6
2-Way Motorized Valve with Feedback installation Manual
HT# 059301-00
A
ValVE DiMEnsiOns
Motorized Valves should be sized by Cv ratings
(the capacity factor or flow coefficient). This is
defined as the number of gallons of water at 60°F
that pass through a device with a one pound per
square inch pressure differential.
1
5
¼
B
c
a
7 ⅝
7 ½
2-Way single-seat Motorized Valve
Valve
size
catalog
number
Flow
Coefficient
cv
Dimensions
Mount
Body
trim
Est
shipping
Weight
Medium
temp
range °F
a
B
c
1 ½”
928051-50-VM
24
5 ¾
3 ¼
19”
NPT
Bronze
S. Steel
31
32 to 400
2”
928052-00-VM
40
6 ½“
3 ⅝ ”
19 ¼”
NPT
Bronze
S. Steel
35
32 to 400
2 ½”
928052-50-VM
65
9”
4 ¾”
20 ¾”
Flanged
Iron
Bronze
71
32 to 300
3”
928053-00-VM
90
10”
5 ⅜”
21 ⅝”
Flanged
Iron
Bronze
88
32 to 300
4”
928054-00-VM
170
13”
6 ⅜"
22 ⅝”
Flanged
Iron
Bronze
135
32 to 300
5”
928055-00-VM
280
15 ¾”
5 ¾"
23 ¼”
Flanged
Iron
Bronze
150
32 to 300
6”
928056-00-VM
360
17 ¾”
6 ½”
23 ⅞”
Flanged
Iron
Bronze
191
32 to 300
8”
928058-00-VM
680
16 ¼”
8 ⅞”
25 ⅛”
Flanged
Iron
Bronze
306
32 to 300
10”
928060-00-VM
960
20"
9 ⅞”
25 ⅞”
Flanged
Iron
Bronze
451
32 to 300
trOUBlEsHOOting
loud banging noise.
• Make sure that the valve is installed on a horizontal pipe.
• Make sure that no condensate will drain back against the valve when closed. This will cause the steam to flash the
condensate causing the banging when the valve opens.
actuator does not move.
• Make sure that the control is sending a moving signal to the actuator. The control must have a relay in each of the
outputs.
• Check that the transformer is operating properly and is its VA rating is equal to or higher than the actuator's VA