INSTALLATION AND OPERATION INSTRUCTIONS

SEQ-3 DIGI-E

lItE

Hydronic Multi-Stage Boiler Control

R

Blue (Output B)

White (Output C)

Yellow (Output A)

Boiler

SYS

Pump

DHW

Pump

SET

®

C  O  R  P  O  R  A  T  I  O  N

R

SYSTEM =  

147F

TARGET =  

150F

C

2 Line Alphanumeric Display

Displays sensor values and 

menu settings

Output Lights indicate

output status

Display Section Locking Screws

Black (120VAC power)

®

 WARNING

This Heat-Timer control is strictly an operating control; 
it should never be used as a primary limit or safety 
control. All equipment must have its own certified 
limit and safety controls required by local codes. The 
installer must verify proper operation and correct any 
safety problems prior to the installation of this Heat-
Timer control.

Hot Water Control with Outdoor Reset, Set Point and 

DHW for Hydronic Applications

The SEQ-3 DIGI-SPAN Elite is a multi-boiler or multi-stage 
outdoor reset hydronic heating control. It establishes ambient 
comfort by varying the temperature of the heating system’s 
circulating hot water in response to changes in the outdoor 
temperature.  In addition, it provides an outdoor temperature 
based cutoff, heating system pump control, and domestic hot 
water (DHW) pump control.  Two unique features have been 
added to this control including a customized reset ratio curve.  
A Set Point option was added for applications where outdoor 
reset will not apply.

Two sensors are used, one to monitor the outdoor temperature 
and one to monitor the circulating hot water temperature in 
the heating system. When the outdoor temperature falls below 
the outdoor cutoff setting, the heating system is activated 
and the target water temperature is increased proportionally 
to satisfy the load. Should it get warmer outdoors, the target 
water temperature is automatically lowered by the control. If 
the outdoor temperature continues to rise to the outdoor cutoff 
setting then the heating system is turned off.

Because of the many different physical characteristics of 
buildings including the type of radiation; i.e., baseboard or 
radiant, the heat loss varies.  In one building, a 1-degree 
outdoors temperature change may require a change of 1 degree 
in heating water temperature; for another it may require a 
change of 2, 3, or even 4 degrees in order to gain the desired 
comfort level.  This is known as the Reset Ratio. The Reset 
Ratio chart shows the wide range of Reset Ratios available for 
the SEQ-3 in addition to the customized reset ratio. See page 2.

The installer fits the SEQ-3 to a specific building by adjusting 

the Reset Ratio curve.  With curve number 4 (2:1 reset ratio) 
a 2-degree change in outdoor temperature will change the 
circulating target temperature by 1 degree; at curve number 
11(1:3 reset ratio) an outdoor change of 1 degree will change 
the target temperature by 3 degrees.  Most buildings with 
baseboard radiation require a curve of 6, 7, or 8. Radiant heat 

Summary of Contents for DIGI-Elite SEQ-3

Page 1: ...ns where outdoor reset will not apply Two sensors are used one to monitor the outdoor temperature and one to monitor the circulating hot water temperature in the heating system When the outdoor temper...

Page 2: ...ergize If sequencing multiple stages or boilers are the primary function of the SEQ 3 the SEQ 3 will use the Purge Delay See Purge Delay on page 12 to start the lead boiler Then it will use the Reacti...

Page 3: ...the SEQ 3 marked 24VAC and COM Wiring Input Terminals Heating System Sensor HSS Installation T1 COM Locating HSS Place the Heating System sensor in the common header where it will register the output...

Page 4: ...put C See Output Mode Table on page 5 DHW Call terminals are dry contact N O terminals Wire an aquastat or another control to provide dry contact closure on the DHW Call terminals Wiring the Enable Di...

Page 5: ...rcuit initiating the Low Fire signal Then wire the two White wires to the High fire circuit The SEQ 3 does not source any output power to the boiler The relay makes when energized Wiring the System an...

Page 6: ...1 T2 COM COM T3 T3 EXT EXT P P COM 24VAC System Sensor Outdoor Sensor Enable Dry Contact Setback Timer Wiring 3 On Off Boilers Boiler 2 Blue Output B Boiler 3 White Output C Boiler 1 Yellow Output A D...

Page 7: ...Cutoff 60 F Min Tgt 120 F Max Tgt 200 F Back Cutoff 60 F Reset Ratio O S Custom 1 8 00 1 00 2 4 00 1 00 3 3 00 1 00 4 2 00 1 00 5 1 50 1 00 6 1 25 1 00 7 1 00 1 00 8 1 00 1 25 9 1 00 1 50 10 1 00 2 00...

Page 8: ...f F is selected all temperatures will display in Fahrenheit If C is selected all temperatures will display in Celsius DISPLAY UNIT F C Control Mode Options Outdoor Reset Set Point Default Outdoor Rese...

Page 9: ...48 F Cutoff 65 F Operating Menu Options Click SET Button Set Point Available when Startup Control Mode Set Point Options From 10 F 23 C to 230 F 110 C Default 70 F 21 C SET Set Point The Set Point op...

Page 10: ...et apply to all reset ratios including the custom reset ratio ones Offset Available when Startup Control Mode Outdoor Reset Options From 40 F 22 C to 40 F 22 C Default 0 F 0 C SET Out Reset Offset Off...

Page 11: ...Purge 0 0m Min Runtime 2m Lead A Rotate Time Back Lead Boiler A Lead Rotation Time Manual Rotation Period 24hrs Reaction Time 5m Purge Delay 1 0m Minimum Runtime 2m Reaction Time Options 1 to 10 minut...

Page 12: ...lable for Single Boiler Applications only Options From 1 F 1 C to 20 F 11 C Default 5 F 3 C SET Settings Diff Differential 5 F The Differential controls boiler cycling When there is a call for heat th...

Page 13: ...he night or on the weekends when building is not occupied but heat is still required The Setback is activated by closing shorting the P and P terminals using an external timer control or a switch Boos...

Page 14: ...ss the pair of Yellow wires If the wires are continuous the SEQ 3 is calling for the Heating System Pump to run and the problem is not with the SEQ 3 Check the power source to the pump and the pump to...

Page 15: ...Boiler SYS Pump DHW Pump SET C O R P O R A T I O N R SYSTEM 147F TARGET 150F DHW Pump Yellow Wires Output A Blue Wires Output B White Wires Output C C B A Piping 1 On Off Boiler System Pump DHW Pump...

Page 16: ...1 On Off 1 Pump 1 On Off 2 Pump 1 Lo Hi 1 Pump 2 On Off 1 Pump 3 On Off Lead Rotation Manual or Time from 1Hr to 999Hr Purge Delay from 0 0 to 10 0 minutes Reaction Time from 1 to 10 minutes Minimum R...

Reviews: