SQ-Elite-MV & SQ-Elite-EXT Installation Manual 

 19

dHw puMp output

No, Yes  

Default: Yes

Hold Button: 

MENU/<System Startup>/..../DHW Pump Output

•   The SQ-Elite-MV can operate the DHW Pump.  This option allows the user to select if the 

SQ-Elite-MV should be controlling the DHW Pump or not.

--DHW PUMP OUTPUT--

 

No

 Yes

BACK        SAVE

eXternal Input 1 Mode

Shutdown, SEQ Tstat, SEQ Setback  

Default: Shutdown

Hold Button: 

MENU/<System Startup>/..../External Input1

•   The Shutdown function allows the SQ-Elite-MV to receive a remote dry-contact signal to 

terminals 

35 and 36

 to turn off all relays including boilers stages.

•   When Shutdown is selected, any DHW call will be ignored when the control is in Shutdown.

- EXTERNAL INPUT 1

 

Shutdown

 SEQ Tstat

 SEQ Setback

BACK        SAVE

•   The SEQ Tstat option gives terminals 

35 and 36

 the capability of functioning as a heat-call.  That is, when the terminals are 

shorted, the control will sequence the stages to maintain the set point.  However, when terminals are opened, all stages will turn off.  

Unlike the Shutdown, when SEQ Tstat is selected, a DHW call will energize the stages even if the SEQ Tstat is not active.

•   SEQ Setback is used to lower the SEQ Set Point when less load is required during nights and weekends.  No Schedule options will 

be available for the SEQ when this option is selected.  In this case, the Setback can only be activated using a remote input.

•   For SEQ Setback operation, the SQ-Elite-MV can either utilize its built-in day schedule by selecting Shutdown or Tstat options, or 

an external dry-contact signal to input terminals 

35 and 36

 to switch to setback by selecting Setback from this menu.

eXternal Input 2 Mode

SEQ Prove, MOV Tstat  

Default: SEQ Prove

Hold Button: 

MENU/<System Startup>/..../External Input2

•   The SEQ Prove option assigns terminals 

37 and 38

 the Prove function for the SEQ stages.  

Thus, not allowing any stage to operate when those terminals are opened. However, the SEQ 

System Pump can be energized.

•   If SEQ Prove is selected, make sure to connect those terminals to either a flow switch that 

checks the SEQ System pump operation or a combustion air damper end switch.  Otherwise, 

install a jumper on terminals 

37 ad 38

  to allow for stage operation.

- EXTERNAL INPUT2 -

 

SEQ Prove

 MOV Tstat

BACK        SAVE

•   If MOV Tstat was the option selected, the SQ-Elite-MV will activate the motorized valve heating only when terminals 

37 and 38

 

are shorted with a dry-contact input.  When the terminals are opened, the motorized valve Close relay will energize for six minutes 

allowing it to fully close.

Burner type

On/Off, 2-Stage, 3-Stage, 4-Stage  

Default: On/Off

Hold Button: 

MENU/<System Startup>/..../Burner Type

•   The SQ-Elite-MV can sequence from a single stage and up to four stages per boiler.

--- BURNER TYPE ----

 

On/Off

 2-Stage

 3-Stage

 4-Stage

BACK        SAVE

BoIler output

None, Pump, Valve  

Default: None

Hold Button: 

MENU/<System Startup>/..../Boiler Output

•   When None is selected, the SQ-Elite-MV will sequence multiple boilers without any 

additional boiler pumps or valves.

•   The Pump option allows the SQ-Elite-MV to control the boiler stages in addition to their 

pumps.  The stage pump relay will run for the Run-On delay after the lower stage of that 

boiler has de-energized.

-- BOILER OUTPUT --

 

None

 Pump

 Valve

BACK        SAVE

•   The Valve option functions similar to the pump option except that when all SQ-Elite-MV stages are off and after Run-On delay has 

elapsed, the Lead boiler's valve relay will remain energized to allow for flow across the system.  The lead boiler's valve will remain 

energized until the Outdoor temperature rises above the SEQ Outdoor Cutoff or the Shutdown or Summer is activated.

total BoIlers

1 to 22 

Default: varies based on Burner Type and Boiler Output

Hold Button: 

MENU/<System Startup>/..../Boiler Output

•   This option in Combination with Burner Type and Boiler Output option will determine the 

total number of stages the SQ-Elite-MV will need to control.

•   If more stages are selected than the SQ-Elite-MV and SQ-Elite-EXT Extension has, the 

additional boilers containing these stages will have 

CE

 displayed as their status.

-- TOTAL BOILERS --

      6

[

          ]

BACK        SAVE

Summary of Contents for SQ-Elite-EXt

Page 1: ...CONTROL MOV CLOSE INPUT RATINGS 120VAC 60Hz 12VA MAX Use Copper Conductors Only CAUTION Risk of Electric Shock PWR L N 1 2 SENSORS MUST BE GOLD SERIES MOV SYS 3 MOV CLOSE 5 Stage A 7 Stage B 9 Stage C...

Page 2: ...g settings 22 Program Change Settings 22 Season 22 seQ and MoV reset ratio settings 22 SEQ and MOV Reset Ratio 22 SEQ and MOV Customized Reset Ratio 22 SEQ and MOV Target Offset 23 SEQ and MOV Outdoor...

Page 3: ...2A 120VAC MAXIMUM 15A TOTAL FOR ALL CIRCUITS 23 24 MOV OPEN DO NOT APPLY ANY VOLTAGE TO INPUT TERMINALS MOV OPEN MOV SYS SEQ Temp ENCLOSED ENERGY MANAGEMENT EQUIPMENT LISTED 99RA C US Press any button...

Page 4: ...s to quickly make changes to any system setting without having to learn any specialized codes or keyboard commands Two separate menus has been provided One for the installer having all the functions W...

Page 5: ...this means the temperature has fallen 20 from the starting point of 70 F Therefore the heating water temperature will increase 20 to 120 F Each building has different heat loss characteristics A very...

Page 6: ...eset or by maintaining an adjustable Set Point The Outdoor Reset option uses an Outdoor Sensor supplied with the control and achieves better fuel savings in addition to better comfort Using an optiona...

Page 7: ...inals This switch is enclosed with the enclosure wiring cover for security Wiring terminals are of the plug in type to ease installation and removal The Enclosure Base contains the holes to mount and...

Page 8: ...or Shield alert If any of the System Sensors cannot sense the correct system water temperature the SQ Elite MV will not provide comfortable heat levels outdoor sensor InstallatIon Only use the Heat Ti...

Page 9: ...temperature Whether in Set Point or Outdoor Reset modes the outdoor sensor can be used as an Outdoor Cutoff The SQ Elite MV will disable all Boilers and close the motorized valve when the outdoor tem...

Page 10: ...V will sequence the stages to achieve the desired SEQ Set Point However when the terminals are opened all stages will de energize The Tstat signal must be a dry contact only No voltage can be placed a...

Page 11: ...DHW during Summer or when SEQ Tstat input is opened DHW PUMP 13 Stage E 15 Stage F 17 12 14 16 18 19 SEQ SYS SEQ System Pump L N wIrIng tHe MoV systeM output terMInals 19 20 Connect the MOV pump Motor...

Page 12: ...igher stage of the same boiler must be connected to Stage B The boiler valve or pump must be connected to Stage C PWR L N 1 2 3 5 Stage A 7 Stage B 9 Stage C 11 13 Stage E 15 Stage F Stage D 6 8 10 12...

Page 13: ...Two Extension Panels and 4 20mA EMS Interface using RS485 SQ Elite MV SQ Elite MV SEQUENCING CONTROL INPUT RATINGS 115VAC 60Hz 12VA MAX Use Copper Conductors Only CAUTION Risk of Electric Shock Stage...

Page 14: ...Stages On Stages Off BACK SAVE ARE YOU SURE No Yes BACK SAVE eMs set poInt MAINTENANCE Unit F Present Time12 30P Valve Sensor Trim Histories Configuration BACK SELECT SENSOR TRIM SEQ Trim 0 F Outdoor...

Page 15: ...00 SYS 12 1 00 OD 4 00 SYS BACK SAVE SEQ OUTDOOR RESET Reset Ratio 7 Target Offset 0 F Outdoor Cutoff 70 F Min Target 80 F Max Target 240 F BACK SELECT TARGET OFFSET 0 F BACK SAVE MIN TARGET 80 F BACK...

Page 16: ...ings Setback Schedule DHW Prior Timer No Run On 2m Pump Exercise Off BACK SELECT STAGE SETTINGS Reaction Time 1min Purge Delay 0 0min Min Runtime 2min Standby Delay10min Last Stge Hold 5 F Throttle 2...

Page 17: ...1 50 OD 1 00 SYS 6 1 25 OD 1 00 SYS 7 1 00 OD 1 00 SYS 8 1 00 OD 1 25 SYS 9 1 00 OD 1 50 SYS 10 1 00 OD 2 00 SYS 11 1 00 OD 3 00 SYS 12 1 00 OD 4 00 SYS BACK SAVE MOV OUTDOOR RESET Reset Ratio 7 Targe...

Page 18: ...y of displaying temperature information and settings in either F Fahrenheit or C Celsius Select the display unit that is best suited for your application DISPLAY UNIT F C BACK SAVE settIng tHe 4Ma and...

Page 19: ...ized If SEQ Prove is selected make sure to connect those terminals to either a flow switch that checks the SEQ System pump operation or a combustion air damper end switch Otherwise install a jumper on...

Page 20: ...he following are the settings that directly affects this modes operation Reaction Time Hold Button MENU SEQ Settings System Settings Stage Settings Reaction Time Purge Delay Hold Button MENU SEQ Setti...

Page 21: ...et to the MOV Maximum Target set poInt Mode If Valve Close is selected the SQ Elite MV will energize the MOV Close relay when the SEQ System sensor reads Short or Open If Valve Open is selected the SQ...

Page 22: ...g Outdoor Rst Reset Ratio SEQ Hold Button MENU MOV Setting Outdoor Rst Reset Ratio MOV The Reset Ratio determines how the System water temperature will vary with outside temperature changes With any o...

Page 23: ...ding Operation Concept on page 5 The Minimum and Maximum Target will take precedence over the Offset That is if the Max Target was set to 180 F and the Offset was set to 20 F If the set point was 170...

Page 24: ...EQ System temperature around the SEQ Set point If the EMS Mode was Enabled the Set Point will be set by the EMS BMS system and will be available as a read only The range of Set Point in the EMS is set...

Page 25: ...URGE DELAY 0 0min BACK SAVE The Purge Delay helps prevent short cycling of a newly activated boilers Once the lowest boiler stage is activated it MUST run through the entire Purge Delay period The min...

Page 26: ...ng range as a differential The last stage to be turned off will be allowed to exceed the Set Point by a full Throttle before it is turned off This helps prevent the last stage from short cycling when...

Page 27: ...he automatic rotation is recommended for most applications The current Lead Boiler is shown in brackets on the main display Only boilers which are set to Auto Mode can be Lead Therefore not all the bo...

Page 28: ...ost will take place after the Setback is deactivated If 0 F Was selected no boost will take place seQ and MoV Boost perIod Adjustable 0 to 120 minutes Default 0 minutes Hold Button MENU SEQ Settings S...

Page 29: ...30min BACK SAVE Priority period If NO was selected both DHW Pump and System relay will be energized on a DHW call whenever there is a DHW call during Winter In Summer or SEQ Outdoor Cutoff a DHW call...

Page 30: ...that time and read the upper left temperature SEQ 120 F 10 00AM BACK NEXT The first screen will be the SEQ System Temperature History By clicking on the Next button you ll be able to view the Outdoor...

Page 31: ...the SEQ Set Point to the indicated temperature DHW increases calculated temperature to the lower of 200 F or Max Water Holding Return at 110 F The Return sensor is reading less than the Minimum Retur...

Page 32: ...o active boilers Any output without an active boiler must be set to Off The following list describes the MODE options BOILER AB MODE Auto Standby Off On BACK SAVE Auto The SQ Elite MV will control the...

Page 33: ...st and Boost Period values Reduce the Boost amount or Boost Period setting See Boost on page 28 Boiler Mode Settings The SQ Elite MV will only sequence boilers their mode is set to Auto or Standby Che...

Page 34: ...set See MOV Offset on page 23 Setback and Day Night Schedule If reduced heat occurs during Night hours reduce the MOV Setback setting See MOV Setback on page 28 If the building takes a long time to re...

Page 35: ...r continuity across terminals 23 and 24 Otherwise the SQ Elite MV may be damaged Boilers are short cycling Minimum Runtime Increase the Minimum Runtime only if all boilers tend to short cycle Last Sta...

Page 36: ...Temp Outdoor Temp MOV CLOSE SEQ SYS DHW PUMP MOV OPEN SEQ SYS SENSORS MUST BE GOLD SERIES DO NOT APPLY ANY VOLTAGE TO INPUT TERMINALS Use Copper Conductors Only CAUTION Risk of Electric Shock PROGRAM...

Page 37: ...37 38 SEQ PROVE MOV TSTAT 23 24 MOV OPEN SEQ Temp Outdoor Temp MOV CLOSE SEQ SYS DHW PUMP MOV OPEN SEQ SYS SENSORS MUST BE GOLD SERIES DO NOT APPLY ANY VOLTAGE TO INPUT TERMINALS Use Copper Conductors...

Page 38: ...ROVE MOV TSTAT 23 24 MOV OPEN SEQ Temp Outdoor Temp MOV CLOSE SEQ SYS DHW PUMP MOV OPEN SEQ SYS SENSORS MUST BE GOLD SERIES DO NOT APPLY ANY VOLTAGE TO INPUT TERMINALS Use Copper Conductors Only CAUTI...

Page 39: ...age C 11 13 Stage E 15 Stage F 17 Stage D 6 8 10 12 14 16 18 RS485 4 SEQ SYS 19 DHW PUMP 21 27 29 31 MOV Temp 33 SHUTDOWN TSTAT SETBACK 35 Return Temp 20 22 28 30 32 34 36 25 26 DHW 37 38 SEQ PROVE MO...

Page 40: ...00 SYS 3 3 00 OD 1 00 SYS 4 2 00 OD 1 00 SYS 5 1 50 OD 1 00 SYS 6 1 25 OD 1 00 SYS 7 1 00 OD 1 00 SYS 8 1 00 OD 1 25 SYS 9 1 00 OD 1 50 SYS 10 1 00 OD 2 00 SYS 11 1 00 OD 3 00 SYS 12 1 00 OD 4 00 SYS...

Page 41: ...eeded as well as preserve the battery life seQ and MoV reset ratIo settIngs Each of the boiler loop SEQ and motorized valve loop MOV has their own reset ratio settings that can be configured independe...

Page 42: ...Point temperature was 130 F and the Offset was changed from 0 to 10 an increase of 10 then the Set Point temperature would increase to 140 F TARGET OFFSET 0 F BACK SAVE The Offset setting does not ch...

Page 43: ...ar on the main display indicating this condition Setback to 160 F For example if the calculated temperature is 180 F and the Setback is 20 F then when in Setback the SQ Elite MV will hold a Set Point...

Page 44: ...4 20mA EMS Interface optional Reset Ratio Range Outdoor Reset Only 1 4 to 8 1 Outdoor System Water and Custom Reset Ratio Offset Adjustment Outdoor Reset Only minus 40 F 22 C to plus 40 F 22 C Minimum...

Reviews: