background image

22

!

B.  Installing Vent Components

After determining which set of starting collars will be used

(top or rear), follow venting instructions accordingly.

Venting Out the Rear Vent

Remove the installed rear seal cap from the rear starting

collars by cutting the strap at each end. (see Figure 15).

Follow the vent configuration tables accordingly.
Remove the insulation from the 

REAR

 five inch flue, pull

the heat shield out from outside of the firebox.

WARNING: THE TOP HEAT SHIELD (INSIDE

THE FIREBOX) MUST REMAIN ATTACHED IF

THE VENT SYSTEM IS ATTACHED TO THE

REAR STARTING COLLARS. SEE FIGURE 15.

Venting Out the Top Vent

Remove the two screws in the top vent collar seal cap and

remove the top vent collar seal cap and  two pieces of  in-

sulation inside the top two starting collars (See Figure 15).
Remove the heat shield from inside the 

TOP

 five inch flue

from outside of the firebox.
The glass must be taken off again for positioning the logs

when the unit is finally installed in place and finished around

it. Re-install the glass door. Attach vent system to the top

starting collars.

!

   Figure 16.  Attaching the First Vent Component

                     to the Starting Collars

WARNING: A 3/8 INCH (9.5 MM) BEAD OF

STOVE CEMENT MUST BE PLACED AROUND

THE 5 INCH (127 MM) FIREPLACE STARTING COL-

LAR BEFORE ATTACHING THE FIRST VENT COM-

PONENT. FAILURE TO SEAL THIS JOINT MAY

CAUSE THE FIREPLACE TO OPERATE IMPROPERLY.

STARTING

COLLAR

STOVE

SEALANT

BEAD

1 INCH

(25.4mm)

 FIRST VENT

COMPONENT

!

1.   Attach the First Vent Component to the

     Starting Collars

To attach the first vent component to the starting collars of

the fireplace:

• Apply a 3/8 inch (9.5mm) bead of stove cement around

the 5 inch (127mm) fireplace starting collar.

• Make sure that the fiberglass rope gasket supplied with

the fireplace seals between the first 8-5/8 inch (219mm)

vent component and the outer fireplace wrap.

• Lock the vent components into place by sliding the con-

centric pipe sections with four (4) equally spaced interior

beads into the fireplace collar or previously installed com-

ponent end with four (4) equally spaced indented sections.

• When the internal beads of each 8-5/8 inch (219mm)

outer pipe line up, rotate the pipe section clockwise about

one-quarter (1/4) turn. The vent pipe is now locked together.

• The first 90° elbow installed in the vent system of a rear

venting fireplace 

MUST BE

 in a vertical position.

WARNING: ENSURE THAT THE FIBERGLASS

ROPE GASKET SUPPLIED WITH THE

FIREPLACE SEALS BETWEEN THE FIRST VENT

COMPONENT AND THE OUTER FIREPLACE WRAP.

If the installation is for a termination cap attached directly

to the fireplace, skip to the sections, 

Install Firestops

 and

Vent Termination

.

WARNING:  THE REAR VENT COLLAR SEAL

CAP MUST REMAIN ATTACHED TO THE REAR

VENT COLLARS IF THE VENT SYSTEM IS AT-

TACHED TO THE TOP STARTING COLLARS.
WARNING: FAILURE TO REMOVE  INSULATION

IN THE SET OF COLLARS YOU ARE USING

COULD CAUSE A FIRE.
WARNING: YOU MUST LEAVE THE INSULATION

IN PLACE IN THE SET OF COLLARS YOU ARE

NOT USING.

If your vertical vent component is over 10 feet, you may

want to install the vertical baffle (located in the bag containing

the install manual) to improve flame appearance. Center

the vertical baffle on the 5” flue being used, and with self

tapping screws secure the baffle to the inside of the firebox.

Figure 15

Insert screwdriver

or similar object

here to remove cap.

CUT

HERE

Venting Out Rear

Venting Out Top

!

!

!

HEAT

SHIELD

DISCARD

 INSULATION

and

HEAT SHIELD

HEAT

 SHIELD

INSULATION

DISCARD  BOTH

PIECES and

HEAT SHIELD

SEAL 

CAP

SEAL

CAP

Summary of Contents for 6000SEB

Page 1: ...ERENCE 1 This appliance may be installed in an af termarket permanentlylocated manufac tured mobile home wherenotprohibited by local codes 2 Thisapplianceisonlyfor usewiththetype of gas indicated on t...

Page 2: ...he installation FAILURE TO FOLLOW these installation instructions may result in a possible fire hazard and will void the warranty Prior to the first firing of the fireplace READ the Using Your Firepla...

Page 3: ...nt System 16 A Vent System Approvals 16 B Installing Vent Components 22 C Vent Termination 26 Step 4 Positioning Leveling and Securing the Fireplace 29 Step 5 The Gas Control Systems 29 Step 6 The Gas...

Page 4: ...e CSAC22 1 Canadian Electric Code in Canada These models may be installed in a bedroom or bed sitting room in the U S A and Canada 1Approvals and Codes High Altitude Installations U L Listed gas firep...

Page 5: ...in place Remove the two screws holding the pilot assembly to the burner 7 Remove the burner assembly from the firebox 8 Replace the burner orifice with the orifice included in the plastic manual bag B...

Page 6: ...installed The vent system configuration to be used Gas supply piping Electrical wiring Framing and finishing details Whether optional accessories devices such as a fan wall switch or remote control ar...

Page 7: ...he fireplace is one inch 25 mm The back of the fireplace may be recessed 21 1 2 inches 546 mm into combustible construction Minimum Clearances from the Vent Pipe to Combustible Materials Inches mm Ver...

Page 8: ...ng material The dia gram below shows framing reference dimensions CAUTION MEASURE FIREPLACE DIMENSIONS AND VERIFY FRAMING METHODS AND WALL COVERING DETAILS BEFORE FRAMING 1 2 CLEARANCE FROM BACK OF FI...

Page 9: ...T EACH JOINT DV 36D 5 3 4 146mm 8 3 4 222mm 11 3 4 298mm DV 48D 7 3 8 187mm 6 5 32 156mm 11 5 8 295mm 8 5 8 220mm 8 1 2 216mm 6 7 16 164mm 11 1 16 281mm 6 1 2 165mm 8 1 2 216mm 5 1 16 129mm 8 5 8 220m...

Page 10: ...onfiguration used Terminations Kits Identifying Vent Components The vent systems installed on this gas fireplace may in clude one two or three 90 elbow assemblies The rela tionships of vertical rise t...

Page 11: ...ing NOTE On vertical venting configurations where the vertical component is over 10 feet you may want to install the vertical baffle included in the manual bag assembly to improve flame appearance see...

Page 12: ...Venting with One 90 Elbow VENTING WITH ONE 1 90 ELBOW VENTING WITH ONE 1 90 ELBOW V FT H FT 1 MIN 305mm 5 MAX 1 52m 2 MIN 610mm 10 MAX 3 1m 3 MIN 914mm 15 MAX 4 65m 4 MIN 1 22m 20 MAX 6 2m V H 40 MAX...

Page 13: ...914 mm 6 MAX 1 86 m 15 MAX 4 65m 4 MIN 1 22 m 8 MAX 2 48 m 20 MAX 6 2m V H H1 40 MAX 12 4 m H 8 MAX 2 48 m H H1 20 MAX 6 2m Figure 12 Venting with Two 90 Elbows VENTING WITH TWO 2 90o ELBOWS V FT H H...

Page 14: ...914mm 6 MAX 1 86m 15 MAX 4 65m 4 MIN 1 22m 8 MAX 2 48m 20 MAX 6 2m V H H1 H2 40 MAX 12 4 m H 8 MAX 2 48 m H H1 H2 20 MAX 6 2 m V H H H1 H2 1 MIN 305mm 2 MAX 610mm 5 MAX 1 52m 2 MIN 610mm 4 MAX 1 22m...

Page 15: ...m 3 MIN 914mm 15 MAX 4 65m 4 MIN 1 22m 20 MAX 6 2m NOTE H H1 20 MAX 6 2m V V1 H H1 40 MAX 12 4m V FT H H1 FT 1 MIN 305mm 5 MAX 1 52m 2 MIN 610mm 10 MAX 3 1m 3 MIN 914mm 15 MAX 4 65m 4 MIN 1 22m 20 MAX...

Page 16: ...inch 127mm fireplace starting collar Make sure that the fiberglass rope gasket supplied with the fireplace seals between the first 8 5 8 inch 219mm vent component and the outer fireplace wrap Lock the...

Page 17: ...und the preceding component s vertical axis If an el bow does not end up in a locked position with the pre ceding component attach with a minimum of two 2 sheet metal screws Figure 18 CORRECT INCORREC...

Page 18: ...ops for horizontal runs that pass through either interior or exterior walls Cut a 12 inch by 12 inch 305mm X 305mm hole through the wall NOTE The center of the hole is one 1 inch 25 4mm above the cent...

Page 19: ...11 inch 280mm X 280mm hole through the ceiling using the centerpoint previously marked Frame the hole with framing lumber the same size as the ceiling joists Figure 24 Ceiling Firestop Ceiling Side If...

Page 20: ...of the wall firestop to secure the vent pipe in place For trapezoidal cap termination kits Using screws secure the cap to the exterior wall through the flanges in the cap Figure 26 Round Trapezoid Ter...

Page 21: ...oor that may be opened C 9 U S A 12 Canada clearance to permanently closed window D 18 vertical clearance to ventilated soffit located above the termi nal within a horizontal distance of 2 feet 60 cm...

Page 22: ...FOLLOWING DIAGRAM FOR MINIMUM HEIGHTS PROVIDED THE TERMI NATION CAP IS AT LEAST TWO 2 FEET FROM A VERTICALWALLAND 2 FEET BELOWA HORIZON TAL OVERHANG NOTE This also pertains to vertical vent systems i...

Page 23: ...n DSI Standing Pilot Ignition System This system includes millivolt control valve standing pilot thermopile thermocouple flame sensor and piezo ignitor WARNING 110 120 VAC MUST NEVER BE CONNECTED TO A...

Page 24: ...vent cold air infiltration Open the fireplace lower grille insert the gas supply line throughthegaslinehole andconnectittotheshut offvalve When attaching the pipe support the control so that the lines...

Page 25: ...itch in the desired position on a wall Run a maximum of 25 feet 7 8 m or less length of 18 A W G minimum wire and connect it to the fireplace ON OFF switch pigtails WARNING DO NOT CONNECT 110 120 VAC...

Page 26: ...8 m or less of 16A W G minimum wire and connect it to the fireplace ON OFF switch pigtails CAUTION LABEL ALL WIRES PRIOR TO DISCONNEC TION WHEN SERVICING CONTROLS WIRING ERRORS CANCAUSEIMPROPERANDDAN...

Page 27: ...N IF JOINTS BETWEEN THE FINISHED WALLS AND THE FIREPLACE SURROUND TOP AND SIDES ARE SEALED A 300 F MINIMUM SEALANT MATE RIAL MUST BE USED THESE JOINTS ARE NOT RE QUIRED TO BE SEALED ONLY NON COMBUSTIB...

Page 28: ...slightly to avoid excessive flame impingement Step 10 Installing Trim Logs and Ember Material Placing the Ember Material Ember material is shipped with this gas fireplace The bag labeled Golden Ember...

Page 29: ...ll help to cure the chemicals used in the paint and logs Step 12 Lighting the Fireplace You ve reviewed all safety warnings you ve checked the fireplace for gas leaks you know the vent system is unobs...

Page 30: ...Qualified service technician Task Brush or vacuum the control compartment fireplace logs and burner areas surrounding the logs Checking Flame Patterns Flame Height Frequency Periodically By Qualified...

Reviews: