heat-timer DIGI-Elite SEQ-3 Assembly, Installation And Operation Instructions Download Page 10

10

•   If required:

 Adjust the RESET RATiO in cold weather.

  If the ambient building temperatures are too cold in cold weather, 

move the ratio to a higher selection.  That is, if 1.00 (O):1.00 (S) was initially selected, change the selection to 1.00 (O):1.25 (S).  
If the building temperatures are too warm in cold weather, move the ratio to a lower selection.  That is, if 1.00 (O):1.00 (S) was 
initially selected, change the selection to 1.25 (O):1.00 (S).

•   The Custom option gives the user the capability of creating a specialized Reset Ratio curve.  Setting two points on the Reset Ratio 

chart generates the customized curve.  Each point requires a System Water Temperature SYS and an Outdoor Temperature OD.  

The line connecting the two points will be the reset ratio.  The Offset, Minimum Target and Maximum Target settings will  still 
apply to the customized curve.

Set SYS Temp 1:

100 F

At OD Temp 1:

70 F

Outdoor Temperature (in °F)

70

60

50

40

20

30

0

-10

10

-20

120

140

130

150

160

170

180

100

110

W

ater 

T

emperature (in °F)

Custom Reset Ratio

Point1: System=120°F

Oudoor=60°F

Point2: System=170°F

Oudoor=0°F

Point1

Point2

Customized Reset Ratio

Max Target

Min Target

Custom Outdoor Reset Curve

Options: 

Sys Temp 1, 2 (-10ºF/21ºC) to (210ºF/99ºC) 

Default: 1(100ºF/38ºC), 2(171ºF/77ºC)

Options: 

Outdoor Temp 1, 2 (-10ºF/-23ºC) to (100ºF/38ºC) 

Default: 1(70ºF/21ºC), 2(0ºF/-18ºC)

SET

SET

/<Out. Reset>/Reset Ratio/Custom

•   For situations where the standard reset ratios do not provide the perfect building heat-loss 

equilibrium, the customized option can be used.

•   The Custom Reset Ratio is only available when 

Custom

 is selected from the Reset Ratio menu.  

It provides the user with the capability of assigning two points on the reset ratio diagram and use 
the line that connects those two points as the customized reset ratio curve.  Each of the two points 

will need a specific System and Outdoor Temperature to identify it on the diagram.

•   To Specify the first point, set Sys Temp 1, and OD Temp 1.  Then, set Sys Temp 2, and OD 

Temp 2, to set the second point on the curve.  The two points can be any where on the line, not 
necessarily at the ends.

•   The chart shows an example of a customized curve 6(O):5(S) that does not exist in the standard 

curve options.  If the outdoor temperature reaches 30ºF, the system target will be 145ºF.

•   Remember that the Min Target and Max Target apply to all reset ratios including the custom reset 

ratio ones.

Offset (Available when Startup Control Mode = Outdoor Reset)

Options: 

From -40ºF/-22

º

C to +40ºF/+22

º

 

Default: 0

º

F/0

º

C

SET

SET

/<Out. Reset>/Offset

Offset:

+0 F

•   The Offset setting adjusts the starting points of the Reset Ratio curves.  This means that, 

regardless of the Outdoor temperature or the Reset Ratio, when the Offset setting is changed, 
that change is directly added to or subtracted from the calculated Target.  For example, if the Set 
Point temperature was 130°F and the Offset was changed from 0° to +10°, then the Set Point 
temperature would increase to 140°F

•   If required: 

Adjust the Water Offset in mild weather

.  If the ambient building temperatures 

are too warm in the mild weather, decrease the Offset.  If the ambient building temperatures are 
too cold in the mild weather, increase the Offset.  The rule of thumb for baseboard radiation is 
to change the Offset 4°F for every 1°F you wish to change the building temperatures.  In radiant 
heat applications, change the Offset 1°F or 2°F for every 1°F you wish to change the building 
temperature.   See Type of Radiation in Building Table on page 2.

Outdoor Temperature (in °F)

70

60

50

40

20

30

0

-10

10

-20

120

140

130

150

160

170

180

100

110

W

ater 

T

emperature (in °F)

Target Offset

Offset=10°F

Reset Ratio=1.5 : 1.0

Reset Ratio

Max Target

Min Target

Reset Ratio + 10F Offset

Min Target=120°F

Max Target=170°F

Outdoor Cutoff

Options: 

 Off, 30

º

F/0

ºC

 to 75

º

F/25

º

C, On 

Default: 70ºF/21

º

C

SET

SET

/Set Point/Cutoff

 

in Set Point

SET

SET

/<Out. Reset>/Cutoff

 

in Reset

•   In Set Point Mode, if the outdoor sensor is installed, the Outdoor Cutoff setting screen will 

automatically appear after the temperature Set Point has been selected.

Cutoff:

 60 F

•   The Outdoor and Cutoff temperatures can be viewed from the default screen by clicking the Up or Down buttons.

•   When the outdoor temperature falls to the adjustable Outdoor Cutoff temperature, the SEQ-3 will control the System Pump and 

Boiler relays to provide heat.

•   When the outdoor temperature rises to the Outdoor Cutoff plus a 2°F differential, the SEQ-3 will turn the boilers off.  The System 

relay will remain energized for the Run-On delay then de-energize.  

•   The Outdoor Cutoff can be set from 30°F to 75°F.  In addition, the Setting can be set to ON or OFF.  If ON is selected, the System 

Relay will run regardless of the Outdoor temperature and the boilers will be active to hold the calculated water temperature.  If 
OFF is selected, the System and Boiler relays will always be off.

Summary of Contents for DIGI-Elite SEQ-3

Page 1: ...ns where outdoor reset will not apply Two sensors are used one to monitor the outdoor temperature and one to monitor the circulating hot water temperature in the heating system When the outdoor temper...

Page 2: ...ergize If sequencing multiple stages or boilers are the primary function of the SEQ 3 the SEQ 3 will use the Purge Delay See Purge Delay on page 12 to start the lead boiler Then it will use the Reacti...

Page 3: ...the SEQ 3 marked 24VAC and COM Wiring Input Terminals Heating System Sensor HSS Installation T1 COM Locating HSS Place the Heating System sensor in the common header where it will register the output...

Page 4: ...put C See Output Mode Table on page 5 DHW Call terminals are dry contact N O terminals Wire an aquastat or another control to provide dry contact closure on the DHW Call terminals Wiring the Enable Di...

Page 5: ...rcuit initiating the Low Fire signal Then wire the two White wires to the High fire circuit The SEQ 3 does not source any output power to the boiler The relay makes when energized Wiring the System an...

Page 6: ...1 T2 COM COM T3 T3 EXT EXT P P COM 24VAC System Sensor Outdoor Sensor Enable Dry Contact Setback Timer Wiring 3 On Off Boilers Boiler 2 Blue Output B Boiler 3 White Output C Boiler 1 Yellow Output A D...

Page 7: ...Cutoff 60 F Min Tgt 120 F Max Tgt 200 F Back Cutoff 60 F Reset Ratio O S Custom 1 8 00 1 00 2 4 00 1 00 3 3 00 1 00 4 2 00 1 00 5 1 50 1 00 6 1 25 1 00 7 1 00 1 00 8 1 00 1 25 9 1 00 1 50 10 1 00 2 00...

Page 8: ...f F is selected all temperatures will display in Fahrenheit If C is selected all temperatures will display in Celsius DISPLAY UNIT F C Control Mode Options Outdoor Reset Set Point Default Outdoor Rese...

Page 9: ...48 F Cutoff 65 F Operating Menu Options Click SET Button Set Point Available when Startup Control Mode Set Point Options From 10 F 23 C to 230 F 110 C Default 70 F 21 C SET Set Point The Set Point op...

Page 10: ...et apply to all reset ratios including the custom reset ratio ones Offset Available when Startup Control Mode Outdoor Reset Options From 40 F 22 C to 40 F 22 C Default 0 F 0 C SET Out Reset Offset Off...

Page 11: ...Purge 0 0m Min Runtime 2m Lead A Rotate Time Back Lead Boiler A Lead Rotation Time Manual Rotation Period 24hrs Reaction Time 5m Purge Delay 1 0m Minimum Runtime 2m Reaction Time Options 1 to 10 minut...

Page 12: ...lable for Single Boiler Applications only Options From 1 F 1 C to 20 F 11 C Default 5 F 3 C SET Settings Diff Differential 5 F The Differential controls boiler cycling When there is a call for heat th...

Page 13: ...he night or on the weekends when building is not occupied but heat is still required The Setback is activated by closing shorting the P and P terminals using an external timer control or a switch Boos...

Page 14: ...ss the pair of Yellow wires If the wires are continuous the SEQ 3 is calling for the Heating System Pump to run and the problem is not with the SEQ 3 Check the power source to the pump and the pump to...

Page 15: ...Boiler SYS Pump DHW Pump SET C O R P O R A T I O N R SYSTEM 147F TARGET 150F DHW Pump Yellow Wires Output A Blue Wires Output B White Wires Output C C B A Piping 1 On Off Boiler System Pump DHW Pump...

Page 16: ...1 On Off 1 Pump 1 On Off 2 Pump 1 Lo Hi 1 Pump 2 On Off 1 Pump 3 On Off Lead Rotation Manual or Time from 1Hr to 999Hr Purge Delay from 0 0 to 10 0 minutes Reaction Time from 1 to 10 minutes Minimum R...

Reviews: