ETS-LT CONTROL MODULE WIRING
ETS-LT CONTROL MODULE COMMUNICATIONS WIRING (OPTIONAL)
The ETS-LT Control Module can be connected to a network using either an internet (RINET), BACnet (IP or MSTP),
or ModBUS connection.
INTERNET (RINET) COMMUNICATIONS WIRING (OPTIONAL)
To connect the ETS-LT Control Module to the internet:
1
Run a CAT5 cable from the modem or router through a knockout located on the bottom
of the ETS-LT Control Module enclosure.
2
Connect the CAT5 cable to the Ethernet connector on the ETS-LT Control Module.
BACNET COMMUNICATIONS WIRING (OPTIONAL)
To connect the ETS-LT Control Module to a BACnet interface:
1
Run a CAT5 cable through a knockout located on the bottom of the ETS-LT Control
Module enclosure.
2
Connect the CAT5 cable to the Ethernet connector on the ETS-LT Control Module.
3
Run the BACnet connection wires through a knockout located on the bottom of the
ETS-LT Control Module enclosure.
4
Connect the positive (+) wire to terminal 30 on the ETS-LT Control Module.
5
Connect the ground wire to terminal 31 on the ETS-LT Control Module.
6
Connect the negative (–) wire to terminal 32 on the ETS-LT Control Module.
MODBUS COMMUNICATIONS WIRING (OPTIONAL)
To connect the ETS-LT Control Module to a ModBUS interface:
1
Run the ModBUS connection wires through a knockout located on the bottom of the
ETS-LT Control Module enclosure.
2
Connect the positive (+) wire to terminal 30 on the ETS-LT Control Module.
3
Connect the ground wire to terminal 31 on the ETS-LT Control Module.
4
Connect the negative (–) wire to terminal 32 on the ETS-LT Control Module.
COMPLETING THE ETS OPTIONAL FIELD WIRING
1
After all wiring to the ETS-LT Control Module is complete, replace the Enclosure wiring
cover and secure it in place with two screws.
2
Optionally secure the enclosure using a padlock with a maximum shank diameter of
⅛
”.
BMS—BACNET
Modem or Router
BMS—ModBUS
+
+
G
G
–
–
CAT5
CAT5
Summary of Contents for ETS-100
Page 1: ...INSTALLATION AND OPERATION MANUAL 059327 00 REV C ETS LT ELECTRONIC TEMPERING STATION...
Page 7: ...HEAT TIMER CORP 7 03 SPECIFICATIONS FIGURE 3 ETS LT DIMENSIONS...
Page 43: ...HEAT TIMER CORP 43 ETS LT 07 PIPING DIAGRAMS...
Page 46: ...46 HEAT TIMER CORP 059327 00 REV C 09 NOTES...
Page 48: ...20 NEW DUTCH LANE FAIRFIELD NJ 07004 PHONE 973 575 4004 FAX 973 575 4052 HEAT TIMER COM...