SEQ-3 Digi-Elite Operation Manual

Domestic Hot Water (DHW) Priority

Options: 

 NO and From 1 min to 120 min  

Default: NO

SET

SET

/Settings>/DHW Prior.

DHW Priority:
60m

•   The DHW Priority, with a value set to other than NO, provides the user with an adjustable DHW priority timer for the domestic 

hot water call.  That is, initiating a DHW call will de-energize the system pump relay for the period set by the DHW Priority.  
However, the DHW relay, when 1-On/Off+2-Pump is selected as the Output mode from the Startup menu, will remain energized 
for as long as the DHW is active.  This will take place whenever the Outdoor temperature is below Outdoor Cutoff and the EXT+/
EXT- (Enable/Disable terminals) are closed/shorted.

•   On the other hand, when the EXT+/EXT- (Enable/Disable terminals) are open or the Outdoor temperature is 2°F above the  

Outdoor Cutoff, a DHW priority call will energize the DHW pump and boiler relays.  When the DHW call expires, the DHW 
Pump relay will remain energized for the Run-On delay then de-energize.

•   If NO was selected as the option for the DHW Priority, a DHW call will energize both relays, system pump and DHW pump even 

when TSTAT is de-activated.

Setback

Options: 

 From 0

º

F/0

ºC

 to 80

º

F/44

ºC

  

Default: 10

º

F/6

ºC

SET

SET

/Settings>/Setback.

•   The Setback feature can be used to provide the SEQ-3 with a lower temperature Set Point when 

less heat is required by closing the P+ and P- terminals.

•   The lower Set Point will appear on the main display indicating  

SBC TGT=

 .

Setback:

20 F

SYSTEM= 

68 F

SBC TGT= 

140 F

•   For example; when the calculated temperature is 160°F and the Setback is set to 20°F, a setback 

call will change the Set Point to (160°F - 20°F) 140°F.

•   A typical use for the Setback is to provide a reduced system temperature to a building during the 

night or on the weekends when building is not occupied, but heat is still required.

•   The Setback is activated by closing/shorting the P+ and P- terminals using an external timer, 

control, or a switch.

Boost

Options: 

 Yes, No  

Default: No

SET

SET

/Settings>/Setback/Boost.

•   The morning Boost is designed to return the building to comfortable ambient temperatures 

after the night Setback period.  The SEQ-3 will accomplish this by running elevated water 
temperatures (will add Setback setting to calculated water temperature) for 30 minutes after 

the opening of the setback terminals P+ and P-.  That is, if the normal set point at a specific 

outdoor was 145˚F and the Setback setting was 20˚F, the boost will raise the system calculated 

temperature to 165˚F for 30 minutes after the setback.

Boost:

No
Yes

System and Outdoor Trim

Options: 

 From -20F

º

/-11

 to +20F

º

/+11

  

Default: 0F

º

/0

SET

SET

/<Maintenance>/Sys. Trm or  Out. Trim

•   The Heat-Timer sensors are very accurate.  However, sometime it might be beneficial to adjust 

the values to match and existing system.  The System and Outdoor Trim values adjust the System 

Sensor and Outdoor Sensor readings using positive or negative values.

System Trim:

+0 F

Outdoor Trim:

+0 F

Enable/Disable (TSTAT) Input

•   The SEQ-3 will provide heat only if the EXT- and EXT+ terminals are shorted.  If no external 

equipment or switch is connected to these terminals, leave the factory jumper 

installed.

•   

When the terminals are OPEN, the Target will display 

TSTAT OPEN

.

•   

Even if the EXT terminals are open, a call for DHW will energize the output relays based on the 
DHW Priority configuration.

•   

The Enable /Disable terminals can be used as a Summer/Winter switch when connected to an 
external switch.

T2

T3+

COM

T3- EXT+ EXT- P+ P- COM 24V

Enable/Disable

Wiring

NOTE:

 On a sensor fault while the Enable/Disable terminals are open, the control will follow the 

Enable /Disable state regardless of the sensor fault condition.

SYSTEM= 

55 F

TSTAT OPEN

SYSTEM= 

SHORT

TSTAT OPEN

Summary of Contents for DIGI-Elite SEQ-3

Page 1: ...ns where outdoor reset will not apply Two sensors are used one to monitor the outdoor temperature and one to monitor the circulating hot water temperature in the heating system When the outdoor temper...

Page 2: ...ergize If sequencing multiple stages or boilers are the primary function of the SEQ 3 the SEQ 3 will use the Purge Delay See Purge Delay on page 12 to start the lead boiler Then it will use the Reacti...

Page 3: ...the SEQ 3 marked 24VAC and COM Wiring Input Terminals Heating System Sensor HSS Installation T1 COM Locating HSS Place the Heating System sensor in the common header where it will register the output...

Page 4: ...put C See Output Mode Table on page 5 DHW Call terminals are dry contact N O terminals Wire an aquastat or another control to provide dry contact closure on the DHW Call terminals Wiring the Enable Di...

Page 5: ...rcuit initiating the Low Fire signal Then wire the two White wires to the High fire circuit The SEQ 3 does not source any output power to the boiler The relay makes when energized Wiring the System an...

Page 6: ...1 T2 COM COM T3 T3 EXT EXT P P COM 24VAC System Sensor Outdoor Sensor Enable Dry Contact Setback Timer Wiring 3 On Off Boilers Boiler 2 Blue Output B Boiler 3 White Output C Boiler 1 Yellow Output A D...

Page 7: ...Cutoff 60 F Min Tgt 120 F Max Tgt 200 F Back Cutoff 60 F Reset Ratio O S Custom 1 8 00 1 00 2 4 00 1 00 3 3 00 1 00 4 2 00 1 00 5 1 50 1 00 6 1 25 1 00 7 1 00 1 00 8 1 00 1 25 9 1 00 1 50 10 1 00 2 00...

Page 8: ...f F is selected all temperatures will display in Fahrenheit If C is selected all temperatures will display in Celsius DISPLAY UNIT F C Control Mode Options Outdoor Reset Set Point Default Outdoor Rese...

Page 9: ...48 F Cutoff 65 F Operating Menu Options Click SET Button Set Point Available when Startup Control Mode Set Point Options From 10 F 23 C to 230 F 110 C Default 70 F 21 C SET Set Point The Set Point op...

Page 10: ...et apply to all reset ratios including the custom reset ratio ones Offset Available when Startup Control Mode Outdoor Reset Options From 40 F 22 C to 40 F 22 C Default 0 F 0 C SET Out Reset Offset Off...

Page 11: ...Purge 0 0m Min Runtime 2m Lead A Rotate Time Back Lead Boiler A Lead Rotation Time Manual Rotation Period 24hrs Reaction Time 5m Purge Delay 1 0m Minimum Runtime 2m Reaction Time Options 1 to 10 minut...

Page 12: ...lable for Single Boiler Applications only Options From 1 F 1 C to 20 F 11 C Default 5 F 3 C SET Settings Diff Differential 5 F The Differential controls boiler cycling When there is a call for heat th...

Page 13: ...he night or on the weekends when building is not occupied but heat is still required The Setback is activated by closing shorting the P and P terminals using an external timer control or a switch Boos...

Page 14: ...ss the pair of Yellow wires If the wires are continuous the SEQ 3 is calling for the Heating System Pump to run and the problem is not with the SEQ 3 Check the power source to the pump and the pump to...

Page 15: ...Boiler SYS Pump DHW Pump SET C O R P O R A T I O N R SYSTEM 147F TARGET 150F DHW Pump Yellow Wires Output A Blue Wires Output B White Wires Output C C B A Piping 1 On Off Boiler System Pump DHW Pump...

Page 16: ...1 On Off 1 Pump 1 On Off 2 Pump 1 Lo Hi 1 Pump 2 On Off 1 Pump 3 On Off Lead Rotation Manual or Time from 1Hr to 999Hr Purge Delay from 0 0 to 10 0 minutes Reaction Time from 1 to 10 minutes Minimum R...

Reviews: