 2 SENSORS MUST BE GOLD SERIES MOV SYS 3 MOV CLOSE 5 Stage A 7 Stage B 9 Stage C...

Page 2: ...g settings 22 Program Change Settings 22 Season 22 seQ and MoV reset ratio settings 22 SEQ and MOV Reset Ratio 22 SEQ and MOV Customized Reset Ratio 22 SEQ and MOV Target Offset 23 SEQ and MOV Outdoor...

Page 3: ...2A 120VAC MAXIMUM 15A TOTAL FOR ALL CIRCUITS 23 24 MOV OPEN DO NOT APPLY ANY VOLTAGE TO INPUT TERMINALS MOV OPEN MOV SYS SEQ Temp ENCLOSED ENERGY MANAGEMENT EQUIPMENT LISTED 99RA C US Press any button...

Page 4: ...s to quickly make changes to any system setting without having to learn any specialized codes or keyboard commands Two separate menus has been provided One for the installer having all the functions W...

Page 5: ...this means the temperature has fallen 20 from the starting point of 70 F Therefore the heating water temperature will increase 20 to 120 F Each building has different heat loss characteristics A very...

Page 6: ...eset or by maintaining an adjustable Set Point The Outdoor Reset option uses an Outdoor Sensor supplied with the control and achieves better fuel savings in addition to better comfort Using an optiona...

Page 7: ...inals This switch is enclosed with the enclosure wiring cover for security Wiring terminals are of the plug in type to ease installation and removal The Enclosure Base contains the holes to mount and...

Page 8: ...or Shield alert If any of the System Sensors cannot sense the correct system water temperature the SQ Elite MV will not provide comfortable heat levels outdoor sensor InstallatIon Only use the Heat Ti...

Page 9: ...temperature Whether in Set Point or Outdoor Reset modes the outdoor sensor can be used as an Outdoor Cutoff The SQ Elite MV will disable all Boilers and close the motorized valve when the outdoor tem...

Page 10: ...V will sequence the stages to achieve the desired SEQ Set Point However when the terminals are opened all stages will de energize The Tstat signal must be a dry contact only No voltage can be placed a...

Page 11: ...DHW during Summer or when SEQ Tstat input is opened DHW PUMP 13 Stage E 15 Stage F 17 12 14 16 18 19 SEQ SYS SEQ System Pump L N wIrIng tHe MoV systeM output terMInals 19 20 Connect the MOV pump Motor...

Page 12: ...igher stage of the same boiler must be connected to Stage B The boiler valve or pump must be connected to Stage C PWR L N 1 2 3 5 Stage A 7 Stage B 9 Stage C 11 13 Stage E 15 Stage F Stage D 6 8 10 12...

Page 13: ...Two Extension Panels and 4 20mA EMS Interface using RS485 SQ Elite MV SQ Elite MV SEQUENCING CONTROL INPUT RATINGS 115VAC 60Hz 12VA MAX Use Copper Conductors Only CAUTION Risk of Electric Shock Stage...

Page 14: ...Stages On Stages Off BACK SAVE ARE YOU SURE No Yes BACK SAVE eMs set poInt MAINTENANCE Unit F Present Time12 30P Valve Sensor Trim Histories Configuration BACK SELECT SENSOR TRIM SEQ Trim 0 F Outdoor...

Page 15: ...00 SYS 12 1 00 OD 4 00 SYS BACK SAVE SEQ OUTDOOR RESET Reset Ratio 7 Target Offset 0 F Outdoor Cutoff 70 F Min Target 80 F Max Target 240 F BACK SELECT TARGET OFFSET 0 F BACK SAVE MIN TARGET 80 F BACK...

Page 16: ...ings Setback Schedule DHW Prior Timer No Run On 2m Pump Exercise Off BACK SELECT STAGE SETTINGS Reaction Time 1min Purge Delay 0 0min Min Runtime 2min Standby Delay10min Last Stge Hold 5 F Throttle 2...

Page 17: ...1 50 OD 1 00 SYS 6 1 25 OD 1 00 SYS 7 1 00 OD 1 00 SYS 8 1 00 OD 1 25 SYS 9 1 00 OD 1 50 SYS 10 1 00 OD 2 00 SYS 11 1 00 OD 3 00 SYS 12 1 00 OD 4 00 SYS BACK SAVE MOV OUTDOOR RESET Reset Ratio 7 Targe...

Page 18: ...y of displaying temperature information and settings in either F Fahrenheit or C Celsius Select the display unit that is best suited for your application DISPLAY UNIT F C BACK SAVE settIng tHe 4Ma and...

Page 19: ...ized If SEQ Prove is selected make sure to connect those terminals to either a flow switch that checks the SEQ System pump operation or a combustion air damper end switch Otherwise install a jumper on...

Page 20: ...he following are the settings that directly affects this modes operation Reaction Time Hold Button MENU SEQ Settings System Settings Stage Settings Reaction Time Purge Delay Hold Button MENU SEQ Setti...

Page 21: ...et to the MOV Maximum Target set poInt Mode If Valve Close is selected the SQ Elite MV will energize the MOV Close relay when the SEQ System sensor reads Short or Open If Valve Open is selected the SQ...

Page 22: ...g Outdoor Rst Reset Ratio SEQ Hold Button MENU MOV Setting Outdoor Rst Reset Ratio MOV The Reset Ratio determines how the System water temperature will vary with outside temperature changes With any o...

Page 23: ...ding Operation Concept on page 5 The Minimum and Maximum Target will take precedence over the Offset That is if the Max Target was set to 180 F and the Offset was set to 20 F If the set point was 170...

Page 24: ...EQ System temperature around the SEQ Set point If the EMS Mode was Enabled the Set Point will be set by the EMS BMS system and will be available as a read only The range of Set Point in the EMS is set...

Page 25: ...URGE DELAY 0 0min BACK SAVE The Purge Delay helps prevent short cycling of a newly activated boilers Once the lowest boiler stage is activated it MUST run through the entire Purge Delay period The min...

Page 26: ...ng range as a differential The last stage to be turned off will be allowed to exceed the Set Point by a full Throttle before it is turned off This helps prevent the last stage from short cycling when...

Page 27: ...he automatic rotation is recommended for most applications The current Lead Boiler is shown in brackets on the main display Only boilers which are set to Auto Mode can be Lead Therefore not all the bo...

Page 28: ...ost will take place after the Setback is deactivated If 0 F Was selected no boost will take place seQ and MoV Boost perIod Adjustable 0 to 120 minutes Default 0 minutes Hold Button MENU SEQ Settings S...

Page 29: ...30min BACK SAVE Priority period If NO was selected both DHW Pump and System relay will be energized on a DHW call whenever there is a DHW call during Winter In Summer or SEQ Outdoor Cutoff a DHW call...

Page 30: ...that time and read the upper left temperature SEQ 120 F 10 00AM BACK NEXT The first screen will be the SEQ System Temperature History By clicking on the Next button you ll be able to view the Outdoor...

Page 31: ...the SEQ Set Point to the indicated temperature DHW increases calculated temperature to the lower of 200 F or Max Water Holding Return at 110 F The Return sensor is reading less than the Minimum Retur...

Page 32: ...o active boilers Any output without an active boiler must be set to Off The following list describes the MODE options BOILER AB MODE Auto Standby Off On BACK SAVE Auto The SQ Elite MV will control the...

Page 33: ...st and Boost Period values Reduce the Boost amount or Boost Period setting See Boost on page 28 Boiler Mode Settings The SQ Elite MV will only sequence boilers their mode is set to Auto or Standby Che...

Page 34: ...set See MOV Offset on page 23 Setback and Day Night Schedule If reduced heat occurs during Night hours reduce the MOV Setback setting See MOV Setback on page 28 If the building takes a long time to re...

Page 35: ...r continuity across terminals 23 and 24 Otherwise the SQ Elite MV may be damaged Boilers are short cycling Minimum Runtime Increase the Minimum Runtime only if all boilers tend to short cycle Last Sta...

Page 36: ...Temp Outdoor Temp MOV CLOSE SEQ SYS DHW PUMP MOV OPEN SEQ SYS SENSORS MUST BE GOLD SERIES DO NOT APPLY ANY VOLTAGE TO INPUT TERMINALS Use Copper Conductors Only CAUTION Risk of Electric Shock PROGRAM...

Page 37: ...37 38 SEQ PROVE MOV TSTAT 23 24 MOV OPEN SEQ Temp Outdoor Temp MOV CLOSE SEQ SYS DHW PUMP MOV OPEN SEQ SYS SENSORS MUST BE GOLD SERIES DO NOT APPLY ANY VOLTAGE TO INPUT TERMINALS Use Copper Conductors...

Page 38: ...ROVE MOV TSTAT 23 24 MOV OPEN SEQ Temp Outdoor Temp MOV CLOSE SEQ SYS DHW PUMP MOV OPEN SEQ SYS SENSORS MUST BE GOLD SERIES DO NOT APPLY ANY VOLTAGE TO INPUT TERMINALS Use Copper Conductors Only CAUTI...

Page 39: ...age C 11 13 Stage E 15 Stage F 17 Stage D 6 8 10 12 14 16 18 RS485 4 SEQ SYS 19 DHW PUMP 21 27 29 31 MOV Temp 33 SHUTDOWN TSTAT SETBACK 35 Return Temp 20 22 28 30 32 34 36 25 26 DHW 37 38 SEQ PROVE MO...

Page 40: ...00 SYS 3 3 00 OD 1 00 SYS 4 2 00 OD 1 00 SYS 5 1 50 OD 1 00 SYS 6 1 25 OD 1 00 SYS 7 1 00 OD 1 00 SYS 8 1 00 OD 1 25 SYS 9 1 00 OD 1 50 SYS 10 1 00 OD 2 00 SYS 11 1 00 OD 3 00 SYS 12 1 00 OD 4 00 SYS...

Page 41: ...eeded as well as preserve the battery life seQ and MoV reset ratIo settIngs Each of the boiler loop SEQ and motorized valve loop MOV has their own reset ratio settings that can be configured independe...

Page 42: ...Point temperature was 130 F and the Offset was changed from 0 to 10 an increase of 10 then the Set Point temperature would increase to 140 F TARGET OFFSET 0 F BACK SAVE The Offset setting does not ch...

Page 43: ...ar on the main display indicating this condition Setback to 160 F For example if the calculated temperature is 180 F and the Setback is 20 F then when in Setback the SQ Elite MV will hold a Set Point...

Page 44: ...4 20mA EMS Interface optional Reset Ratio Range Outdoor Reset Only 1 4 to 8 1 Outdoor System Water and Custom Reset Ratio Offset Adjustment Outdoor Reset Only minus 40 F 22 C to plus 40 F 22 C Minimum...

Reviews: