background image

2-Way Motorized Valve with Feedback installation Manual

 

 

3

HT# 059301-00 

A

Mounting alignment

•   To avoid valve problems, all dirt, metal shavings, and 

debris inside the piping must be removed or flushed out 

prior to installing the valve.

•   The preferred installation position of the valve and actuator 

is upright.  However, where space restrictions dictate, the 

valve assembly can be mounted diagonally.

•   The installation should account for an additional clearance 

of 4 to 6” above the actuator.  This space is needed for the 

manual operation of the actuator.  See "Actuator Manual 

Operation" on page 4.

 

Warning

Motorized Valves MUST NOT be installed upside down or horizontally.  

Warranty is void if valve installation position was installed incorrectly.

OK

OK

OK

OK

OK

OK

Valve actuator assembly

•   For smaller valves, it is usually easier to assemble the 

valve and actuator before the installation of the valve on 
the pipe.

•   For larger valves, install the valve in position prior to 

installing the actuator to the valve.

•   Thread and tighten the Valve Bushing to the valve.
•   Remove the Actuator Brass Brackets.  This should release 

the Stem Attachment.

•   Thread the Stem Attachment to the Valve Stem.  Make 

sure that it is tightened against the Stem Nut.

•   Mount the Actuator on top of the Valve.
•   Thread the Bushing Locknut to the Valve Bushing.  Make 

sure that the locknut’s beveled surface is facing the valve.

•   Manually close or open the actuator to bring the Stem 

Attachment to meet the bottom of the Actuator Shaft.  See 

"Actuator Manual Operation" on page 4.

•   Join the Stem Attachment and the Actuator Shaft using 

the Actuator Brass Bracket.  Make sure the Actuator Brass 

Bracket internal shape fits and locks Stem Attachment and 

Actuator Shaft securely.

•   For proper Actuator Brass Bracket operation, its 

protrusions must be at the bottom (closer to the valve).

•   Tighten the Actuator Brass Bracket screws and nuts using 

the provided Hex Wrench.

Valve Bushing

Actuator Brass Bracket

Stem Attachment

Stem Nut

Bushing Locknut

Stem

Actuator Shaft

Protrusion must
be at bottom

actuator lED

The actuator has two LEDs.  
•   A Green LED that lights when the actuator is moving its shaft downward.  It 

is labeled Down Limit.  

•   A Red LED that lights when the actuator is moving its shaft upward.  It is 

labeled Up Limit.

Up limit

Down limit

Summary of Contents for 928051-50-VM

Page 1: ...y control All equipment must have its own certified limit and safety controls required by local codes The installer must verify proper operation and correct any safety problems prior to the installati...

Page 2: ...ped per the following packing lists Valve package actuator package Valve Bushing Locknut Actuator Actuator Brass Bracket with two hex screws and two nuts Hex Wrench 5 24 VAC Transformer Stem Nut Stem...

Page 3: ...the valve Remove the Actuator Brass Brackets This should release the Stem Attachment Thread the Stem Attachment to the Valve Stem Make sure that it is tightened against the Stem Nut Mount the Actuato...

Page 4: ...oating type signal R W B The actuator must be powered using the provided 24 VAC transformer A single transformer can only power a single actuator The transformer is supplied with every complete valve...

Page 5: ...SENSORS INPUTS ROUTE SENSOR AND AUXILIARY WIRES THROUGH THIS KNOCKOUT ONLY SYS AUX CLOCK OPTION 1 T T Cycle On 5 60m Val 45 Day OD 31 o F SYS 148 o F OUTPUT T T C O R P O R A T I O N R 2 3 4 5 9 10 12...

Page 6: ...Bronze 88 32 to 300 4 928054 00 VM 170 13 6 22 Flanged Iron Bronze 135 32 to 300 5 928055 00 VM 280 15 5 23 Flanged Iron Bronze 150 32 to 300 6 928056 00 VM 360 17 6 23 Flanged Iron Bronze 191 32 to...

Page 7: ...ted to the heating system boilers or electrical power system that is required for proper operation of any controls or other equipment installed by Heat timer corporation or any contractor third party...

Page 8: ...actuator for manual operation Mounting Vertical above center line of valve Feedback Signal 1K ohm Terminals 8 9 10 2 Way Valve Specifications Body 1 2 Valves ANSI B16 15 Bronze 250lb Threaded NPT 2 1...